Notifier FSP-951

Notifier FSP-951 Intelligent Addressable Photo Detector

Instruktionsmanual

Model: FSP-951 | Brand: Notifier

1. Introduktion

The Notifier FSP-951 is an intelligent addressable photoelectric smoke detector designed for use with Notifier's FlashScan protocol. This device provides advanced detection capabilities for fire alarm systems, offering reliable smoke sensing and communication with the control panel. Its photoelectric sensing chamber is optimized to detect a wide range of combustion products, making it suitable for various applications. This manual provides essential information for the proper installation, operation, and maintenance of the FSP-951 detector.

2. Sikkerhedsoplysninger

Always adhere to local codes and regulations, as well as NFPA 72 (National Fire Alarm and Signaling Code) requirements, when installing and maintaining fire alarm devices. Disconnect power to the control panel before installing, removing, or servicing the detector. This device operates on a low-voltage circuit; however, improper wiring can damage the detector or the control panel. Refer to the control panel's documentation for specific wiring diagrams and compatibility information. Do not paint the detector, as this can interfere with its operation.

3. Komponenter overview

The FSP-951 detector consists of a detector head and a compatible mounting base (sold separately). The detector head contains the photoelectric sensing chamber, processing electronics, and communication circuitry. The mounting base provides the electrical connections to the fire alarm circuit and allows for easy installation and removal of the detector head.

Front view of the Notifier FSP-951 smoke detector

Figur 3.1: Forside view of the Notifier FSP-951 Intelligent Addressable Photo Detector. This image shows the white, circular detector head with its central sensing area.

Bag view of the Notifier FSP-951 smoke detector showing wiring terminals and model information

Figur 3.2: Bagside view of the Notifier FSP-951 detector head. This view displays the electrical contacts, model number (FSP-951), and manufacturing details, including the country of origin (Mexico) and a warning about connecting to a compatible fire alarm control panel.

Orange protective cap for the smoke detector

Figure 3.3: An orange protective cap, typically used to cover the detector during construction or dusty conditions to prevent contamination of the sensing chamber.

4. Opsætning og installation

Installation of the FSP-951 detector requires a compatible Notifier mounting base (e.g., B501, B224RB, B224BI, B200S, B200SR). Ensure the mounting location complies with all applicable codes and provides optimal smoke detection coverage.

4.1 Mounting the Base

  1. Secure the detector mounting base to a standard electrical box or directly to the ceiling using appropriate fasteners.
  2. Ensure the base is firmly attached and level.

4.2 Ledningsføring

Wire the mounting base according to the specific wiring diagram provided in the control panel's installation manual and the detector base's instructions. The FSP-951 uses two-wire addressable communication. Ensure correct polarity and secure all wire connections.

4.3 Installing the Detector Head

  1. Align the detector head with the mounting base.
  2. Rotate the detector clockwise until it drops into place and locks securely. A slight click may be heard.
  3. Verify that the detector is firmly seated and cannot be easily removed without using the removal tool or by twisting counter-clockwise.
Product label for Notifier FSP-951

Figure 4.1: Product label for the Notifier FSP-951, showing the model number, color (WHITE), and UPC (734038305157). This label is typically found on the product packaging.

5. Betjeningsvejledning

Once properly installed and powered, the FSP-951 detector continuously monitors the air for the presence of smoke. It communicates its status to the fire alarm control panel using the FlashScan protocol.

5.1 LED-indikatorer

  • Normal drift: The detector's LED will flash periodically (e.g., every few seconds) to indicate normal communication with the control panel.
  • Alarmtilstand: If smoke is detected, the LED will illuminate steadily (or flash rapidly, depending on panel programming) and the detector will send an alarm signal to the control panel.
  • Problemtilstand: A specific flash pattern or no illumination may indicate a trouble condition (e.g., dirty chamber, internal fault). Refer to the control panel's display for detailed trouble messages.

5.2 Test af detektoren

Regular testing of the smoke detector is crucial to ensure its proper operation. Consult NFPA 72 for recommended testing frequencies.

  • Funktionstest: Use an approved aerosol smoke stimulant to test the detector. Apply the stimulant to the detector's sensing chamber until an alarm is initiated.
  • Magnet Test: Some bases allow for a magnet test. Refer to the base's documentation for details.
  • After testing, ensure the detector resets and returns to normal supervisory mode.

6. Vedligeholdelse

Proper maintenance ensures the longevity and reliable operation of your FSP-951 detector.

6.1 Rengøring

Dust and debris can accumulate in the sensing chamber, leading to false alarms or reduced sensitivity. Clean the detector annually or as needed.

  1. Afbryd strømmen til brandalarmcentralen.
  2. Gently twist the detector head counter-clockwise to remove it from the mounting base.
  3. Use a vacuum cleaner with a soft brush attachment to remove dust from the exterior and the sensing chamber openings.
  4. Do not use cleaning solvents or liquids on the detector.
  5. Reinstall the detector head by aligning it with the base and twisting clockwise until it locks.
  6. Genopret strømmen til kontrolpanelet, og bekræft normal drift.

6.2 Udskiftning

Smoke detectors have a limited lifespan. Consult the manufacturer's recommendations and local codes for the recommended replacement interval, typically 10 years from the date of manufacture.

7. Fejlfinding

This section addresses common issues you might encounter with the FSP-951 detector.

ProblemMulig årsagLøsning
Detector LED not flashingNo power, wiring error, detector not seated correctly, or internal fault.Check power to the panel. Verify wiring connections. Ensure detector is fully seated on its base. If problem persists, replace detector.
Falske alarmerDust/debris in chamber, high humidity, cooking fumes, or improper placement.Clean the detector (see Section 6.1). Relocate if frequently exposed to non-fire smoke sources.
Trouble signal on panelDirty chamber, internal fault, or communication issue.Check the control panel display for specific trouble codes. Clean the detector. If trouble persists, replace the detector.
Detector does not alarm during testInsufficient smoke stimulant, faulty detector, or wiring issue.Ensure adequate smoke stimulant is applied. Verify wiring. Replace detector if necessary.

For persistent issues, consult a qualified fire alarm technician or contact Notifier technical support.

8. Specifikationer

AttributDetalje
MærkeUnderretning
ModelnummerFSP-951
SensortypePhotoelectric (Photo Sensor)
TeknologiFlashScan
StrømkildePlug-in (from fire alarm control panel)
FarveHvid
Produktdimensioner5" D x 5" B x 2" H
Varens vægt4.61 ounce
AlarmtypeVisual (LED indicator)
Øverste temperaturvurdering57 grader Celsius
UPC734038305157
FabrikantMEDDELELSE

9. Garanti og support

For specific warranty information, please refer to the documentation provided with your purchase or contact Notifier directly. Notifier products are typically covered by a limited warranty against defects in materials and workmanship.

For technical support, product inquiries, or service, please contact your authorized Notifier distributor or visit the official Notifier website. You can also find general product information on the Notifier brand page on Amazon.

Relaterede dokumenter - FSP-951

Preview Installation og vedligeholdelse af Notifier FSP-951 og FSP-951-IV intelligente fotoelektriske røgsensorer
Dette dokument indeholder installations- og vedligeholdelsesvejledning til Notifier FSP-951 og FSP-951-IV intelligente fotoelektriske røgsensorer. Det beskriver produktspecifikationer, retningslinjer for ledningsføring, testprocedurer, rengøringsmetoder og overholdelsesoplysninger for branddetekteringssystemer.
Preview Notifier FSP-751 and FSP-751T Intelligent Photoelectronic Smoke Sensors Installation and Maintenance Instructions
Installation and maintenance instructions for Notifier FSP-751 and FSP-751T intelligent photoelectronic smoke sensors, including general description, specifications, wiring, testing, and cleaning procedures.
Preview Notifier DHX-501 røgdetektor til luftkanal Installations- og vedligeholdelsesmanual
Denne manual indeholder detaljerede installations-, ledningsførings-, test- og vedligeholdelsesprocedurer for Notifier DHX-501 intelligent luftkanalrøgdetektorhus. Den dækker generelle beskrivelser, komponentlister, sikkerhedsadvarsler, trinvis installation, periodisk vedligeholdelse og specifikationer til brug med Notifier CPX-551 og SDX-551 detektorhoveder.
Preview Installationsvejledning til Notifier FST-951-SELFT Intelligent Programmerbar Temperatur Selvtest Sensor
Omfattende installations- og vedligeholdelsesvejledning til Notifier FST-951-SELFT intelligent programmerbar temperaturselvtestsensor. Detaljeret specifikationer, ledningsføringsprocedurer, selvtest- og manuelle testmetoder, rengøringsinstruktioner og overholdelsesoplysninger for denne UL 521-godkendte brandalarmenhed.
Preview FSP-851R Intelligent fotoelektrisk røgsensor Installation og vedligeholdelse
Installations- og vedligeholdelsesvejledning til FSP-851R intelligent fotoelektrisk røgsensor med fjerntestfunktion, designet til kanalanvendelser. Indeholder specifikationer, ledningsføringsvejledninger, testprocedurer og rengøringsinstruktioner.
Preview Notifier SLC-ledningsføringsmanual: Installationsvejledning til intelligent kontrolpanel
Omfattende ledningsføringsmanual til Notifier Intelligent Control Panel SLC-enheder. Dækker installation, ledningsføringskrav, enhedsspecifikationer og sikkerhedsforanstaltninger for brandalarmsystemer, der understøtter forskellige Notifier FACP'er.