Produkt overview
The Rectorseal Aspen Mini Lime Condensate Pump Kit is designed for efficient removal of condensed water from ductless mini-split AC systems. This compact unit integrates both the pump and reservoir, facilitating flexible installation options. It is engineered for quiet operation and easy maintenance, making it an ideal solution for managing condensate in various HVAC applications.

Image: Components of the Aspen Mini Lime Condensate Pump Kit, including the pump unit, tubing, and slimline cover.
Sikkerhedsoplysninger
Always disconnect power before installing or servicing the pump. Ensure all electrical connections comply with local codes and regulations. This device operates with electrical components and water; improper installation can lead to electric shock or fire. Do not operate the pump if it is damaged or if any wires are frayed. Keep out of reach of children.
- Læs alle instruktioner før brug.
- Brug passende personlige værnemidler (PPE) under installation og vedligeholdelse.
- Sørg for korrekt jording.
- Do not submerge the pump unit in water.
Opsætning og installation
The Aspen Mini Lime pump is designed for easy installation, either to the left or right of the evaporator unit. It integrates the pump and reservoir into a single unit, eliminating the need for separate connecting tubes or wires for the reservoir.
Nødvendige værktøjer:
- Skruetrækker sæt
- Afisoleringstænger
- Drill (if mounting to wall)
- Målebånd
- Niveau
Installationstrin:
- Forbered området: Ensure the area around the mini-split evaporator is clean and accessible. Identify the condensate drain outlet.
- Montering af pumpen: The pump can be mounted directly onto the reservoir. Position the pump unit in a location that allows for minimal suction lift from the evaporator's condensate tray. The slimline cover is designed to conceal the unit and line set.
- Tilslut afløbsledning: Connect the condensate drain line from the evaporator coil to the inlet of the pump's reservoir. Ensure a secure, watertight connection.
- Connect Discharge Line: Attach the discharge tubing from the pump's outlet to a suitable drain point, ensuring a continuous downward slope to prevent water traps. The pump can lift water up to 33 feet vertically.
- Elektriske forbindelser:
- Connect the pump's power supply wires to a suitable 100-250V AC power source. Refer to the wiring diagram provided with the product for specific connections.
- Safety Switch (NC Dry Contacts): Connect the 3A NC (Normally Closed) dry contacts to the AC unit's control circuit. This safety switch will shut down the AC unit if the pump reservoir reaches a high water level, preventing overflow. These contacts are rated at 5A inductive at 230V AC.
- Sikre komponenter: Secure all tubing and electrical wiring using appropriate fasteners or clips. Install the slimline cover to conceal the line set and pump unit for a clean finish.
- Test drift: After installation, power on the AC unit and observe the condensate drainage. Ensure the pump activates when the reservoir fills and effectively discharges water. Check for any leaks.
Betjeningsvejledning
The Aspen Mini Lime pump operates automatically. When condensate water from the AC unit fills the pump's reservoir to a predetermined level, the internal float switch activates the pump. The pump then discharges the water through the drain line until the reservoir level drops, at which point the pump deactivates.
- The pump is designed for non-continuous duty cycle.
- The sound level during operation is approximately 25.5dB(A).
- If the high-level safety switch is connected, the AC unit will shut off if the pump fails to drain water, preventing overflow.
Opretholdelse
Regular maintenance ensures optimal performance and longevity of your condensate pump. It is recommended to perform maintenance at least once a year, or more frequently in dusty environments.
Cleaning the Reservoir and Filter:
- Afbryd strømmen: Always turn off the power to the AC unit and the condensate pump before performing any maintenance.
- Access Reservoir: The transparent reservoir easily clips off for quick access. Carefully remove the elbow cover and detach the reservoir.
- Rengøring af komponenter: Remove any debris, sludge, or algae buildup from the reservoir, float switch, and filter screen. Use warm water and a mild detergent. Avoid abrasive cleaners.
- Inspicer slange: Check the inlet and outlet tubing for any blockages or kinks. Clear any obstructions.
- Saml igen: Reattach the reservoir and elbow cover securely. Ensure all connections are tight.
- Prøve: Restore power and verify proper operation by observing the pump's cycle.
Fejlfinding
If your Aspen Mini Lime pump is not functioning as expected, refer to the following common issues and solutions:
| Problem | Mulig årsag | Løsning |
|---|---|---|
| Pumpen kører ikke | No power; Clogged reservoir/float; Safety switch activated; Motor failure | Check power supply; Clean reservoir and float; Check safety switch wiring; Contact qualified technician |
| Pumpen kører kontinuerligt | Float stuck; Check valve faulty; Leak in discharge line; Excessive condensate production | Clean float; Inspect/replace check valve; Check for leaks; Verify AC unit size/humidity levels |
| Water overflow from reservoir | Pump not running (see above); Discharge line blocked/kinked; Pump undersized | Address pump not running; Clear discharge line; Ensure pump capacity matches AC unit BTU/hr |
| Overdreven støj | Air in pump; Pump not securely mounted; Debris in pump | Allow air to purge; Secure pump mounting; Clean pump/reservoir |
For issues not listed or if solutions do not resolve the problem, contact Rectorseal customer support or a qualified HVAC technician.
Specifikationer
| Feature | Detalje |
|---|---|
| Model | 83849 (Aspen Mini Lime) |
| Voltage | 100-250V AC |
| Wattage | 16 watt |
| Maks. Kapacitet | Op til 54,600 BTU/time |
| Flow Rate (Zero Head) | 2.9-3.2 GPH (Gallons Per Hour) |
| Flow Rate (33ft Head) | 1.3-1.5 GPH (Gallons Per Hour) |
| Lydniveau | 25.5dB(A) |
| Sikkerhedskontakter | 3A NC dry contacts rated @ 5A inductive at 230V AC |
| Lineset Elbow Casing Dimensions | H-5 1/4" x W-5 1/4" x D-2 3/4" |
| Lineset Duct Casing Dimensions | H-31" x W-5 1/4" x D-2 3/4" |
| Materiale | Plast |
| Varens vægt | 3.5 pund |
Garantioplysninger
Rectorseal products are manufactured to high standards. For specific warranty terms and conditions, please refer to the warranty card included with your product or visit the official Rectorseal webwebsted. Gem din købsbevis til garantikrav.
Kundesupport
For technical assistance, troubleshooting beyond this manual, or warranty inquiries, please contact Rectorseal customer support:
- Webwebsted: www.rectorseal.com
- Telefon: 1-800-231-3345
- Adresse: Se produktemballagen eller website for corporate address.
Når du kontakter support, bedes du have dit produktmodelnummer (83849) og købsdatoen klar.