1. Introduktion
This manual provides comprehensive instructions for the installation, operation, and maintenance of the Bemko TS-GM1 24-Hour Mechanical Timer Switch. Please read this manual thoroughly before installation and use to ensure safe and efficient operation. This device is designed to control electrical circuits based on a programmed 24-hour schedule, suitable for applications such as automatic lighting, control circuits, and other timed operations.
2. Sikkerhedsinstruktioner
- Always disconnect power to the circuit before attempting any installation, wiring, or maintenance.
- Installationen skal udføres af en kvalificeret elektriker i overensstemmelse med alle lokale og nationale el-forskrifter.
- Do not exceed the specified maximum load capacity of 16A or 3500W. Overloading can cause damage to the device and create a fire hazard.
- This device is designed for indoor use only within the specified operating temperature range (-10 °C to +50 °C).
- Ensure proper grounding where applicable and secure all wire connections firmly to prevent loose contacts.
- Do not open or attempt to repair the device. Refer servicing to qualified personnel.
3. Pakkens indhold
- 1x Bemko TS-GM1 24-Hour Mechanical Timer Switch
4. Produktet er slutview
The Bemko TS-GM1 is a compact 24-hour mechanical timer switch designed for DIN rail mounting. It features a rotating dial for time setting and programming segments for scheduling ON/OFF cycles.



5. Opsætning
5.1 Montering
The Bemko TS-GM1 timer is designed for DIN rail mounting (DIN/TH/TS 35 mm standard) inside an electrical enclosure. Snap the timer onto the DIN rail until it clicks securely into place.
5.2 Ledningsføring
ADVARSEL: Sørg for, at strømmen er afbrudt før ledningsføring.
- Identify the input terminals (L for Live, N for Neutral) and output terminals (typically marked 1 and 2 for the switching contact). Refer to the wiring diagram printed on the device.
- Connect the incoming power supply (220-240V AC, 50/60Hz) to the input terminals.
- Connect the load (e.g., light fixture, appliance) to the output terminals. The timer features a 1 NO (Normally Open) switching contact.
- Use wires with a cross-section of 2.5 mm² for all connections. Ensure all screw terminals are tightened securely to prevent loose connections and overheating.
5.3 Indstilling af starttidspunkt
After wiring, restore power. Rotate the central dial clockwise until the current time aligns with the arrow indicator on the timer's face. The dial is marked for 24 hours (e.g., 18 for 6 PM).
6. Betjeningsvejledning
6.1 Programmering af tænd/sluk-cyklusser
The timer allows for up to 96 ON/OFF switching cycles within a 24-hour period. Each segment on the dial represents 15 minutes.
- To program an ON period, push the corresponding segments outwards.
- To program an SLUKKET period, leave the segments pushed inwards.
F.eksample, to turn a device ON from 7:00 AM to 8:00 AM, push out the four segments corresponding to 7:00, 7:15, 7:30, and 7:45.
6.2 Operating Modes (Manual Override)
The timer typically includes a manual override switch, often a small lever or slider, on its front face. This switch allows you to temporarily bypass the programmed schedule:
- Automatisk tilstand: Position the switch to the clock symbol or 'AUTO' setting. The timer will operate according to the programmed segments.
- Kontinuerlig ON: Position the switch to 'I' or 'ON'. The connected device will remain ON, regardless of the programmed schedule.
- Continuous OFF: Position the switch to 'O' or 'OFF'. The connected device will remain OFF, regardless of the programmed schedule.
Remember to return the switch to the automatic position for programmed operation to resume.
7. Vedligeholdelse
The Bemko TS-GM1 timer requires minimal maintenance. Periodically inspect the wiring connections for tightness and ensure the device is free from dust and debris. Clean the exterior with a dry, soft cloth. Do not use abrasive cleaners, solvents, or liquids directly on the device.
8. Fejlfinding
- Timer not switching:
- Check power supply connections to ensure they are secure and live.
- Ensure the manual override switch is in the automatic (clock symbol) position.
- Verify that the programming segments are correctly pushed out for the desired ON periods.
- Forkert timing:
- Ensure the current time is correctly set on the dial.
- Check for power interruptions. The timer has a power reserve of up to 100 hours, but prolonged outages may require resetting the current time.
- Enheden tænder ikke:
- Bekræft input voltage (220-240V) and frequency (50/60Hz) are correct.
- Kontroller afbryderen eller sikringen til kredsløbet.
- Ensure the load is properly connected and functional.
9. Specifikationer
| Modelnummer | A26-TSGM1 |
| Mærke | Bemko |
| Strømforsyning | ~ 220-240 V AC |
| Frekvens | 50/60 Hz (± 10%) |
| Maks. Skiftende strøm | 3500 W |
| Maks. Indlæs strøm | 16 A |
| Strømforbrug | 10 A/250 V ~ (internal) |
| Skiftekapacitet | 0.5 |
| Nøjagtighed | ± 3 seconds / 1 day |
| Power Reserve | Max 100 hours (after power cut) |
| Programmeringsintervaller | 96 times / 24 hours; 15-minute segments |
| Connection Wire Size | 2.5 mm² |
| Driftstemperatur | -10 °C til +50 °C |
| Beskyttelsesklasse | IP20 |
| Isoleringsklasse | II |
| Monteringstype | DIN rail (DIN/TH/TS 35 mm) |
| Skiftekontakt | 1 NO (Normalt åben) |
| Materiale | Plast |
| Certifikater | CE, RoHS, EAC |
| Dimensioner (L x B x H) | 6.3 x 1.8 x 9.2 cm |
| Vægt | 82 g |
10. Garanti og support
For warranty information or technical support regarding your Bemko TS-GM1 24-Hour Mechanical Timer Switch, please contact your retailer or the manufacturer, Bemko. Keep your purchase receipt as proof of purchase for any warranty claims.