Schneider Electric LC1D12EHE

Schneider Electric TeSys Deca Green LC1D12EHE Kontaktor Brugsanvisning

Model: LC1D12EHE

1. Introduktion

This manual provides essential information for the safe and effective installation, operation, and maintenance of the Schneider Electric TeSys Deca Green LC1D12EHE Contactor. This device is designed for integration into control systems, primarily for motor starter applications.

The TeSys D Green contactors are engineered for reliability and performance in industrial electrical systems. Please read this manual thoroughly before proceeding with any installation or operation.

2. Produktfunktioner

  • Type: IEC contactor, TeSys Deca Green, non-reversing.
  • Nuværende vurdering: 12A inductive.
  • Hestekræfter vurdering: 7.5HP at 480VAC (3-phase).
  • Short Circuit Current Rating (SCCR): Up to 100kA when used with appropriate protection.
  • Coil Voltage: 48/130VAC/VDC wide band electronic coil, low consumption.
  • Hjælpekontakter: One normally open (NO) and one normally closed (NC) built-in (NC contact is mirror certified).
  • Montering: DIN rail or direct panel mounting.
  • Terminaler: Skrue clamp terminals for load and auxiliary connections.
  • Certificeringer: UL, CSA, IEC, CCC, EAC, Marine standards. RoHS/REACh compliant (Green Premium product).

3. Sikkerhedsoplysninger

WARNING: Risk of electric shock or explosion.

  • Installation, adjustment, repair, and maintenance must be performed by qualified personnel only.
  • Afbryd al strøm, før du arbejder på udstyret.
  • Brug altid korrekt nominel voltage sensing devices to confirm power is off.
  • Brug kun den angivne mængdetage for the control coil.
  • Ensure proper grounding and wiring according to local and national electrical codes.
  • Manglende overholdelse af disse instruktioner kan resultere i dødsfald, alvorlig personskade eller beskadigelse af udstyr.

4. Opsætning og installation

The LC1D12EHE contactor can be mounted on a DIN rail or directly to a panel using screws.

4.1. Montering

DIN-skinnemontering:

  1. Ensure the DIN rail is securely fastened within the enclosure.
  2. Hook the top edge of the contactor onto the DIN rail.
  3. Press the bottom of the contactor firmly until it clicks into place.

Panelmontering:

  1. Identify the mounting holes on the contactor base.
  2. Mark and drill appropriate holes on the panel surface.
  3. Secure the contactor using screws of suitable size and length.

4.2. Ledninger

Refer to the wiring diagram provided with your specific application or system. The contactor features screw clamp terminals for both power and auxiliary connections.

  • Power Terminals (1L1, 3L2, 5L3, 2T1, 4T2, 6T3): Connect the main power circuit to these terminals. Ensure correct phase sequence for 3-phase applications.
  • Control Coil Terminals (A1, A2): Connect the 48-130VAC/VDC control voltage til disse terminaler.
  • Auxiliary Contacts (13 NO, 14 NO, 21 NC, 22 NC): Use these contacts for control circuit interlocking, signaling, or other auxiliary functions.

Always verify all connections are tight and secure before applying power.

Schneider Electric TeSys Deca Green LC1D12EHE Contactor, front-side view

Figur 1: Forside view of the LC1D12EHE Contactor, showing main power terminals (1L1, 3L2, 5L3, 2T1, 4T2, 6T3), auxiliary contacts (13 NO, 14 NO, 21 NC, 22 NC), and coil terminals (A1, A2).

5. Betjening

The TeSys Deca Green contactor is designed for switching electrical loads, primarily motors, in industrial control applications. When the appropriate control voltage (48-130VAC/VDC) is applied to the coil terminals (A1 and A2), the contactor's main contacts close, allowing power to flow to the connected load.

  • Aktivering af spolen: Applying the specified voltage to A1 and A2 will energize the coil, causing the main power contacts (1L1-2T1, 3L2-4T2, 5L3-6T3) to close. Simultaneously, the built-in auxiliary contacts will change state (NO contacts close, NC contacts open).
  • Afbrydelse af spolen: Fjernelse af voltage from A1 and A2 will de-energize the coil, causing the main power contacts to open and the auxiliary contacts to return to their original state.

Ensure the control circuit is properly designed and protected to prevent unintended operation or damage.

6. Vedligeholdelse

Regular inspection and maintenance are crucial for ensuring the long-term reliability and safe operation of the contactor.

  • Strømafbrydelse: Always disconnect all power to the contactor and associated circuits before performing any maintenance.
  • Visuel inspektion: Undersøg kontaktoren regelmæssigt for tegn på slid, skader, misfarvning eller løse forbindelser. Kontroller for ophobning af støv eller snavs.
  • Terminaltæthed: Verify that all screw clamp terminals are securely tightened. Loose connections can lead to overheating and component failure.
  • Contact Condition: While the contactor is de-energized, visually inspect the main contacts for excessive pitting or erosion. Severely worn contacts may require replacement of the contactor.
  • Rensning: Use a dry, lint-free cloth to clean the exterior of the contactor. Do not use solvents or abrasive cleaners.

Do not attempt to repair internal components. If the contactor is damaged or malfunctioning, replace the unit.

7. Fejlfinding

This section provides guidance for common issues. For complex problems, consult a qualified electrician or Schneider Electric technical support.

ProblemMulig årsagLøsning
Contactor does not energize (coil does not pull in)
  • Ingen kontrol voltage til A1/A2.
  • Forkert kontrol voltage.
  • Open circuit in control wiring.
  • Defekt spole.
  • Bekræft kontrolvolumentage at A1/A2.
  • Sørg for voltage matches 48-130VAC/VDC.
  • Check control circuit for breaks, fuses, or tripped breakers.
  • Replace contactor if coil is confirmed faulty.
Contactor energizes but load does not receive power
  • No main power to L1/L2/L3.
  • Open circuit in load wiring.
  • Damaged main contacts.
  • Verify main power supply.
  • Check load circuit for breaks, fuses, or tripped breakers.
  • Udskift kontaktor.
Kontaktor brummer overdrevent
  • Løs montering.
  • Foreign object in magnet assembly.
  • Forkert spolevolumentage.
  • Spænd monteringsskruerne.
  • Inspect and clean magnet assembly (with power off).
  • Bekræft spolevolumentage.

8. Specifikationer

ParameterVærdi
ModelnummerLC1D12EHE
MærkeSchneider Electric
Contactor TypeIEC, TeSys Deca Green, Non-reversing
Current Rating (Inductive)12A
Horsepower Rating (3-Phase)
  • 3HP at 200-208VAC
  • 3HP at 240VAC
  • 7.5HP at 480VAC
  • 10HP at 600VAC
Horsepower Rating (Single-Phase)
  • 0.5HP at 115VAC
  • 2HP at 240VAC
Short Circuit Current Rating (SCCR)
  • Up to 85kA with 480VAC up to 35A circuit breaker
  • Up to 100kA with 600VAC 30A Class J or CC fuse
Coil Voltage48-130VAC/VDC (Wide Band Electronic Coil)
Antal poler3 Phase, 3 NO (Main Contacts)
Hjælpekontakter1 NO (Normally Open), 1 NC (Normally Closed, mirror certified)
TerminalerSkrue Clamp
MonteringDIN Rail or Panel Mount
Dimensioner (H x B x D)3.03 tommer x 1.77 tommer x 3.39 tommer
Vægt0.82 lbs (13.12 ounce)
CertificeringerUL, CSA, IEC, CCC, EAC, Marine, RoHS/REACh (Green Premium)

9. Garanti og support

For warranty information, please refer to the official Schneider Electric website or contact your authorized distributor. Schneider Electric products are typically covered by a standard manufacturer's warranty against defects in materials and workmanship.

For technical assistance, product support, or to locate a service center, please visit the Schneider Electric official webwebsted eller kontakt deres kundeserviceafdeling.

Relaterede dokumenter - LC1D12EHE

Preview Schneider Electric TeSys Katalog 2024: Motorstyringsløsninger
Udforsk Schneider Electrics TeSys-katalog 2024, der byder på innovative og forbundne løsninger til motorstartere, styring, beskyttelse og strømstyring. Oplev et århundredes ekspertise inden for motorstyringsteknologi.
Preview Schneider Electric TeSys Deca kontaktor installations- og sikkerhedsvejledning
Omfattende vejledning til installation og betjening af Schneider Electric TeSys Deca-kontaktorer (CAD32-50A, LC1D09-32A). Indeholder sikkerhedsadvarsler, ledningsdiagrammer og tekniske specifikationer.
Preview Schneider Electric TeSys Control: Katalog over kontaktorer og motorstartere
Udforsk Schneider Electrics TeSys Control-katalog, der indeholder et bredt udvalg af SK-, K-, Deca- og modulære kontaktorer, reverserende kontaktorer og vigtige motorstyringskomponenter som afbrydere og relæer.
Preview Schneider Electric ATS480 Softstarter SCCR-klassificeringer og kompatibilitetsvejledning
Find detaljerede kortslutningsstrømsklassificeringer (SCCR) og kompatible komponentdata for Schneider Electric Altivar ATS480 softstartere, testet i henhold til UL60947-4-2 for elektrisk systemsikkerhed og ydeevne.
Preview Schneider Electric TeSys Deca-kontaktorer i LC1D- og LC2D-serien
Omfattende guide til Schneider Electric TeSys Deca-kontaktorer, inklusive LC1D- og LC2D-serien. Dækker produktspecifikationer, installation, sikkerhedsadvarsler og tilbehørskompatibilitet.
Preview LAD8N11 TeSys D IEC kontaktblok - Schneider Electric Tekniske Specifikationer
Detaljerede tekniske specifikationer, beskrivelse af måltegninger og producentinformation for Schneider Electric LAD8N11 TeSys D IEC kontaktblok. Dette 1NO 1NC sidemonterede tilbehør er til TeSys D IEC kontaktorer og styrerelæer.