1. Produktet er slutview
The BEST BAL700 Emergency Lighting Ballast is designed to convert new or existing fluorescent fixtures into emergency lighting units. This ballast allows fluorescent lighting fixtures to operate for both normal and emergency purposes. In the event of a power outage, it automatically switches to battery power, providing a minimum of 90 minutes of emergency illumination. It is compatible with a wide range of fluorescent lamps and AC ballasts.
Image 1.1: The BEST BAL700 Emergency Lighting Ballast, showing its compact white housing and multi-colored wiring harness for connection to a fluorescent fixture.
2. Nøglefunktioner
- Dual Voltage Kompatibilitet: Fungerer på både 120V og 277V AC strømforsyninger.
- Nødbelysning: Provides a minimum of 90 minutes of emergency lighting with a maximum initial lumen output of 700 lumens.
- Automatisk overførsel: Features an internal solid-state transfer switch that automatically connects the internal battery to the fluorescent lamp(s) during power interruptions.
- AC Output Enhancement: Ensures compatibility with newer lamp technologies and contributes to prolonged lamp liv.
- Genopladeligt batteri: Equipped with a long-life, maintenance-free, rechargeable sealed NiCd battery.
- Hurtig genopladning: Fully automatic solid-state, two-rate charger recharges a discharged battery within 24 hours.
- Test Switch and Indicator: Includes an LED charge rate/power ON indicator light and a push-to-test switch for mandated code compliance testing.
- Tidsforsinkelse: Incorporates a time delay enhancement to overcome end-of-life circuit protection in fluorescent lamps.
- Damp Placering bedømt: UL listed for installation in damp steder.
- Kompakt design: Durable painted steel construction in a white finish, designed to fit most fluorescent fixtures.
3. Tekniske specifikationer
| Attribut | Værdi |
|---|---|
| Modelnummer | BAL700 |
| Lumen Output (Emergency) | 700 lumens (initial) |
| Nøddriftstid | Minimum 90 minutter |
| Input bindtage | 120/277V AC, 60Hz |
| Batteritype | Sealed NiCd (Nickel Cadmium) |
| Batteriets genopladningstid | 24 timer |
| Dimensioner (L x B x H) | 9.5 x 2.4 x 1.5 tommer |
| Vægt | Cirka 0.01 ounce (Note: This weight seems incorrect based on typical ballast weights, please verify with manufacturer if critical.) |
| Materiale til hus | Malet stål |
| Driftstemperatur | UL opført for damp steder |
| Lamp Kompatibilitet | Most one, two, three, and four-lamp electronic standard and dimming AC ballasts. Operates one 17W-40W T8 through T12, two 13W-39W, one 13W-42W 4-pin compact or one 18W-40W 4-pin compact fluorescent lamps. |
| Certificeringer | UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes, UL listed for damp steder. |
Billede 3.1: En side view of the BEST BAL700 Emergency Lighting Ballast, highlighting its compact form factor suitable for various fixture installations.
4. Installationsvejledning
4.1. Sikkerhedsforanstaltninger
- ADVARSEL: Risiko for elektrisk stød. Afbryd strømmen ved afbryderen eller sikringsboksen før installation eller service.
- Installation should be performed by a qualified electrician in accordance with the National Electrical Code (NEC) and local codes.
- Sørg for, at input voltage (120V or 277V) matches the building's electrical supply.
- Do not use with dimming ballasts unless specifically rated for such use.
- Må ikke installeres i nærheden af gas- eller elektriske varmeapparater.
4.2. Montering
The BAL700 ballast is suitable for installation inside, on top of, or remotely from the fixture. Its compact design allows for versatile placement within most fluorescent fixtures.
- Choose a mounting location that allows for proper heat dissipation and access for maintenance.
- Secure the ballast using appropriate fasteners (not included) through the mounting tabs.
4.3. Ledninger
Refer to the wiring diagram provided on the ballast label for specific connections. General steps include:
- Connect the unswitched AC power supply (120V or 277V) to the ballast's input wires.
- Connect the ballast's output wires to the fluorescent lamp(s) and the existing AC ballast as per the diagram.
- Sørg for, at alle forbindelser er sikre og isolerede.
- Install the LED test switch in an accessible location on the fixture or wall plate.
Note: The BAL700 can be used in both switched and unswitched fixtures. For switched fixtures, ensure the emergency ballast receives unswitched power to allow for emergency operation regardless of the wall switch position.
5. Betjeningsvejledning
5.1. Normal drift
When AC power is present, the BAL700 ballast charges its internal battery. The connected fluorescent lamp(s) will operate normally via the existing AC ballast. The LED indicator light on the test switch will illuminate, indicating that the battery is charging and the unit is ready for emergency operation.
5.2. Emergency Operation
Upon interruption of normal AC power, the BAL700 automatically switches to emergency mode. The internal solid-state transfer switch activates, powering one fluorescent lamp from the internal NiCd battery for a minimum of 90 minutes. When AC power is restored, the unit automatically returns to normal operation and begins recharging the battery.
5.3. Testing the Unit
Regular testing is required to ensure proper emergency function and compliance with safety codes.
- Månedlig test: Press and hold the push-to-test switch for at least 30 seconds. The emergency lamp should illuminate. Release the switch; the lamp should extinguish (if AC power is present).
- Årlig test: Conduct a full 90-minute discharge test. Interrupt AC power to the fixture for 90 minutes. The emergency lamp should remain illuminated for the entire duration. After the test, restore AC power and allow the battery to recharge for 24 hours.
Note: Keep records of all tests for inspection purposes.
6. Vedligeholdelse
The BEST BAL700 Emergency Lighting Ballast is designed for low maintenance. The NiCd battery is sealed and maintenance-free. However, regular checks are recommended:
- Visuel inspektion: Periodically inspect the unit for any visible damage, loose connections, or signs of overheating.
- Opladning af batteri: After any emergency discharge or test, ensure the unit has at least 24 hours of uninterrupted AC power to fully recharge the battery.
- Rensning: If necessary, gently wipe the exterior of the ballast with a dry, soft cloth. Do not use abrasive cleaners or solvents.
- Udskiftning af batteri: While designed for long life, NiCd batteries have a finite lifespan. If the unit fails to provide 90 minutes of emergency illumination during an annual test, the battery may need replacement. Contact qualified service personnel for battery replacement.
7. Fejlfinding
| Problem | Mulig årsag | Løsning |
|---|---|---|
| Nødsituation lamp does not illuminate during test or power outage. |
|
|
| LED indicator light is off. |
|
|
| Nødsituation lamp illuminates for less than 90 minutes. |
|
|
Hvis fejlfindingstrinene ikke løser problemet, skal du kontakte kundesupport.
8. Garantioplysninger
The BEST BAL700 Emergency Lighting Ballast comes with a Fem års garanti against defects in material and workmanship. This warranty excludes lamps. For warranty claims or detailed terms and conditions, please refer to the original purchase documentation or contact BEST customer support.
9. Kundesupport
For technical assistance, installation questions, or warranty inquiries, please contact BEST customer support:
- Webwebsted: Visit the official BEST Lighting Products website for FAQs and contact information.
- Telefon: Refer to your product packaging or the manufacturer's webhjemmeside for det seneste kundeservicetelefonnummer.
- E-mail: General inquiries can often be sent via email forms available on the manufacturer's webwebsted.
When contacting support, please have your product model number (BAL700) and purchase date available.