Danfoss-LOGO

Danfoss 80G8280 Ejector Controller

Danfoss-80G8280-Ejector-Controller-PRODUCT

Produktinformation

  • The EKE 80 Ejector Controller receives input signals from Danfoss controllers AK-PC 782A/AK-PC 782B or a PLC.
  • It can control multiple HP/LP ejectors and up to 2 modulating control valves to facilitate the ‘lift’ of the MT suction pressure, thereby decreasing energiforbrug.
  • The EKE 80 drive controller is suitable for both new and retrofit systems.
  • Identify the connectors on the EKE 80 Ejector Controller according to the manual.
  • Connect the necessary input signals from the Danfoss controllers or PLC to the designated connectors on the EKE 80.
  • Ensure proper power supply connection to the controller.
  • Follow the specific wiring instructions for connecting HP/LP ejectors and modulating control valves.
  • Test systemet for at sikre korrekt funktionalitet.
  • Refer to the manual for detailed information on connecting various components to the EKE 80 Ejector Controller.
  • Use the specified connectors and follow the wiring guidelines provided.
  • Power on the EKE 80 Ejector Controller.
  • Set the desired parameters using the interface connected to the controller.
  • Monitor the system performance and make adjustments as needed for optimal efficiency.

Indledning

  • The EKE 80 Ejector Controller receive inputs signals from the Danfoss controllers AK-PC 782A/AK-PC 782B or a PLC.
  • It can control multiple HP/LP ejectors and up to 2 modulating control valves to facilitate the ‘lift’ of the MT suction pressure and thereby decrease energy consumption.
  • The EKE 80 drive controller is suitable for both new and retrofit systems.

Identifikation

Danfoss-80G8280-Ejector-Controller-FIG-2

Ansøgning example

Danfoss-80G8280-Ejector-Controller-FIG-3

Generelle funktioner og advarsler

Plasthusfunktioner

  • DIN-skinnemontering i overensstemmelse med EN 60715
  • Selvslukkende V0 i henhold til IEC 60695-11-10 og glødende/varmtrådstest ved 960 °C i henhold til IEC 60695-2-12
  • Kugletest: 125 °C i henhold til IEC 60730-1. Lækstrøm: ≥ 250 V i henhold til IEC 60112

Andre funktioner

  • Driftsforhold CE: -20T60 / UL: 0T50, 90 % RF ikke-kondenserende
  • Opbevaringsforhold: -30T80, 90% RH ikke-kondenserende
  • Skal integreres i apparater i klasse I og/eller II
  • Beskyttelsesindeks: IP40 kun på frontcoveret
  • Periode med elektrisk belastning på tværs af isolerende dele: lang
  • Velegnet til brug i miljøer med en forureningsgrad på 2
  • Kategori af modstandsdygtighed over for varme og brand: D
  • Immunitet mod voltage surges: category II, category III for versions without display
  • Softwareklasse og struktur: klasse A

Overholdelse
CE-mærke

  • Dette produkt er designet til at overholde følgende EU-standarder:
  • Lav voltage direktiv LVD 2014/35/EU:
    • EN60730-1: 2011 (Automatisk elektrisk styring til husholdningsbrug og lignende. Generelle krav)
    • EN60730-2-9: 2010 (særlige krav til temperaturfølende kontroller)
  • Elektromagnetisk kompatibilitet EMC-direktiv 2014/30/EU:
  • EN 61000-6-3: 2007 +A1: 2011 (Emissionsstandard for boliger, kommercielle og letindustrielle miljøer)
  • EN 61000-6-2: 2005 (Immunitet for industrielle miljøer)
  • RoHS-direktiv 2011/65/EU og 2015/863/EU:
    • EN50581:2012
  • Kina RoHS
    UL-godkendelse:
  • UL file E31024

Generelle advarsler

  • Enhver brug, der ikke er beskrevet i denne manual, betragtes som forkert og er ikke autoriseret af producenten
  • Kontroller, at installations- og driftsbetingelserne for enheden overholder dem, der er specificeret i manualen, især hvad angår forsyningsvolumentage og miljøforhold
  • This device contains live electrical components therefor,e all the service and maintenance operations must be performed by qualified personnel
  • Enheden kan ikke bruges som sikkerhedsanordning
  • Ansvaret for skader eller skader forårsaget af forkert brug af apparatet påhviler udelukkende brugeren

Installationsadvarsler

  • Monteringsposition anbefales: lodret
  • Installationen skal udføres i overensstemmelse med landets lokale standarder og lovgivning
  • Brug altid de elektriske forbindelser med enheden afbrudt fra hovedstrømforsyningen
  • Afbryd alle elektriske forbindelser, før du udfører nogen form for vedligeholdelse på enheden
  • Af sikkerhedsmæssige årsager skal apparatet monteres inde i et elektrisk panel uden adgang til strømførende dele
  • Udsæt ikke enheden for kontinuerlige vandspray eller for en relativ luftfugtighed på mere end 90 %.
  • Avoid exposure to corrosive or pollutant gases, natural elements, environments where explosives or mixes of fiammable gases are present, dust, strong vibrations or shock, large and rapid fluctuations in ambient temperature that in combination with high humidity,y can condensate, strong magnetic and/or radio interference (e.g., transmitting antennae)
  • Vær opmærksom på den maksimale strøm for hvert relæ og stik ved tilslutning af belastninger
  • Use cable ends suitable for the corresponding connectors. After tightening the screws of the connectors, slightly tug the cables to check their tightness
  • Brug passende datakommunikationskabler. Se installationsvejledningen "MCX hardware netværksspecifikation" for den type kabel, der skal bruges, og opsætningsanbefalinger
  • Reducer sondens og digitale inputkablers vej så meget som muligt, og undgå spiralbaner, der omslutter strømenheder. Adskil fra induktive belastninger og strømkabler for at undgå mulig elektromagnetisk støj
  • Undgå at røre ved eller næsten røre ved de elektroniske komponenter monteret på kortet for at undgå elektrostatiske udladninger
  • Produktet er ikke egnet til at blive eksponeret direkte på internettet

ANSVARSFRASKRIVELSE: Kun professionel brug

  • Dette produkt er ikke underlagt den britiske PSTI-regulering, da det kun er til levering til og brug af fagfolk med den nødvendige ekspertise og kvalifikationer.
  • Any misuse or improper handling may result in unintended consequences. By purchasinVed brug af dette produkt anerkender og accepterer du, at dets anvendelse kun er til professionel brug.
  • Danfoss påtager sig intet ansvar for skader, kvæstelser eller negative konsekvenser ("skade") som følge af forkert eller ukorrekt brug af produktet, og du accepterer at holde Danfoss skadesløs for enhver sådan skade som følge af din forkerte eller ukorrekte brug af produktet.

Tekniske specifikationer

Strømforsyning

  • 21 – 265 V AC, 50/60 Hz. Maximum power consumption: 15 W. Insulation between power supply and the extra-low voltage: forstærket
  • 40 – 230 V DC

Kommunikationsgrænseflade

Interface Bruge Forbindelsesmærkat Teknisk data
CAN bus Feltbus til tilslutning til brugergrænseflader, MCX-controllere, serviceværktøjer mm. CAN CAN-RJ Physical layer according to ISO 11898-2 High Speed CAN bus Frame format according to CAN 2.0B specification

Transceiver not isolated (power supply has reinforced isolation)

USB-enhed Forberedt til fremtidig brug USB-DEV Stik: Type Mini B
USB vært For connection to the Flash drive for application software update, datalogging and service USB-H Stik: Type A
RS485-1

RS485-2 (kun MCX20B2)

Communication bus to BMS (e.g. Modbus slave), service tools, smart devices (e.g. Modbus master), RS485-1 can be polarized as master from the application RS485-1 RS485-2 Physical layer according to EIA 485 Ref3

Provide 500 V peak transient galvanic isolation

Ethernet For web server functionality, integration (e.g. Modbus TCP)

NOTICE! Do not route cable outside of buildings. Connect only to IT equipment compliant with EN 60950 or EN 62368 (Information technology equipment. Safety. General requirements)

Ethernet Interface type: 10 BASE-T og 100 BASE-TX, IEEE 802.3.

MDI-X (Automatic medium- dependent interface crossover)

Trådlængder

Interface Maks. ledningslængde (m) Maks. baudrate (bps) Min. trådstørrelse
Ethernet 100 10/100 M  
  1000 50 K AWG18
  500 125 K AWG22
CAN bus 250 250 K AWG24
  80 500 K AWG26
  30 1 M AWG26
RS485 1000 125 K AWG22
Signalledninger 30    

Forbindelse

Stik Type Dimensioner
Top Bestyrelse
Digital indgang 1 stik 3-vejs skruestik type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Analog indgang 11-14 stik 7-vejs skruestik type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Digital indgang 2 stik 3-vejs skruestik type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Digital indgang 3 stik 3-vejs skruestik type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Digital indgang 4 stik 3-vejs skruestik type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Digital indgang 5-8 stik 5-vejs skruestik type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Bundbræt
Digital udgang 1-5 stik 10-vejs skruestik type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Digital udgang 6 stik 6-vejs skruestik type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Ethernet-stik 8/8 vejs RJ 45 stik type  
USB-værtsstik USB Type A  
Analog indgang 1-5 stik 11-vejs skruestik type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Strømforsyningsstik 2-vejs skruestik type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Digital udgang 9-13 stik 10-vejs skruestik type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Analog udgang 1-2 stik 8-vejs skruestik type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

RS485 -2 stik 3-vejs skruestik type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

RS485-1 stik 3-vejs skruestik type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

CAN stik 4-vejs skruestik type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

CAN-RJ stik 6/6 vejs telefon RJ12 stik type  
USB DEV-stik USB Mini B  

Brugergrænseflade

LCD Display

  • visningstilstand: STN blå transmitterende
  • back-light: white LED back-light, adjustable via software
  • display format: 128 x 64 dots
  • active visible area: 58 x 29 mm
  • contrast: adjustable via software

Justering af displayindstillinger

  • Settings of the LCD display like contrast and brightness, might need to be adjusted due to external ambient factors.
  • Press and release the Enter and X key after powering on to access the BIOS menu and select the DISPLAY menu.
  • Use UP and DOWN arrow keys to adjust the contrast or the brightness of the display at the desired level.

Eksternt display

Danfoss-80G8280-Ejector-Controller-FIG-4

Dimension

Dimension EKE 80

Danfoss-80G8280-Ejector-Controller-FIG-5

Tilslutning, lavere niveau

Advarsel
Forsyningen voltage of AI may not share the signal with other controllers

Danfoss-80G8280-Ejector-Controller-FIG-6

Tilslutning, øverste niveau

Danfoss-80G8280-Ejector-Controller-FIG-7

AI Mærke Beskrivelse Signal type choice Via software or fieldbus Misligholdelse Modbus register Kommentar
AI-01 AI1 Capacity Reference 0-10 V

0-5 V

2-10 V

0-20 mA

4-20 mA

0-10 V 17902 Max 13.5 V input voltage.

Tilslut ikke voltage sources without current limitation (overall 80 mA) to analog inputs while unit is not powered

AI-02 AI2 ICAD Ejector Mode Feedback 0-20 mA

4-20 mA

4-20 mA 17903
AI-03 AI3 ICAD Bypass Mode Feedback 0-20 mA

4-20 mA

4-20 mA 17904
AI-04 AI4 Tryktransmitter 0-5 V

0-10 V

0-20 mA

4-20 mA

4-20 mA 17905
AI-05 AI5 Temperatursensor 0–10 V NTC–10K PT1000 PT1000 17906
AI-06 N/A Not available for customer use N/A N/A Reserveret Reserveret
AI-07
AI-08
AI-09
AI-10
AI-11 AI11 Not used in logic. User configurable IO None NTC–10K PT1000 0–5 V

0-10 V

2-10 V

0-20 mA

4-20 mA

Ingen 17907 Max 13.5 V input voltage.

Tilslut ikke voltage kilder uden strømbegrænsning (samlet 80 mA) til analoge indgange, mens enheden ikke er strømforsynet

AI-12 AI12 17908
AI-13 AI13 17909
AI-14 AI14 17910
AI-15  

N/A

 

Not available for customer use

 

N/A

 

N/A

 

Reserveret

 

Reserveret

AI-16
A0 Mærke Beskrivelse Signal type valg Misligholdelse Modbus register Kommentar
A0-01 AO1 ICAD Ejector Mode Request OD 0-10 V

2-10 V

0-10 V 18102 Analog Outputs galvanically isolated, minimum load 1K Ω (10 mA) for each output
A0-02 AO2 ICAD Bypass Mode Request OD 0-10 V

2-10 V

0-10 V 18103
A0-03 N/A Not available for customer use N/A Reserveret Reserveret
A0-04
A0-05
A0-06
DI Mærke Beskrivelse Signal type valg Misligholdelse Modbus register Kommentar
DI-01 DI1 Not used in logic, User configurable IO 24 V or 230 V Depending on port used. See upper level diagram  

 

 

 

17498 24 V Opto isolated, 24 V AC 50/60 Hz or 24 V DC Rated current: 5 mA @ 24 V AC

230 V Opto isolated, 86–265 V AC / 50/60 Hz, Reinforced isolation, Rated current: 2,5 mA @ 265 V AC

DI-02 DI2 Not used in logic, User configurable IO 17499
DI-03 DI3 Not used in logic, User configurable IO 17500
DI-04 DI4 Not used in logic, User configurable IO 17501
DI-05 DI5 Suction Flow Control Dry contact and/or 24 V AC  

 

 

17503 As the inputs are not isolated, caution has to be used when applying 24 V AC: the same polarity of the supply MUST always be used on COM/GND connection. Counting function with max frequency of 16.6 Hz (30 ms minimum pulse time)
DI-06 DI6 Ejector Mode Signal Error 17504
DI-07 DI7 Bypass Mode Error Signal 17505
DI-08 N/A Not used in logic N/A N/A Reserveret Reserveret
DI-09
DI-10
DI-11
DI-12
DI-13
DI-14
DI-15
DI-16
DI-17
DI-18
DI-19
DI-20
DI-21
DI-22
DO Mærke Beskrivelse Signal type valg Misligholdelse Modbus register Kommentar
DO-01 DO1 Alarmudgang   17702 5 A 250 V AC til resistive belastninger – 100,000 cyklusser

3 A 250 V AC for induktive belastninger – 100,000 cyklusser med cos(phi) = 0.4

UL: 3 A resistive, 250 V AC, 100,000 cycles; 1/8 hp, 125/250 V AC, 30,000 cycles; C300 pilot duty, 125/250 V AC, 30,000 cycles

DO-02 N/A Not used in logic N/A N/A Reserveret  
DO-03 DO3 User-assigned Ejector  

 

 

 

 

 

Not assigned Ejector 1

Udkaster 2

Udkaster 3

Udkaster 4

Ejector 5-8 expansion module only

Ikke tildelt 17703 Internal Solid State Relay for Industrial Ejector Coils:

15–280 Vrms, 0.5 A

UL: Making current: 7 A, Breaking current:

0.7 A, Pilot duty (cos θ 0.35), 240 V AC, N.O

VIGTIG: For a Multi-Ejector, an external Solid State Relay is necessary between the assigned DO and the

Multi-Ejector solenoid coils that meet the following specifications:

Leakage current suppression.

At least 2 A rating for both 110 V and 230 V Multi-Ejector coils.

VIGTIG: Ejectors 5 to 8 can only be assigned to an extension module. An extension module is the same controller device as this device except that it is user-configured/ defined as an extension module for control of extra Ejectors, i.e., When there are more than 4 Industrial Ejectors.

DO-04 DO4 User-assigned Ejector Ikke tildelt 17704
DO-05 DO5 User-assigned Ejector Ikke tildelt 17705
DO-06 DO6 User-assigned Ejector Ikke tildelt 17706
DO-07 N/A Not used in logic N/A N/A Reserveret N/A
DO-08
DO-09
DO-10
DO-11
DO-12
DO-13
DO-14
DO-15
DO-16
DO-17
DO-18
DO-19
DO-20

KONTAKTE

  • Danfoss A / S
  • Klimaløsninger
  • danfoss.com
  • +45 7488 2222

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals cataloques descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding it and to the extent, explicit reference is made in a quotation or order confrmation. Dantoss cannot accept any responsibility for possible errors in catalogues, brochures, videos, and other material. Janfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered, provided that such alterations can be made without changes to form, fit or function of the product.
Alle varemærker i dette materiale tilhører Danfoss A/S eller Danfoss koncernselskaber. Danfoss og Danfoss-logoet er varemærker tilhørende Danfoss A/S. Alle rettigheder forbeholdes.

Danfoss-80G8280-Ejector-Controller-FIG-1

FAQ

Q: Can the EKE 80 Ejector Controller be used with third-party controllers?

A: The EKE 80 is designed to work with Danfoss controllers AK-PC 782A/AK-PC 782B or a PLC. Compatibility with third-party controllers may vary, it is recommended to consult with Danfoss support for further information.

Q: What is the maximum wire length supported for Ethernet connection?

A: The maximum wire length for Ethernet connection is 100 meters.

Dokumenter/ressourcer

Danfoss 80G8280 Ejector Controller [pdf] Installationsvejledning
080G5022, 080R9502, 80G8280, 80G8280 Ejector Controller, 80G8280, Ejector Controller, Controller

Referencer

Efterlad en kommentar

Din e-mailadresse vil ikke blive offentliggjort. Påkrævede felter er markeret *