1. Introduktion

This manual provides essential information for the safe and effective operation, maintenance, and troubleshooting of the Megger TDR500/3 Basic Handheld Time Domain Reflectometer. The TDR500/3 is a compact, portable instrument designed for accurately locating faults on metallic cables, such as opens, shorts, and impedance changes.

Please read this manual thoroughly before using the device to ensure proper understanding and to prevent damage to the instrument or injury to personnel.

2. Sikkerhedsoplysninger

WARNING: Always observe standard safety precautions when working with electrical equipment and cables. Failure to do so may result in serious injury or death.

3. Produktet er slutview

The Megger TDR500/3 is engineered for ease of use and precision in cable fault location. Its robust design and intuitive interface make it suitable for professional use in various industrial and scientific applications.

3.1 Nøglefunktioner

3.2 Enhedslayout

Megger TDR500/3 Handheld Time Domain Reflectometer with screen showing a trace, control buttons, and a rotary selector.

Figur 1: Forside view of the Megger TDR500/3. The device features a monochrome LCD at the top, displaying trace data, velocity factor (UF), and impedance (Z). Below the screen are navigation buttons and a backlight control. A central four-way directional pad and a 'HOLD' button are located mid-body. The lower section includes a large rotary selector with 'AUTO', 'OFF', TDR waveform, and 'Setup' (wrench) positions, along with the Megger TDR500/3 branding.

The TDR500/3 features a clear graphical display and a user-friendly control layout:

4. Opsætning

4.1 Strømforsyning til enheden

The Megger TDR500/3 operates on AC power. Connect the supplied AC adapter to the device's power input and then to a suitable AC power outlet. The device does not use internal batteries.

4.2 Connecting to Cables

Before connecting the TDR500/3 to any cable, ensure the cable is completely de-energized and isolated from all power sources. Connect the appropriate test leads (not included, but typically BNC or alligator clips) to the TDR500/3's input port and then to the cable under test. Ensure a secure connection to minimize signal reflections.

5. Betjening

5.1 Tænd/sluk

To turn on the TDR500/3, rotate the main selector switch from the 'OFF' position to either 'AUTO' or the TDR measurement symbol.

To turn off the device, rotate the main selector switch to the 'OFF' position.

5.2 AUTO Selection Mode

The 'AUTO' mode simplifies operation by automatically setting the optimal range, pulse width, and gain for the cable under test. This is recommended for initial scans and general fault location.

  1. Rotate the selector switch to 'AUTO'.
  2. The TDR500/3 will automatically scan the cable and display the trace.
  3. Use the directional pad to move the cursor along the trace to identify fault locations. The distance to the cursor position will be displayed on the screen.

5.3 Manual Settings (TDR Mode)

For advanced testing or specific cable types, you can manually adjust parameters in the TDR measurement mode.

  1. Rotate the selector switch to the TDR measurement symbol.
  2. Use the directional pad and control buttons to access and adjust settings such as:
    • Velocity Factor (VF): Adjust this value (0.2 to 0.99) to match the cable's dielectric constant for accurate distance measurements. The current VF is displayed on the screen (e.g., "UF=0.69").
    • Output Impedance (Z): Select from 25, 50, 75, or 100 Ohms to match the characteristic impedance of the cable. The current impedance is displayed (e.g., "Z=100Ω").
    • Rækkevidde: Manually set the maximum display range (e.g., "100 m").
  3. Observe the trace and use the cursor to pinpoint faults.

5.4 Trace HOLD Feature

Press the 'HOLD' button to freeze the current trace on the display. This is useful for comparing traces or for detailed analysis without the trace continuously updating. Press 'HOLD' again to resume live trace updates.

5.5 Display Adjustments

Use the control buttons below the LCD to adjust the display contrast and backlight intensity for optimal viewunder forskellige lysforhold.

6. Vedligeholdelse

6.1 Rengøring

Wipe the instrument with a soft, damp klud. Brug ikke slibende rengøringsmidler eller opløsningsmidler. Sørg for, at der ikke kommer fugt ind i enheden.

6.2 Opbevaring

Store the TDR500/3 in a clean, dry environment within the specified operating temperature range. Protect it from dust, moisture, and extreme temperatures.

6.3 Kalibrering

Regular calibration by authorized service centers is recommended to ensure the continued accuracy and performance of the TDR500/3. Refer to Megger's official documentation or website for recommended calibration intervals.

7. Fejlfinding

ProblemMulig årsagLøsning
Enheden tænder ikke.No AC power, faulty power adapter, or internal issue.Check AC power connection. Ensure power adapter is functioning. If problem persists, contact Megger support.
Unclear or noisy trace.Incorrect impedance setting, poor cable connection, or external interference.Verify impedance setting matches cable. Ensure test leads are securely connected. Check for strong electromagnetic interference.
Incorrect distance readings.Incorrect Velocity Factor (VF) setting.Adjust the VF setting to match the known velocity factor of the cable under test. Refer to cable specifications.
Skærmen er for svag eller for lys.Display contrast or backlight settings are incorrect.Adjust display contrast and backlight using the control buttons below the LCD.

For issues not listed here, or if solutions do not resolve the problem, please contact Megger customer support.

8. Specifikationer

ParameterVærdi
ModelnummerTDR500/3 (also 1002-227)
Opløsning0.1 m (0.3 fod)
Maksimal rækkevidde5 km (15,000 ft) (dependent on VF and cable type)
Output Impedances25, 50, 75, 100 Ω
Velocity Factor (VF) Range0.2 til 0.99
Display TypeBacklit Graphics Monochrome LCD (256 x 128 pixels)
StrømkildeAC (external adapter)
Varens vægt3.65 pund
Produktmål (L x B x H)9.06 x 1.89 x 4.53 tommer
OprindelseslandStorbritannien
BrugProfessionel

9. Garanti og support

Megger products are designed for reliability and performance. For information regarding warranty coverage, technical support, service, or replacement parts, please contact Megger customer service or visit the official Megger website. Please have your product model number (TDR500/3) and serial number ready when contacting support.

For de mest opdaterede kontaktoplysninger, besøg venligst: www.megger.com

Relaterede dokumenter - TDR500/3

Preview Megger TDR500 brugervejledning: Specifikationer og betjening af tidsdomænereflektometer
Omfattende brugervejledning til Megger TDR500 tidsdomænereflektometeret, der dækker mekaniske, miljømæssige og elektriske specifikationer, kabelhastighedsfaktorer, sikkerhedsadvarsler og driftsmæssige detaljer.
Preview Megger TDR1000/3 Échomètre de Poing : Caractéristiques et Spécifications Techniques
Découvrez le Megger TDR1000/3, un échomètre de poche portable et compact pour la localisation précise des défauts sur câbles métalliques. Idéal pour les techniciens, il offre une haute résolution, une large portée et des fonctionnalités intuitives comme le réglage AUTO et la fonction HOLD.
Preview Megger ADVANCED Range 5 kV, 10 kV, 15 kV isolationsmodstandstestere
Udforsk den robuste og pålidelige Megger ADVANCED-serie af 5 kV, 10 kV og 15 kV isolationsmodstandstestere. Opdag avancerede funktioner som RE>Act-tilstand for forbedret nøjagtighed, PI-prædiktor for hurtigere testning og højvolumen.tage-kapaciteter på op til 30 TΩ. Disse testere er designet til industrielle anvendelser og tilbyder overlegen sikkerhed (CAT IV-klassificeret) og intuitiv betjening til effektiv elektrisk vedligeholdelse og testning.
Preview Megger TORKEL 900-seriens batteriladeenhed brugermanual
Denne brugermanual indeholder omfattende instruktioner til betjening af Megger TORKEL 900-seriens batteriladeenheder. Den dækker produktfunktioner, sikkerhedsretningslinjer, testprocedurer, navigation i menusystemet, ekstern strømmåling og valgfrit udstyr som TXL Extra Loads og BVM Battery Vol.tage-skærme, essentielle til industrielle applikationer, transformerstationer og datacentre.
Preview Megger MIT400/2 KAT IV Isolationstestere: Funktioner, Specifikationer og Anvendelser
Omfattende datablad for Megger MIT400/2-serien af ​​KAT IV isolations- og kontinuitetstestere. Detaljer om funktioner, specifikationer, anvendelser, sikkerhed og modelsammenligninger til elektrisk og industriel testning.
Preview Megger TORKEL 900-seriens brugervejledning: Batteriladningsenheds drift og specifikationer
Omfattende brugervejledning til Megger TORKEL 900-serien af ​​batteriladeenheder. Dækker produktbeskrivelse, funktioner, sikkerhedsinstruktioner, betjening, testprocedurer, valgfrit udstyr som TXL Extra Loads og BVM, fejlfinding og tekniske specifikationer.