HOLD OP! All work detailed in these instructions must be done by a qualified technician.
Specifikationer
- Emne: Danfoss ERC112D Universal Programming Instructions
- Dato: 28. februar 2024
- Modeller / Berørte dele: Temperature Control Kit P#848288
- Voltages: Alle Voltages
Overview
- Universal Danfoss ERC112D temperaturstyringssæt indeholder alle komponenter, der potentielt er nødvendige for at reparere en temperaturstyringsfejl. Brugen af komponenter vil variere afhængigt af reparationen.
- The replacement control is preprogrammed for universal use and may require changes to parameter settings based on model type and application.
- Some component operations may change with new universal settings.
KUN CVM/GDM/TCR/TD/TMC/TUC/TWT KØLESKABE: Ingen programmeringsændringer nødvendige.
Andre instruktioner
Follow the links/QR codes for digital copies of instructions associated with this kit.
Før du begynder
Hvis sætpunktet justeres til 5 °C eller højere, skal den medfølgende advarselsmærkat om farlige fødevarer placeres under serienummermærkatet inde i apparatet, som vist i fig. 1. Denne etiket underretter brugerne om, at apparatet er indstillet til at opretholde en temperatur, der ligger uden for NSF's retningslinjer for opbevaring af letfordærvelige fødevarer. 
Installation
KUN TOAM-72: Kontroller, at den tredje afrimningssonde fungerer. Genbrug sonden, hvis den fungerer korrekt. Hvis den fungerer forkert, se afsnittet "Kun TOAM-72 — Tredje afrimningssonde" (s. 4).
- FORSIGTIGHED! Electrical shock or burn hazard. Powering off an electronic control does not remove power from all components. Unplug the unit or turn off the power supply before installation.
- FORSIGTIGHED! Sharp edges. Take care when installing, cleaning, servicing, and/or maintaining the equipment.

Kontrolprogramstruktur
- Parametre er arrangeret i parametergrupper efter deres formål (se fig. 2a). For eksempelampAlle ventilatorfunktioner findes i parametergruppen FAn (se fig. 2b).
- For yderligere information om navigering i styreprogrammeringen, se afsnittet "Juster parametre".

Unlock Control
- Press any button to show the current lock status.

- If the display shows unL, proceed to “Enter Password” section. If the display shows Loc, press and hold the back button
and the up arrow
until the display shows unL.
NOTE: The control will lock after 60 seconds of inactivity.

- Proceed to “Change System of Measure,” “Enter Password,” or “Adjust the Set Point” sections.
Ændring af målesystem
Displayet kan vise temperaturen i enten Fahrenheit eller Celsius.
- Unlock the display. See “Unlock Control” section.
- Tryk på tilbage-knappen


Indtast adgangskode
NOTE: After three (3) consecutive incorrect password entries, the control will lock for 15 minutes.
- Push and hold both the up
arrows until the display shows PAS.
- Wait for the display to show 000.

- Press the down arrow until the display shows 989.

- Press okay
to show PS2.
- Wait for the display to show tHE.

- Proceed to “Adjust Parameters” or “Adjust the Set Point” sections.
Danfoss ERC112D Programmeringsvejledning

Juster parametre
- See table 1 (next page) for required parameter adjustments before proceeding.
- Figurerne viser, hvordan man i parametergruppen FAn ændrer parameteren FCt til parameterindstillingen FAo (også vist i fig. 3). Denne ændring af indstillingen er muligvis ikke nødvendig for din applikation.
NOTE: Incorrect parameter settings can lead to improper appliance operation and unsafe product temperatures.
- Unlock the control. See “Unlock Control” section.
NOTE: The control will lock after 60 seconds of inactivity. - Enter the password and enter the programming. See “Enter Password” section.

- Tryk på op
arrow as needed to show the desired parameter group.
- Press okay
to select the parameter group.
- Press the up or down arrow as needed to show the desired parameter.

- Press okay to select the parameter.

- Press the up or down arrow as needed to show the desired parameter setting.

- Press okay to select the parameter setting. The display will return to the selected parameter.

- Tryk på tilbage-knappen
to return to the selected parameter group. Repeat steps 3-8 as needed to adjust parameter settings per table 1 (next page).
- Exit the programming.
- Press the back button twice (x2) OR
- Leave the control inactive for 30 seconds
Justering af parameterindstillinger
- Tabel 1 viser, hvordan du ændrer det universelle styreprogram, så det passer til din specifikke model og anvendelse.
- Find din modeltype, og skift derefter parameterindstillingerne til de viste værdier. Se afsnittet "Juster parametre" for instruktioner om ændring af parameterindstillinger.
- FREEZER MODELS ONLY: Be sure to change duA before adjusting any other parameter setting.
Efter ændring af programmeringen skal du sørge for at justere sætpunktet for applikationen i henhold til tabel 2.
KUN TOAM-72 — Tredje afrimningssonde
- Kontroller den tredje afrimningssondes funktion. Genbrug sonden, hvis den fungerer korrekt.
- Hvis den fungerer forkert, skal du fjerne en tand (se fig. 4) fra den medfølgende afrimningssonde.
- For en ekstra afrimningssonde, i USA eller Canada, kontakt venligst vores reservedelsafdeling på 800-424-8783 or Deleforespørgsler@TrueMfg.com. For all other locations, please see the contact information.

| Model Type | Tabel 1. Nødvendige ændringer af parameterindstillinger efter model | ||||||||||||||||||||
| Parametergruppe | det | Ventilator | dEF | CoP | ASi | ||||||||||||||||
| Parameter | SPr | diF | duA* | FCt | di | dAi | dit | dAt | Ftd | doC | dEt | dE2 | dt2 | dSo | CSt | S3A | S4A | diC | o2C | o4C | |
| CPT | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | EuA | – | – | – | – | |
| CVM | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| FLM (Freezer)
(1 Cond Unit) |
– | – | du2 | – | – | – | – | – | 0°F (-17.8°C) | – | – | – | – | – | – | – | – | – | – | – | |
| GDIM | – | – | du2 | – | – | – | – | – | 12°F (-11.1°C) | – | -10°F (-23.3°C) | – | – | – | – | – | – | dCo | – | – | |
| GDM (køleskab) | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | ||
| GDM (Vin) | – | – | – | FAo | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| GDM (Freezer)
(1 Cond Unit) |
– | – | du2 | – | – | – | – | – | 0°F (-17.8°C) | – | – | – | – | – | – | – | – | dCo | – | – | |
| GDM-LTF
(1 Cond Unit) |
– | – | du2 | – | – | – | – | – | 0°F (-17.8°C) | – | – | -40°F (-40°C) | – | – | – | – | – | dCo | – | – | |
| Glaskølere | – | – | du2 | – | – | – | – | – | 0°F (-17.8°C) | – | – | – | – | – | – | – | – | – | – | – | |
| T-serien (køleskab) | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | dCo | – | – | |
| T-serien (fryser) (1 køleenhed) | – | – | du2 | – | – | – | – | – | 0°F (-17.8°C) | – | – | – | – | – | – | – | – | dCo | – | – | |
| TBR | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| TBR (Vin) | – | – | – | FAo | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| TCF | – | – | du2 | – | – | – | – | – | 0°F (-17.8°C) | – | – | – | 50°F (10°C) | – | – | – | – | – | – | – | |
| TCGG | – | – | – | – | – | – | 75 | 90 | – | 180 | -13°F (-25°C) | – | – | – | – | – | – | – | – | – | |
| TCR | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| TD | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| TDM | – | – | – | FAo | – | 6 | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| TDM-CW | – | – | – | FAo | – | 6 | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| TFP | – | 3°F (1.7°C) | – | FAo | – | 3 | 2 | – | – | – | 5°F (-15°C) | – | – | – | 2 | – | – | – | – | – | |
| TGN (køleskab) | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | dCo | – | – | |
| TGN (Fryser) | – | – | du2 | – | – | – | – | – | 0°F (-17.8°C) | – | – | – | – | – | – | – | – | dCo | – | – | |
| THAC | – | – | – | FA0 | – | 1 | – | – | – | – | – | – | – | af | – | – | – | – | – | – | |
| Model Type | Tabel 1. Nødvendige ændringer af parameterindstillinger efter model | ||||||||||||||||||||
| Parametergruppe | det | Ventilator | dEF | CoP | ASi | ||||||||||||||||
| Parameter | SPr | diF | duA* | FCt | di | dAi | dit | dAt | Ftd | doC | dEt | dE2 | dt2 | dSo | CSt | S3A | S4A | diC | o2C | o4C | |
| TMC | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| TOAM-30/36 | – | – | – | FAo | – | 1 | – | – | – | – | – | – | – | af | – | – | – | – | – | – | |
| TOAM-48 | – | – | – | FAo | – | 1 | – | – | – | – | – | – | – | af | – | EuA | – | – | – | SCC | |
| TOAM-72 | – | – | – | FAo | – | 1 | – | – | – | – | – | – | – | af | – | EuA | EuA | – | tCC | SCC | |
| TPP | – | 3°F (1.7°C) | – | FAo | – | 3 | 2 | – | – | – | 5°F (-15°C) | – | – | – | 2 | – | – | – | – | – | |
| TRCB | – | – | – | FAo | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| TSSU | – | 3°F (1.7°C) | – | FAo | – | 3 | 2 | – | – | – | 5°F (-15°C) | – | – | – | 2 | – | – | – | – | – | |
| TUC/TWT (køleskab) | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| TUC/TWT (Vin) | – | – | – | FAo | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| TUC/TWT (Fryser) | – | – | du2 | – | – | – | – | – | 0°F (-17.8°C) | – | – | – | – | – | – | – | – | – | – | – | |
| TUFADA | 1 | – | du2 | – | 180 | 8 | – | – | 0°F (-17.8°C) | 240 | – | -25°F (-31.7°C) | – | – | 6 | – | – | – | – | – | |
| TURADA | 1 | – | – | – | 180 | 8 | – | – | – | 240 | 9°F (-12.8°C) | – | – | – | 6 | – | – | – | – | – | |
| TUWADA | 1 | – | – | FAo | 180 | 8 | – | – | – | 240 | 9°F (-12.8°C) | – | – | – | 6 | – | – | – | – | – | |
Juster sætpunktet (efter programmering)
- Changing the set point adjusts the appliance operation to
- keep optimal product temperature. See table 2 for factory-recommended temperature set point adjustments based on model.
NOTE: Adjust the temperature set point after making programming adjustments.

NOTE: The best set point for your application may vary from the factory-recommended setting.
- Unlock the control. See “Unlock Control.”
NOTE: The control will lock after 60 seconds of inactivity. - Tryk på op
arrow to show the current setting.
- Press the up or down arrow until the display shows the desired set point.

- Leave the display inactive until it shows the current appliance temperature.

| Tabel 2. Factory-Recommended Temperatur setpunkter | |
| Model | Sætpunkt |
| CPT | Ingen yderligere ændringer nødvendige |
| CVM | Ingen yderligere ændringer nødvendige |
| FLM (Freezer)
(1 Cond Unit) |
Ingen yderligere ændringer nødvendige |
| GDIM | 18°F (-7.8°C) |
| GDM (køleskab) | Ingen yderligere ændringer nødvendige |
| GDM (Rødvin) | 55°F (12.8°C) |
| GDM (Hvidvin) | 45°F (7.2°C) |
| GDM (Freezer)
(1 Cond Unit) |
Ingen yderligere ændringer nødvendige |
| GDM-LTF
(1 Cond Unit) |
-15°F (-26.1°C) |
| Glaskølere | 4°F (-15.5°C) |
| T-serien (køleskab) | Ingen yderligere ændringer nødvendige |
| T-serien (fryser) (1 køleenhed) | Ingen yderligere ændringer nødvendige |
| TBR | 34°F (1.1°C) |
| TBR (Rødvin) | 55°F (12.8°C) |
| TBR (Hvidvin) | 45°F (7.2°C) |
| TCF | Ingen yderligere ændringer nødvendige |
| TCGG | Ingen yderligere ændringer nødvendige |
| TCR | Ingen yderligere ændringer nødvendige |
| TD | Ingen yderligere ændringer nødvendige |
| TDM | 38°F (3.3°C) |
| TDM-CW | 55°F (12.8°C) |
| TFP | 34°F (1.1°C) |
| TGN | Ingen yderligere ændringer nødvendige |
| THAC | 38°F (3.3°C) |
| TMC | Ingen yderligere ændringer nødvendige |
| TOAM | 38°F (3.3°C) |
| TPP | 34°F (1.1°C) |
| TRCB | Ingen yderligere ændringer nødvendige |
| TSSU | 34°F (1.1°C) |
| TUC/TWT (køleskab) | Ingen yderligere ændringer nødvendige |
| Tabel 2. Factory-Recommended Temperatur setpunkter | |
| Model | Sætpunkt |
| TUC/TWT (Rødvin) | 55°F (12.8°C) |
| TUC/TWT (Hvidvin) | 45°F (7.2°C) |
| TUC/TWT (Fryser) | Ingen yderligere ændringer nødvendige |
| TUFADA | Ingen yderligere ændringer nødvendige |
| TURADA | Ingen yderligere ændringer nødvendige |
| TUWADA | 55°F (12.8°C) |
Spørgsmål eller bekymringer
For mere information, kontakt venligst vores tekniske serviceteam. Se kontaktoplysninger nedenfor.
Kontakt os
- Nordamerika – USA, Canada og Caribien
- Garantitelefon: +1 855 878 9277
- Garanti fax: +1 636 980 8510
- Garanti e-mail: WarrantyInquiries@TrueMfg.com
- Teknisk telefon: +1 855 372 1368
- Teknisk e-mail: Service@TrueMfg.com
- 7:00-6:00 CST mandag-fredag;
- 8-00 lørdag
- Mexico
- Telefon: + 52 555 804 6343 / 44
- Service-MexicoCity@TrueMfg.com
- 9:00-5:30 MF
- Latinamerika
- Telefon: + 52 555 804 6343 / 44
- ServiceLatAm@TrueMfg.com
- 9:00-5:30 MF
- Storbritannien, Irland, Mellemøsten, Afrika og Indien
- Telefon: +44 (0) 800 783 2049
- Service-EMEA@TrueMfg.com
- 8:30-5:00 MF
- Australien
- Telefon: +61 2 9618 9999
- Service-Aus@TrueMfg.com
- 8:30-5:00 MF
- Den Europæiske Union og Commonwealth af Uafhængige Stater
- Telefon: +41 61 563 0705
- Service-EMEA@TrueMfg.com
- 8:00-5:00 MF
BYGNING AF DET FINESTE ERHVERVSKØLESKAB — Sandt nok, "Det bedste af de kolde"
FAQ
What should I do if the control locks after inactivity?
If the control locks after 60 seconds of inactivity, press any button to check the lock status. If it shows 'Loc,' press and hold the back button and up arrow until 'unL' appears.
How can I unlock the control?
To unlock the control, follow the steps mentioned in the 'Enter Password' section of the manual.