1. Introduktion
The REFCO GOBI II Universal Condensate Pump is designed for efficient and quiet removal of condensate from air conditioning, HVAC, and dehumidifier systems. Suitable for systems ranging from 6,000 BTU/h to 120,000 BTU/h, this pump features a digital water sensor, universal voltage compatibility, and individually configurable flow rates, making it a versatile solution for various applications. This manual provides essential information for safe installation, operation, maintenance, and troubleshooting of your GOBI II pump.

Figur 1.1: Samlet view of the GOBI II Universal Condensate Pump.
2. Sikkerhedsoplysninger
Læs alle sikkerhedsinstruktioner omhyggeligt inden installation og betjening. Manglende overholdelse af disse instruktioner kan resultere i elektrisk stød, brand eller alvorlig personskade.
- Afbryd altid strømmen til klimaanlægget og pumpen, før du udfører installation, vedligeholdelse eller fejlfinding.
- Installation must be performed by a qualified technician in accordance with all local and national electrical and plumbing codes.
- Sørg for, at pumpen er installeret et sted, hvor den er beskyttet mod direkte vandsprøjt og ekstreme temperaturer.
- Do not operate the pump with damaged cables or if it has been dropped or damaged.
- This pump is designed for condensate water only. Do not use it for other liquids.
- Hold børn og uautoriserede personer væk fra installationsområdet.
3. Produktet er slutview
The GOBI II pump system consists of several key components designed for reliable condensate removal.

Figure 3.1: GOBI II kit components and labeled diagram.
3.1. Inkluderede komponenter:
- Strømkabel
- Alarm kabel
- Star tube and anti-siphon device
- Skruer (til montering)
- Skruankre
- Factory-installed alarm fuse
- Kabelbindere
3.2. Nøglefunktioner:
- Universal application for various AC systems.
- High pumping capacity: 11 GPH (gallons per hour).
- High discharge head: up to 65.6 ft.
- Extremely quiet operation: less than 19 dB noise level.
- Reliable digital water sensor, eliminating traditional float problems.
- Demand-oriented control for optimized pumping capacity.
4. Opsætning og installation
The GOBI II pump is designed for direct mounting under the air conditioner unit. Follow these steps for proper installation:
- Montering: Secure the pump's wall back plate (component 9 in Figure 3.1) to a stable surface directly beneath the air conditioning unit using the provided screws and screw anchors. Ensure it is level.
- Pump Body Installation: Slide the pump body (component 1 in Figure 3.1) onto the mounted back plate until it clicks securely into place.
- Condensate Inlet Connection: Connect the condensate drain line from the air conditioning unit to the pump's inlet. Ensure a tight, leak-free connection.
- Tilslutning af udløbsledning: Connect the 1/4" discharge tube from the pump's outlet to your desired drain point. Install the provided anti-siphon device in the discharge line to prevent backflow and ensure proper pump operation. Ensure the discharge line rises vertically for at least 6 inches before running horizontally or downwards.
- Elektrisk tilslutning: Connect the power cable to the pump and then to a suitable power supply (100-240 VAC, 50/60 Hz). Ensure all electrical connections are secure and comply with local electrical codes.
- Alarm Cable Connection (Optional but Recommended): Connect the alarm cable to the pump's alarm relay terminals and integrate it with your HVAC system's alarm circuit if desired. The alarm relay is interchangeable (NO or NC) and rated for 250VAC, 6.3A or 28VDC, 6.3A.
- Test: Once all connections are made, restore power to the system. Pour a small amount of water into the air conditioner's drain pan to verify the pump activates and discharges water correctly. Check for any leaks.
5. Betjeningsvejledning
The GOBI II condensate pump operates automatically based on the water level detected by its digital sensor. It will activate when condensate accumulates and shut off once the water is cleared.
5.1. Digital Sensor and Flow Control:
The integrated digital sensor (component 4 in Figure 3.1) precisely monitors the water level, ensuring the pump activates only when necessary. The pump's demand-oriented control adjusts the pumping capacity as needed, optimizing efficiency and minimizing noise.
5.2. Diagnostic LEDs:
The pump features a diagnostic LED (component 8 in Figure 3.1) to indicate its operational status.

Figure 5.1: Diagnostic LED indicators.
- Grøn LED: Indicates normal operation. The pump is powered and functioning correctly.
- Rød LED: Indicates an error or alarm condition. Refer to the Troubleshooting section for possible causes.
6. Vedligeholdelse
Regular maintenance ensures the longevity and optimal performance of your GOBI II pump.
- Månedlig kontrol: Visually inspect the pump, inlet, and discharge lines for any blockages, kinks, or leaks. Ensure the pump housing is clean.
- Årlig rengøring: Disconnect power to the pump and the AC unit. Carefully remove the pump body from the wall back plate. Clean the water tray (component 5 in Figure 3.1) and the digital sensor (component 4) to remove any sludge, mold, or debris. A soft brush and mild detergent can be used. Rinse thoroughly with clean water.
- Filterudskiftning: The pump includes a replaceable filter (component 3 in Figure 3.1). Check its condition during annual cleaning and replace if it appears clogged or damaged.
- Genmontering: After cleaning, reassemble all components, ensuring they are securely in place. Restore power and test the pump's operation.
7. Fejlfinding
If you encounter issues with your GOBI II pump, refer to the following table for common problems and solutions. Always disconnect power before attempting any inspection or repair.
| Problem | Mulig årsag | Løsning |
|---|---|---|
| Pumpen kører ikke | No power; Clogged inlet/outlet; Faulty sensor; Motor issue | Check power supply; Clear blockages; Clean digital sensor; Contact support if issue persists. |
| Pumpen kører kontinuerligt | Anti-siphon device missing/incorrectly installed; Leak in discharge line; Sensor issue | Install/check anti-siphon device; Inspect discharge line for leaks; Clean sensor. |
| Vandoverløb | Pump not running; Clogged lines; Pump capacity exceeded; Alarm not connected | See "Pump does not run"; Clear blockages; Ensure system BTU/h is within pump's range; Connect alarm. |
| Red diagnostic LED is on | Error condition (e.g., high water alarm, pump fault) | Check for blockages, ensure proper installation, and verify power. If the issue persists after checking, contact technical support. |
8. Specifikationer
Detailed technical specifications for the GOBI II Universal Condensate Pump.
| Parameter | Værdi |
|---|---|
| Maks. Strømningshastighed | 11 GPH (0.18 gallon pr. minut) |
| Maks. Udledningshoved | 65.6 fod |
| Maks. Sugeløft | 10 fod |
| Støjniveau | <19 dB(A) |
| Pumpetype | Diafragma type |
| Rør diameter | 1/4" |
| Voltage | 100 - 240 VAC |
| Frekvens | 50/60 Hz |
| Energiforbrug | 8 W |
| Beskyttelsesklasse | I |
| Alarmrelæ | Udskiftelig NO eller NC, klassificeret 250VAC, 6.3A eller 28VDC, 6.3A |
| Beskyttelse mod indtrængen | IP44 |
| Kabellængde | 5 fod |
| Driftstemperaturområde | 5-40 °C |
| Vandtemperaturområde | 5-40 °C |
| Opbevaringstemperaturområde | -4 - 122 °F (-20 - 50 °C) |
| Varens vægt | 2.59 pund |
| Pakkedimensioner | 13.66 x 12.8 x 2.6 tommer |
8.1. Capacity Curve:
The following graph illustrates the pump's capacity (flow rate) versus vertical lift/head pressure.

Figure 8.1: GOBI II Capacity Curve.
9. Garanti
The manufacturer warranty for the GOBI II Universal Condensate Pump begins with the commissioning of the unit. Please refer to the warranty documentation included with your purchase for specific terms and conditions.
10. Support
For technical assistance, spare parts, or further inquiries, please contact your REFCO product supplier or visit the official REFCO webwebsted for supportkontaktoplysninger.