Hubbell LHIRS1-G-WH

Hubbell Lighting LHIRS1-G-WH LightHAWK vægafbrydersensor brugermanual

Model: LHIRS1-G-WH

1. Introduktion

This manual provides detailed instructions for the installation, operation, and maintenance of the Hubbell Lighting LHIRS1-G-WH LightHAWK Wall Switch Sensor. This device is designed to automatically control lighting based on occupancy and ambient light levels, enhancing energy efficiency in various indoor environments.

2. Sikkerhedsoplysninger

ADVARSEL: Risk of electric shock. Installation should only be performed by a qualified electrician in accordance with all national and local electrical codes. Always turn off power at the circuit breaker or fuse box before installing or servicing this device. Failure to follow these instructions may result in serious injury or death.

3. Produktet er slutview

3.1 Nøglefunktioner

3.2 Komponenter

The Hubbell LightHAWK Wall Switch Sensor consists of the following primary components:

Front view of the Hubbell LightHAWK Wall Switch Sensor in white.

Figur 1: Forside view of the Hubbell LightHAWK Wall Switch Sensor. This image displays the front of the white Hubbell LightHAWK Wall Switch Sensor. It features a large rectangular sensor lens at the top, a smaller rectangular button below it, and a small indicator light at the bottom center, all set within a standard wall plate.

4. Installation og opsætning

Proper installation is crucial for optimal performance. This sensor requires a Universal Voltage Power Pack (Models UVPP or UVPPM) for operation, which is sold separately.

4.1 Trin før installation

  1. Sluk for strømmen: Locate the circuit breaker or fuse controlling the light fixture and turn off the power. Verify power is off using a voltage tester.
  2. Forbered ledningsføring: Ensure the electrical box has the necessary wiring (line, load, neutral, ground) for the sensor and power pack.
  3. Consult Power Pack Manual: Refer to the instruction manual for your specific Universal Voltage Power Pack (UVPP or UVPPM) for detailed wiring diagrams and instructions, as this sensor integrates with it.

4.2 Wiring the Sensor

Connect the sensor to the Universal Voltage Power Pack and the lighting load according to the wiring diagram provided with the power pack. Typically, connections will include:

Ensure all wire connections are secure and insulated with wire nuts.

4.3 Montering

Mount the sensor in a standard wall box. Ensure the sensor lens has an unobstructed view of the area to be controlled. Avoid mounting near heat sources, air vents, or in direct sunlight, which can interfere with sensor performance.

5. Betjeningsvejledning

The LightHAWK sensor offers flexible operation modes to suit different needs.

5.1 driftstilstande

5.2 Adjusting Settings (IntelliDAPT and Photocell)

The sensor features IntelliDAPT technology, which continuously analyzes the environment and automatically adjusts sensitivity and time delay settings for optimal performance. The integrated photocell also contributes to energy savings by preventing lights from turning on if sufficient natural light is present.

Specific adjustments for time delay, sensitivity, and photocell settings are typically performed via the control button or through a dedicated programming method. Refer to the detailed programming guide for the LHIRS1-G-WH sensor for precise instructions on how to configure these settings.

6. Vedligeholdelse

The Hubbell LightHAWK Wall Switch Sensor requires minimal maintenance.

7. Fejlfinding

If the sensor is not functioning as expected, review følgende almindelige problemer:

ProblemMulig årsagLøsning
Lights do not turn ON with occupancy.
  • Strømmen er slukket.
  • Sensor in Vacancy (Manual-ON) mode.
  • Ledningsfejl.
  • Sensor lens obstructed.
  • Utilstrækkelig bevægelse registreret.
  • Photocell preventing activation due to ambient light.
  • Tjek afbryderen.
  • Press the control button to turn ON lights or switch to Occupancy mode.
  • Verify wiring connections (consult power pack manual).
  • Clear any obstructions from the sensor lens.
  • Increase sensor sensitivity (refer to programming guide).
  • Adjust photocell settings or cover photocell temporarily for testing.
Lights do not turn OFF.
  • Kontinuerlig bevægelse registreret.
  • Time delay set too long.
  • Ledningsfejl.
  • Ensure no constant motion is within the sensor's view.
  • Adjust time delay to a shorter duration (refer to programming guide).
  • Verify wiring connections (consult power pack manual).
Lysene flimrer eller opfører sig uregelmæssigt.
  • Løs ledningsforbindelse.
  • Incompatible load type.
  • Interferens fra andre enheder.
  • Kontroller og fastgør alle ledningsforbindelser.
  • Ensure lighting load is compatible with the sensor and power pack.
  • Relocate sensor or identify source of interference.

If problems persist after attempting these solutions, contact Hubbell Lighting technical support or a qualified electrician.

8. Specifikationer

AttributDetalje
ModelnummerLHIRS1-G-WH
SensortypeDigital Passive Infrared (PIR)
TeknologiIntelliDAPT Self-Adaptive
Voltage120/277VAC (requires Universal Voltage Power Pack)
DækningsområdeOp til 1000 sq. ft.
DriftstilstandeOccupancy (Auto-ON), Vacancy (Manual-ON)
Yderligere funktionerPhotocell, Single Circuit Control
FarveHvid
Produktdimensioner4.2 x 1.8 x 1.75 tommer
Vægt5.12 ounce
FabrikantHubbell Lighting

9. Garanti og support

For specific warranty information, please refer to the documentation included with your product at the time of purchase or visit the official Hubbell Lighting website. Technical support and further assistance can be obtained by contacting Hubbell Lighting directly.

You can find more products and information from the brand at the Hubbell Store.

Relaterede dokumenter - LHIRS1-G-WH

Preview Installations- og justeringsvejledning til IWS-ZP-3P tilstedeværelsessensor
Omfattende installations- og justeringsvejledning til Hubbell IWS-ZP-3P tilstedeværelsessensor, med detaljerede indstillinger for ledningsføring, timing, følsomhed og fotocelle for optimal ydeevne.
Preview Trinetics UltraVac Solid Dielektriske Motordrevne Vakuumafbrydere: Installations- og betjeningsvejledning
Omfattende installations- og betjeningsvejledning til Trinetics UltraVac Solid Dielectric Motor Driven Vacuum Switches fra Hubbell. Dækker produktspecifikationer, dimensioner, elektriske tilslutninger, sikkerhedsadvarsler, håndtering og vedligeholdelse.
Preview Hubbell OMNI PBX varmepumpe vandvarmer betjenings- og vedligeholdelsesmanual
Omfattende drifts- og vedligeholdelsesmanual til Hubbell OMNI PBX varmepumpevandvarmer, der dækker installation, betjening, fejlfinding og garantioplysninger.
Preview Hubbell MULTI-CONNECT Indbyggede vægbokse - Bestillingsvejledning
En vejledning til bestilling af Hubbell MULTI-CONNECT indbyggede vægdåser, inklusive valg af vægdåser, modulære frontplader (snap-in og skruetype) og vægflanger. Detaljer om farvemuligheder, dimensioner og tilgængelige samlingskonfigurationer.
Preview Hot Box-kabinetter: Tekniske løsninger til udendørs infrastruktur
Udforsk det omfattende udvalg af Hot Box®-kabinetter, der er designet til optimal beskyttelse og nem vedligeholdelse af tilbageløbssikring, pumpe- og sprinkleraggregater. Opdag muligheder i aluminium, glasfiber og HDPE, der er konstrueret til at opfylde ASSE 1060-standarder og forskellige miljømæssige udfordringer.
Preview Hubbell Twist-Lock 50A jordstik og flangeindtag installationsvejledning
Officiel installationsvejledning fra Hubbell til Twist-Lock 50A jordstik og flangeindtag. Dækker ledningsføring, montering og sikkerhedsforanstaltninger for kvalificerede elektrikere.