REFCO 3004145

GOBI II Universal Condensate Pump

Model: 3004145

Instruktionsmanual

1. Introduktion

The REFCO GOBI II Universal Condensate Pump is designed for efficient and quiet removal of condensate from air conditioning, HVAC, and dehumidifier systems. Suitable for systems ranging from 6,000 BTU/h to 120,000 BTU/h, this pump features a digital water sensor, universal voltage compatibility, and individually configurable flow rates, making it a versatile solution for various applications. This manual provides essential information for safe installation, operation, maintenance, and troubleshooting of your GOBI II pump.

REFCO GOBI II Universal Condensate Pump, assembled view

Figur 1.1: Samlet view of the GOBI II Universal Condensate Pump.

2. Sikkerhedsoplysninger

Læs alle sikkerhedsinstruktioner omhyggeligt inden installation og betjening. Manglende overholdelse af disse instruktioner kan resultere i elektrisk stød, brand eller alvorlig personskade.

  • Afbryd altid strømmen til klimaanlægget og pumpen, før du udfører installation, vedligeholdelse eller fejlfinding.
  • Installation must be performed by a qualified technician in accordance with all local and national electrical and plumbing codes.
  • Sørg for, at pumpen er installeret et sted, hvor den er beskyttet mod direkte vandsprøjt og ekstreme temperaturer.
  • Do not operate the pump with damaged cables or if it has been dropped or damaged.
  • This pump is designed for condensate water only. Do not use it for other liquids.
  • Hold børn og uautoriserede personer væk fra installationsområdet.

3. Produktet er slutview

The GOBI II pump system consists of several key components designed for reliable condensate removal.

Diagram showing GOBI II pump components and included accessories

Figure 3.1: GOBI II kit components and labeled diagram.

3.1. Inkluderede komponenter:

  • Strømkabel
  • Alarm kabel
  • Star tube and anti-siphon device
  • Skruer (til montering)
  • Skruankre
  • Factory-installed alarm fuse
  • Kabelbindere

3.2. Nøglefunktioner:

  • Universal application for various AC systems.
  • High pumping capacity: 11 GPH (gallons per hour).
  • High discharge head: up to 65.6 ft.
  • Extremely quiet operation: less than 19 dB noise level.
  • Reliable digital water sensor, eliminating traditional float problems.
  • Demand-oriented control for optimized pumping capacity.

4. Opsætning og installation

The GOBI II pump is designed for direct mounting under the air conditioner unit. Follow these steps for proper installation:

  1. Montering: Secure the pump's wall back plate (component 9 in Figure 3.1) to a stable surface directly beneath the air conditioning unit using the provided screws and screw anchors. Ensure it is level.
  2. Pump Body Installation: Slide the pump body (component 1 in Figure 3.1) onto the mounted back plate until it clicks securely into place.
  3. Condensate Inlet Connection: Connect the condensate drain line from the air conditioning unit to the pump's inlet. Ensure a tight, leak-free connection.
  4. Tilslutning af udløbsledning: Connect the 1/4" discharge tube from the pump's outlet to your desired drain point. Install the provided anti-siphon device in the discharge line to prevent backflow and ensure proper pump operation. Ensure the discharge line rises vertically for at least 6 inches before running horizontally or downwards.
  5. Elektrisk tilslutning: Connect the power cable to the pump and then to a suitable power supply (100-240 VAC, 50/60 Hz). Ensure all electrical connections are secure and comply with local electrical codes.
  6. Alarm Cable Connection (Optional but Recommended): Connect the alarm cable to the pump's alarm relay terminals and integrate it with your HVAC system's alarm circuit if desired. The alarm relay is interchangeable (NO or NC) and rated for 250VAC, 6.3A or 28VDC, 6.3A.
  7. Test: Once all connections are made, restore power to the system. Pour a small amount of water into the air conditioner's drain pan to verify the pump activates and discharges water correctly. Check for any leaks.

5. Betjeningsvejledning

The GOBI II condensate pump operates automatically based on the water level detected by its digital sensor. It will activate when condensate accumulates and shut off once the water is cleared.

5.1. Digital Sensor and Flow Control:

The integrated digital sensor (component 4 in Figure 3.1) precisely monitors the water level, ensuring the pump activates only when necessary. The pump's demand-oriented control adjusts the pumping capacity as needed, optimizing efficiency and minimizing noise.

5.2. Diagnostic LEDs:

The pump features a diagnostic LED (component 8 in Figure 3.1) to indicate its operational status.

Diagram showing diagnostic LEDs: green for normal operation, red for error

Figure 5.1: Diagnostic LED indicators.

  • Grøn LED: Indicates normal operation. The pump is powered and functioning correctly.
  • Rød LED: Indicates an error or alarm condition. Refer to the Troubleshooting section for possible causes.

6. Vedligeholdelse

Regular maintenance ensures the longevity and optimal performance of your GOBI II pump.

  • Månedlig kontrol: Visually inspect the pump, inlet, and discharge lines for any blockages, kinks, or leaks. Ensure the pump housing is clean.
  • Årlig rengøring: Disconnect power to the pump and the AC unit. Carefully remove the pump body from the wall back plate. Clean the water tray (component 5 in Figure 3.1) and the digital sensor (component 4) to remove any sludge, mold, or debris. A soft brush and mild detergent can be used. Rinse thoroughly with clean water.
  • Filterudskiftning: The pump includes a replaceable filter (component 3 in Figure 3.1). Check its condition during annual cleaning and replace if it appears clogged or damaged.
  • Genmontering: After cleaning, reassemble all components, ensuring they are securely in place. Restore power and test the pump's operation.

7. Fejlfinding

If you encounter issues with your GOBI II pump, refer to the following table for common problems and solutions. Always disconnect power before attempting any inspection or repair.

ProblemMulig årsagLøsning
Pumpen kører ikkeNo power; Clogged inlet/outlet; Faulty sensor; Motor issueCheck power supply; Clear blockages; Clean digital sensor; Contact support if issue persists.
Pumpen kører kontinuerligtAnti-siphon device missing/incorrectly installed; Leak in discharge line; Sensor issueInstall/check anti-siphon device; Inspect discharge line for leaks; Clean sensor.
VandoverløbPump not running; Clogged lines; Pump capacity exceeded; Alarm not connectedSee "Pump does not run"; Clear blockages; Ensure system BTU/h is within pump's range; Connect alarm.
Red diagnostic LED is onError condition (e.g., high water alarm, pump fault)Check for blockages, ensure proper installation, and verify power. If the issue persists after checking, contact technical support.

8. Specifikationer

Detailed technical specifications for the GOBI II Universal Condensate Pump.

ParameterVærdi
Maks. Strømningshastighed11 GPH (0.18 gallon pr. minut)
Maks. Udledningshoved65.6 fod
Maks. Sugeløft10 fod
Støjniveau<19 dB(A)
PumpetypeDiafragma type
Rør diameter1/4"
Voltage100 - 240 VAC
Frekvens50/60 Hz
Energiforbrug8 W
BeskyttelsesklasseI
AlarmrelæUdskiftelig NO eller NC, klassificeret 250VAC, 6.3A eller 28VDC, 6.3A
Beskyttelse mod indtrængenIP44
Kabellængde5 fod
Driftstemperaturområde5-40 °C
Vandtemperaturområde5-40 °C
Opbevaringstemperaturområde-4 - 122 °F (-20 - 50 °C)
Varens vægt2.59 pund
Pakkedimensioner13.66 x 12.8 x 2.6 tommer

8.1. Capacity Curve:

The following graph illustrates the pump's capacity (flow rate) versus vertical lift/head pressure.

Graph showing GOBI II pump capacity in GPH and l/hr versus vertical lift/head pressure in feet and meters

Figure 8.1: GOBI II Capacity Curve.

9. Garanti

The manufacturer warranty for the GOBI II Universal Condensate Pump begins with the commissioning of the unit. Please refer to the warranty documentation included with your purchase for specific terms and conditions.

10. Support

For technical assistance, spare parts, or further inquiries, please contact your REFCO product supplier or visit the official REFCO webwebsted for supportkontaktoplysninger.

Relaterede dokumenter - 3004145

Preview Gobi II kondensatpumpe installations- og betjeningsmanual
Omfattende vejledning til REFCO Gobi II kondensatpumpen, der dækker installation, drift, vedligeholdelse og fejlfinding af HVAC/R-systemer.
Preview REFCO GOBI II kondensatpumpe: Hurtig installationsvejledning
Officiel hurtigguide til REFCO GOBI II kondensatpumpe (model 3004145). Indeholder vigtige oplysninger om installation, drift, sikkerhed og vedligeholdelse for effektiv fjernelse af kondensat i HVAC-systemer.
Preview REFCO Gobi II kondensatpumpe installations- og driftsmanual
En omfattende guide til REFCO Gobi II kondensatpumpen med detaljerede oplysninger om installation, betjening, sikkerhedsforanstaltninger, tekniske specifikationer og fejlfinding. Funktionerne omfatter konfigurerbar støjsvag tilstand, diagnostisk LED, USB-tilslutning og bredt anvendelsesområde.
Preview REFCO Combi Universal Kondenspumpe 3004146 Installations- og teknisk manual
Dette dokument indeholder omfattende installations-, tekniske specifikationer, sikkerhedsretningslinjer og fejlfindingsoplysninger for REFCO Combi Universal-kondenspumpen (model 3004146).
Preview REFCO VAMP-F Kondenspumpe Kvikguide
En kortfattet vejledning til installation, drift og vedligeholdelse af REFCO VAMP-F kondensatpumpe, designet til effektiv fjernelse af kondensat fra HVAC-systemer. Inkluderer tekniske specifikationer og sikkerhedsinstruktioner.
Preview REFCO VAMP-X Kondenspumpe Brugsanvisning
Denne brugsanvisning indeholder detaljerede oplysninger om REFCO VAMP-X kondensatpumpe, der dækker dens specifikationer, installation, drift, vedligeholdelse, sikkerhedsretningslinjer og fejlfinding. Fås på engelsk, tysk, fransk, italiensk og spansk.