Indledning
The AEMC Model 3711 is a portable clamp-on ground resistance tester designed for measuring electrical ground rod and grid resistance in multi-grounded systems. This instrument offers a non-intrusive method for testing without the need for auxiliary rods or disconnecting the ground system. It also measures leakage, neutral, and phase currents, providing a comprehensive solution for electrical system analysis.
Sikkerhedsoplysninger
ADVARSEL: Always read and understand all safety instructions before operating this instrument. Failure to do so may result in serious injury or death.
- This instrument is rated CAT III, indicating its suitability for measurements in building installations.
- Adhere to all local and national safety codes and regulations.
- Do not use the instrument if it appears damaged or is operating abnormally.
- Sørg for, at batterirummet er forsvarligt lukket før brug.
- Avoid contact with live circuits during measurement.
- The instrument is double-insulated for enhanced safety.
Hvad er der i æsken
Kontroller, at alle genstande er til stede ved udpakning:
- AEMC Ground Resistance Tester Model 3711
- Calibration Check Loop, 25Ω
- Hård bæretaske
- 9V alkalisk batteri
- Brugervejledning (dette dokument)
Produkt overview

Image: The AEMC Model 3711 Clamp-On Ground Resistance Tester. This image displays the device with its red clamp jaws open, a black body, and a green digital display showing "9.8 Ω". Control buttons are visible below the display.
The AEMC Model 3711 features an ergonomic design for one-handed operation. Its robust polycarbonate construction ensures durability for outdoor use. Key components include:
- Clamp Kæber: 1.25" opening to accommodate ground rods and cables up to 1000kcmil.
- LCD-skærm: Digital readout for resistance and current measurements.
- Kontrolknapper: For power, data hold, and mode selection.
- Batterirum: Located at the rear for a 9V battery.
Opsætning og batteriinstallation
- Open the battery compartment cover on the rear of the instrument.
- Insert the supplied 9V Alkaline battery, observing correct polarity.
- Luk batterirummets dæksel forsvarligt.
- Press the "ON" button to power on the device. The display should illuminate.
Betjeningsvejledning
Ground Resistance Measurement
- Power on the AEMC 3711.
- Åbn clamp jaws by pressing the release lever.
- Placer clamp around the ground conductor or rod to be tested, ensuring the jaws are fully closed.
- The instrument will automatically measure and display the ground resistance in Ohms (Ω).
- For stable readings, allow approximately one second for the measurement to settle.
- To hold the current reading on the display, press the "HOLD" button. Press again to release.
Strømmåling
- Power on the AEMC 3711.
- Åbn clamp kæber.
- Placer clamp around the conductor carrying the current to be measured (leakage, neutral, or phase current). Ensure the jaws are fully closed.
- The instrument will automatically measure and display the current in Amperes (A) eller milliAmperes (mA).
- The current measurement function provides direct readings for leakage current flowing to ground or circulating in ground loops (down to 1mA) and neutral/phase currents (up to 30A RMS).
Vedligeholdelse og kalibrering
Rensning
Rengør instrumentet med en blød, damp klæde. Brug ikke slibende rengøringsmidler eller opløsningsmidler.
Udskiftning af batteri
When the low battery indicator appears on the display, replace the 9V battery as described in the "Setup and Battery Installation" section.
Kalibreringskontrol
Use the supplied 25Ω calibration check loop to verify the instrument's accuracy periodically. Clamp the tester around the loop; the reading should be approximately 25Ω. If the reading deviates significantly, contact AEMC customer support for service.
Opbevaring
Store the instrument in its hard carrying case in a dry, cool environment when not in use. Remove the battery if storing for extended periods.
Fejlfinding
- No Display/Instrument Not Powering On: Kontroller batteriinstallationen, og sørg for, at batteriet er tilstrækkeligt opladet. Udskift om nødvendigt.
- Ustabile aflæsninger: Sørg for at clamp jaws are fully closed around the conductor. Verify there is no excessive electrical noise in the environment.
- "OL" or Overload Indication: The measured value exceeds the instrument's range. Ensure the correct measurement function is selected or the circuit parameters are within the device's limits.
- Upræcise læsninger: Perform a calibration check using the 25Ω loop. If the issue persists, contact technical support.
Specifikationer
| Parameter | Værdi |
|---|---|
| Ground Resistance Range | Autoranging 0.01 to 1200Ω |
| Nuværende måleområde | Autoranging 1mA to 30.00A RMS |
| Resistance Measuring Frequency | 2403 Hz |
| Current Measuring Frequency | 47 til 800 Hz |
| Accuracy (Resistance) | ±2% reading ±0.02Ω (up to 25% of reading for 600-1200Ω) |
| Driftstemperatur | -10 til 55°C (14 til 131°F) |
| Strømkilde | 9V batteri (inkluderet) |
| Vægt | 1 kg (2.2 lbs) |
| Dimensioner (H x B x D) | 235 x 100 x 55mm (9.25 x 3.94 x 2.17 inches) |
| Kæbeåbning | 1.25 tommer |
| Sikkerhedsvurderinger | EN 61010, CAT III, UL approved, CE marked |
Garanti og support
For warranty information, technical support, or service inquiries, please refer to the official AEMC Instruments webwebstedet eller kontakt deres kundeserviceafdeling. Gem din købskvittering til garantikrav.





