1. Introduktion
This manual provides essential information for the safe and efficient operation of your APC Smart-UPS SRT1000XLA. Please read this manual thoroughly before installation and use, and retain it for future reference.
2. Sikkerhedsoplysninger
Overhold altid følgende sikkerhedsforanstaltninger for at forhindre personskade eller beskadigelse af udstyret.
- Åbn ikke UPS-kabinettet. Der er ingen dele indeni, som brugeren kan servicere.
- Ensure proper grounding. Connect the UPS to a grounded outlet.
- Do not block ventilation openings. Maintain adequate airflow around the unit.
- Undgå at installere UPS'en i områder med meget støv, fugtighed eller ekstreme temperaturer.
- Frakobl UPS'en fra strømkilden, før du udfører vedligeholdelse eller rengøring.
3. Produktet er slutview
3.1 Komponenter

Figur 3.1: Forside View of UPS. This image displays the front of the APC Smart-UPS SRT1000XLA, highlighting its tower form factor and the integrated LCD screen for status monitoring.

Figur 3.2: Bagside View of UPS. This image illustrates the back panel of the UPS, detailing the NEMA 5-15P input, six NEMA 5-15R output receptacles, and various communication ports for connectivity.
3.2 Nøglefunktioner
- 1000VA / 900W Pure Sine Wave Online UPS: Provides high-quality power output suitable for sensitive electronic equipment.
- Double-Conversion On-Line Topology: Ensures continuous, clean, and stable power by isolating connected equipment from raw utility power.
- Skalerbar kørselstid: Compatible with external battery packs (SRT48RMBP, sold separately) to extend backup time. Up to 10 external battery packs can be connected.
- NEMA 5-15P Input / (6) NEMA 5-15R Output: Standard connections for typical office and IT equipment.
- Energy-Star Certified: Meets energy efficiency requirements, reducing operational costs.
- Intuitiv LCD-grænseflade: Provides real-time status updates and configuration options.
- Udskiftelige batterier i realtid: Allows for battery replacement without interrupting power to connected devices.
- Intelligent batteristyring: Features battery replacement recommendations, temperature-compensated charging, periodic self-tests, and disconnect notifications.
4. Opsætning
4.1 Udpakning og inspektion
- Pak forsigtigt UPS'en og dens tilbehør ud af emballagen.
- Inspect the unit for any shipping damage. If damage is found, notify the carrier and dealer.
- Retain the packaging materials for future use or return.
4.2 Placering
Place the UPS in a protected area that is free from excessive dust, humidity, and is well-ventilated. Ensure sufficient clearance around the unit for proper airflow.
4.3 Første tilslutning
- Connect the UPS to a grounded 120V NEMA 5-15R wall outlet using the provided NEMA 5-15P input cable.
- Allow the UPS to charge its internal batteries for at least 24 hours before connecting critical equipment to ensure full runtime capability.
- Connect your equipment to the NEMA 5-15R output receptacles on the rear of the UPS.
5. Betjeningsvejledning
5.1 Tænd/sluk
- For at tænde: Press and hold the power button on the front panel until the LCD display illuminates.
- For at slukke: Press and hold the power button until the LCD display turns off. Ensure all connected equipment is properly shut down before powering off the UPS.
5.2 LCD-skærmnavigation
The LCD display provides real-time status information and allows for configuration adjustments. Use the navigation buttons (up, down, enter, escape) to browse menus and select options.
5.3 Batteridrift
I tilfælde af en magt outage, the UPS will automatically switch to battery mode, providing continuous power to connected devices. The LCD will indicate "On Battery" status. The duration of battery backup depends on the connected load and battery charge level.
6. Vedligeholdelse
6.1 Udskiftning af batteri
The UPS features user-replaceable, hot-swappable batteries. When the UPS indicates a battery fault or low battery life, replace the battery module. Refer to the specific battery replacement instructions provided with the replacement battery kit.
6.2 Rengøring
Rengør UPS'ens yderside regelmæssigt med en blød, tør klud. Brug ikke flydende rengøringsmidler eller rengøringsmidler på aerosolbasis. Sørg for, at ventilationsåbningerne er fri for støv og snavs.
6.3 firmwareopdateringer
Check the APC website for available firmware updates for your UPS model. Firmware updates can improve performance and add new features. Follow the instructions provided with the firmware update package carefully.
7. Fejlfinding
This section provides solutions to common issues you may encounter with your UPS.
| Problem | Mulig årsag | Løsning |
|---|---|---|
| UPS'en tænder ikke. | No input power; discharged battery. | Verify the input power cable is securely connected to a live outlet. Allow the battery to charge for 24 hours. |
| UPS'en bipper kontinuerligt. | On battery mode; overload condition. | Check if utility power is present. Reduce the connected load if an overload alarm is active. |
| Kort batterilevetid. | Batteriet er ikke fuldt opladet; batteri er gammelt. | Ensure the battery has charged for at least 24 hours. Consider replacing the battery if it is old. |
If the problem persists after attempting these solutions, contact APC technical support.
8. Specifikationer
| Attribut | Værdi |
|---|---|
| Model | SRT1000XLA |
| Kapacitet | 1000VA / 900W |
| Input bindtage | 120 volt |
| Udgang Voltage | 120 Volts (Pure Sine Wave) |
| Indgangsforbindelse | NEMA 5-15P |
| Udgangsforbindelser | (6) NEMA 5-15R |
| Batteritype | Forseglet blysyre |
| Produktmål (H x B x D) | 20 x 3.4 x 17 tommer |
| Varens vægt | 48.5 pund |
9. Garanti og support
9.1 Produktgaranti
The APC Smart-UPS SRT1000XLA comes with a 3-year warranty on the UPS unit og en 2-year warranty on the internal battery. Denne garanti dækker fejl i materialer og udførelse ved normal brug.
9.2 Returneringspolitik
This product is eligible for a 30-day easy returns policy. Please refer to your purchase agreement or retailer's policy for specific return procedures.
9.3 Teknisk support
For technical assistance, troubleshooting beyond this manual, or warranty claims, please contact APC Customer Support. Visit the official APC webhjemmeside for kontaktoplysninger og yderligere ressourcer: www.apc.com