GEYA GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA

GEYA GRD9L-R Automatisk Genlukkeenhed Brugermanual

Model: GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA

1. Produktet er slutview

The GEYA GRD9L-R Automatic Reclosing Device is an electromagnetic leakage circuit breaker (RCCB) designed to enhance electrical system reliability and reduce manual intervention. It automatically recloses the circuit when a leakage fault causes the RCD to trip unexpectedly, minimizing downtime and maintenance costs.

This device is suitable for various applications, including electrical network terminal lines, meter boxes, new energy circuit management, solar PV control boxes, smart electricity systems, smart homes, and charging stations for new energy vehicles.

Nøglefunktioner:

  • Automatic reclosing function after RCD trip, eliminating the need for manual reset.
  • Integrated 3 reclosing attempts. An auxiliary contact can send an alarm if continuous tripping occurs within 15 minutes.
  • Manual/Automatic selector switch for operational flexibility.
  • Features double mechanical/electronic locking for enhanced safety.
  • Compatible with auxiliary contacts, alarm contacts, shunt releases, and undervoltage-udgivelser.
  • Reclosing attempt counter resets if no trip occurs or after a manual reset within 15 minutes of successful reclosure.
GEYA GRD9L-R Automatic Reclosing Device

Figur 1: Forside view of the GEYA GRD9L-R Automatic Reclosing Device.

2. Sikkerhedsoplysninger

ADVARSEL: Installation and maintenance of this device must be performed by a qualified electrician in accordance with all local and national electrical codes and regulations. Failure to do so may result in electric shock, fire, or other serious injury.

  • Afbryd altid strømmen, før du installerer, servicerer eller fjerner enheden.
  • Sørg for korrekt jordforbindelse af det elektriske system.
  • Brug ikke enheden, hvis den ser ud til at være beskadiget.
  • Verify correct wiring connections to prevent malfunction or damage.
  • Enheden er designet til specifikke volumengradertage and current ratings. Do not exceed these limits.

3. Product Components and Diagrams

3.1 Funktionsbeskrivelse

Function Description Diagram

Figure 2: Diagram illustrating the automatic reclosing logic and function description. The device attempts to reclose the circuit up to three times with specific time intervals. If the interval between two successful closings exceeds 15 minutes, the program clears the accumulated closing times.

3.2 Functions Diagram (Auto Mode Logic)

Functions Diagram Auto Mode

Figure 3: Detailed flow chart of the automatic reclosing sequence. After a trip, the device attempts to reclose. If successful, it waits. If it trips again, it attempts a second reclose after 10 seconds. A third attempt follows after 60 seconds if the second fails. If all three attempts fail within 15 minutes, the device locks out and sends an auxiliary alarm. The power delay (Tr) is 2 seconds. Note: Customization of closing times and delay times requires contacting the manufacturer.

3.3 Låsefunktion

Locking Function Diagram

Figure 4: Illustration of the locking mechanism. When the locking function is activated (e.g., by inserting a padlock with a diameter less than 3.5 mm), the RCCB cannot be closed, ensuring safety during circuit checks or maintenance. This prevents accidental reclosure.

4. Opsætning og installation

The GEYA GRD9L-R device is designed for DIN rail mounting and can be integrated with other electrical components such as an RCCB and auxiliary modules.

4.1 Component Integration

Component Integration Diagram

Figur 5: Eksample of how the GRD9L-R device can be installed alongside an Auxiliary module and an RCCB on a standard DIN rail. Ensure proper alignment and secure fastening of all components.

4.2 Ledningsdiagram

Ledningsdiagram Eksample

Figur 6: Et example application wiring diagram. This diagram shows the connection of the GRD9L-R device with an alarm lamp, an RCCB, and multiple load circuits. Red lines indicate live connections, blue lines indicate neutral connections. The auxiliary contacts (A1, A2, COM, NO) are used for external signaling, such as an alarm lamp. Always consult a qualified electrician for correct wiring specific to your installation.

4.3 Installation Steps (General Guidelines):

  1. Strømafbrydelse: Sørg for, at hovedstrømforsyningen til kredsløbet er helt afbrudt, før installationen påbegyndes.
  2. Montering: Mount the GRD9L-R device, the associated RCCB, and any auxiliary modules onto a standard DIN rail within an appropriate electrical enclosure.
  3. Ledningsføring: Connect the input and output terminals of the GRD9L-R and RCCB according to the wiring diagram (Figure 6) and local electrical codes. Pay close attention to live (L) and neutral (N) connections.
  4. Hjælpeforbindelser: If using, connect auxiliary contacts (A1, A2, COM, NO) for remote signaling or control, such as an alarm lamp.
  5. Verifikation: Dobbelttjek alle ledningsforbindelser for tæthed og korrekthed.
  6. Strømgendannelse: Når installationen er færdig og verificeret, skal strømmen til kredsløbet genoprettes.

5. Betjeningsvejledning

5.1 Manual/Automatic Selector

The device features a selector switch labeled "AUTO" and "MANU" (Manual). This switch allows you to choose the operating mode:

  • AUTO-tilstand: In this mode, the device will automatically attempt to reclose the associated RCCB after a trip, following the reclosing logic described in Figure 3. This is the default and recommended mode for continuous operation.
  • MANU-tilstand: In this mode, the automatic reclosing function is disabled. If the RCCB trips, it must be manually reset. This mode is useful for maintenance or specific operational requirements where automatic reclosure is not desired.

5.2 Reclosing Logic (Auto Mode)

When in AUTO mode, the device follows a specific sequence of reclosing attempts:

  1. 1st Trip: If the RCD trips, the device waits for 10 seconds, then attempts to reclose.
  2. 2nd Trip: If the RCD trips again within 15 minutes of the first reclosure, the device waits for 60 seconds, then attempts a second reclosure.
  3. 3rd Trip: If the RCD trips a third time within 15 minutes of the second reclosure, the device waits for 300 seconds (5 minutes), then attempts a third reclosure.
  4. Låst ude: If the RCD trips a fourth time within 15 minutes, or if any of the three reclosing attempts fail, the device enters a lockout state. It will not attempt further reclosures automatically and will activate the auxiliary alarm contact (if connected). Manual intervention is required to reset the device.
  5. Resetting Closing Times: If no trip occurs for 15 minutes after a successful reclosure, or if the device is manually reset, the reclosing attempt counter is cleared.

5.3 Testknap

The associated RCCB typically has a test button. Pressing this button simulates a leakage fault and should cause the RCCB to trip. This is used to verify the proper functioning of the RCCB and, in AUTO mode, the reclosing device.

6. Vedligeholdelse

The GEYA GRD9L-R Automatic Reclosing Device is designed for minimal maintenance. However, regular checks are recommended to ensure optimal performance and safety.

  • Visuel inspektion: Undersøg regelmæssigt enheden for tegn på fysisk skade, misfarvning eller løse forbindelser.
  • Funktionstest: Regularly test the associated RCCB using its test button. Observe if the GRD9L-R device initiates its reclosing sequence in AUTO mode.
  • Rensning: Sørg for, at enheden holdes ren og fri for støv og snavs. Brug en tør, blød klud til rengøring. Brug ikke flydende rengøringsmidler.
  • Professionel inspektion: It is recommended to have the electrical system, including this device, inspected by a qualified electrician at least once a year.

7. Fejlfinding

If the GEYA GRD9L-R device is not functioning as expected, consider the following:

ProblemMulig årsagLøsning
Enheden lukker ikke automatisk igen.
  • Device is in MANU mode.
  • Device is in lockout state after multiple failed reclosures.
  • Vedvarende fejl i kredsløbet.
  • Locking function is activated.
  • Skift til AUTO-tilstand.
  • Manually reset the device and investigate the cause of repeated trips.
  • Identify and rectify the electrical fault.
  • Ensure no padlock is inserted in the locking mechanism.
Alarm contact is continuously active.
  • Device is in lockout state.
  • Auxiliary contact wiring issue.
  • Investigate and clear the fault, then manually reset the device.
  • Check wiring of auxiliary contacts.
RCCB trips immediately after reclosure.
  • Persistent or severe electrical fault (e.g., short circuit, ground fault).
  • Immediately disconnect power and have a qualified electrician diagnose and repair the fault. Do not attempt further reclosures until the fault is resolved.

If the problem persists after attempting these solutions, contact a qualified electrician or GEYA customer support.

8. Specifikationer

FeatureDetalje
ModelnummerGRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA
MærkeGEYA
Voltage220 Volt AC
Nominel strøm63 A (as per model number)
Antal poler2
Afbryder typeRCD (Residual Current Device)
MonteringstypeWall Mount, Flush Mount (DIN Rail compatible)
Pakkedimensioner12 x 11.6 x 9.1 cm
Varens vægt350 gram
FabrikantZHEJIANG GEYA ELECTRICAL CO.,LTD

9. Garanti og support

Specific warranty information for the GEYA GRD9L-R Automatic Reclosing Device is not available in the provided product details. Please refer to the product packaging or contact GEYA customer support for detailed warranty terms and conditions.

For technical support, inquiries, or assistance with installation and troubleshooting, please contact GEYA directly through their official channels or the retailer from whom the product was purchased.

Relaterede dokumenter - GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA

Preview GEYA Elektrisk Udstyr Katalog - Afbrydere, Kontaktorer og Mere
Omfattende katalog over GEYA elektriske produkter, herunder miniatureafbrydere, kontaktorer, omskiftere og andet sikkerhedsudstyr, med detaljerede specifikationer, anvendelser og overholdelse af standarder.
Preview GEYA GRD9L-W WiFi-styret MCB/RCCB/RCBO: Brugsanvisning og teknisk vejledning
Omfattende instruktionsmanual og teknisk vejledning til GEYA GRD9L-W WiFi-styrede MCB/RCCB/RCBO. Dækker applikationer, funktioner, tekniske specifikationer, installation, netværk, fejlfinding og dimensionsoplysninger for intelligente elektriske systemer.
Preview GEYA GRD9L-W WiFi-styret MCB/RCCB/RCBO: Brugsanvisning og teknisk vejledning
Detaljeret instruktionsmanual til GEYA GRD9L-W WiFi-styret MCB/RCCB/RCBO. Dækker anvendelser i intelligent husholdningselektricitetsstyring og solcelleanlæg, funktionsegenskaber, tekniske parametre, panel- og ledningsdiagrammer, installation, netværksopsætning med Tuya Smart-appen, almindelige fejl og dimensioner. Essentiel guide til sikker og effektiv elektrisk styring.
Preview GEYA miniatureafbrydere, kontaktorer og omskiftere katalog | Tekniske specifikationer
Omfattende katalog fra GEYA med detaljerede oplysninger om miniatureafbrydere (MCB), fejlstrømsafbrydere (RCCB), fejlstrømsafbrydere med overstrømsbeskyttelse (RCBO), støbte afbrydere (MCCB), AC-kontaktorer, automatiske omskiftere og intelligente afbrydere. Indeholder tekniske specifikationer, anvendelsesområde, produktfunktioner og overholdelsesoplysninger for forskellige modeller, der betjener industrielle, kommercielle og private applikationer.
Preview GEYA WiFi-seriens intelligente miniatureafbryder - Betjeningsvejledning
Detaljerede betjeningsvejledninger og ofte stillede spørgsmål til GEYA WiFi-seriens intelligente miniatureafbryder (ZJSB9-serien). Lær om installation, opsætning, fejlfinding, sikkerhed og anvendelse af elektrisk beskyttelse i smarte hjem.
Preview GEYA GPS8-10 bindtage/Strømbeskyttelses instruktionsmanual
Brugsanvisning til GEYA GPS8-10 bindtage/Current Protector, med detaljer om dens anvendelser, funktioner, tekniske parametre, ledningsføring, paneldiagram, parameterindstillinger, fabriksindstillinger og funktionsdiagrammer.