Schneider Electric 9013GHG2J30

Schneider Electric 9013GHG2J30 Trykafbryder Brugsanvisning

Model: 9013GHG2J30

1. Introduktion

This manual provides essential instructions for the safe installation, operation, and maintenance of the Schneider Electric 9013GHG2J30 Pressure Switch. This device is designed for automatic control of electrical circuits in response to changes in fluid pressure. It features a Double Pole Single Throw Normally Closed (DPST-NC) contact configuration and is suitable for various industrial and scientific applications.

Schneider Electric 9013GHG2J30 Pressure Switch

Figur 1: Schneider Electric 9013GHG2J30 Pressure Switch. This image shows the compact gray housing of the pressure switch with its electrical conduit connection point and the pressure sensing port at the bottom.

2. Sikkerhedsoplysninger

ADVARSEL: Read and understand all instructions before installing, operating, or servicing this device. Failure to follow these instructions may result in death, serious injury, or equipment damage.

3. Opsætning og installation

3.1 Montering

Mount the pressure switch in a location free from excessive vibration, moisture, and extreme temperatures. Ensure adequate space for wiring and pressure line connections. The switch is designed for flange mounting.

3.2 Tryktilslutning

  1. Ensure the pressure system is completely depressurized.
  2. Connect the pressure line to the 1/4" NPSF flange port on the switch.
  3. Use appropriate thread sealant to ensure a leak-free connection. Do not overtighten.

3.3 Elektriske ledninger

The 9013GHG2J30 is a Double Pole Single Throw Normally Closed (DPST-NC) switch. This means that under normal (low pressure) conditions, the contacts are closed, and they open when the pressure rises above the set point.

  1. Disconnect all power to the circuit before wiring.
  2. Open the switch enclosure.
  3. Connect the electrical wires to the screw terminals as per your system's wiring diagram. Refer to local electrical codes.
  4. Sørg for, at alle forbindelser er sikre og korrekt isolerede.
  5. Close the switch enclosure securely to maintain its IP54 rating.

3.4 Trykjustering

The switch has an adjustable operating range between 40 psi and 170 psi. The exact adjustment mechanism (e.g., screw, knob) is typically located inside the enclosure. Consult the specific product diagram for precise adjustment instructions.

  1. Depressurize the system and disconnect power.
  2. Open the switch enclosure.
  3. Locate the adjustment screw/mechanism.
  4. Turn the adjustment mechanism to set the desired pressure actuation point within the 40-170 psi range. Turning clockwise typically increases the set point.
  5. Close the enclosure, repressurize the system, and restore power to test the setting. Repeat adjustment if necessary.

4. Betjeningsvejledning

Once properly installed and adjusted, the Schneider Electric 9013GHG2J30 Pressure Switch operates automatically. When the system pressure falls below the set point, the DPST-NC contacts will close, completing the circuit. When the system pressure rises above the set point, the contacts will open, interrupting the circuit.

5. Vedligeholdelse

The 9013GHG2J30 Pressure Switch is designed for reliable operation with minimal maintenance. However, periodic inspection is recommended to ensure optimal performance and longevity.

NOTE: Always disconnect power and depressurize the system before performing any maintenance.

6. Fejlfinding

This section provides guidance for common issues. For problems not listed here, contact Schneider Electric technical support.

ProblemMulig årsagLøsning
Kontakten aktiveres ikke ved indstillet tryk.Forkert trykindstilling.
Blocked pressure port.
Defekt ledningsføring.
Internal switch failure.
Verify and adjust the pressure setting.
Check for obstructions in the pressure line/port.
Undersøg ledningerne for løse forbindelser eller skader.
If all else fails, the switch may need replacement.
Pressure leaks at connection.Improperly sealed connection.
Damaged threads.
Depressurize, disconnect, reapply thread sealant, and reconnect.
Inspect threads for damage; replace components if necessary.
Electrical circuit remains open/closed unexpectedly.Forkert ledningsføring.
Internal contact welding/failure.
Pressure outside operating range.
Review wiring diagram and correct connections.
Test switch continuity; replace if contacts are faulty.
Ensure system pressure is within 40-170 psi.

7. Specifikationer

FeatureDetalje
Model9013GHG2J30
MærkeSchneider Electric
DriftstilstandAutomatisk
KontakttypeDouble Pole Single Throw Normally Closed (DPST-NC)
TrykområdeAdjustable 40 psi to 170 psi
Connector TypeFlange
Trykforbindelse1/4" NPSF
TerminaltypeScrew (DPST)
Kredsløbstype1-vejs
KontaktmaterialeKobber
International Protection RatingIP54
Antal stillinger1

8. Support og garanti

For technical assistance, product support, or warranty information, please contact Schneider Electric customer service or visit their official webwebsted. Gem din købskvittering for garantikrav.

Bemærk: Specifikke garantivilkår kan variere afhængigt af region og produkt.

Relaterede dokumenter - 9013GHG2J30

Preview Schneider Electric PrismaSeT LVS03427 installationsvejledning
Installationsvejledning til Schneider Electric PrismaSeT LVS03427 TransferPact Active Automatic 80-160 3P/4P elektrisk fordelingsmodul. Indeholder monteringsvejledning, tilslutningsdetaljer og sikkerhedsoplysninger.
Preview Schneider Electric PSI og MICROZONE II Diagnostik og Fejlkoder
Omfattende guide til forståelse og fejlfinding af diagnostiske indikatorer og fejlmeddelelser for Schneider Electric PSI- og MICROZONE II-enheder, herunder Universal Input-diagnosticering og kommunikationsfejl.
Preview TransferPacT Active Automatic 32-100 installations- og betjeningsmanual
Dette dokument indeholder installations-, betjenings- og sikkerhedsinstruktioner til Schneider Electric TransferPacT Active Automatic 32-100 automatisk omskifter.
Preview Schneider Electric Pressure Transmitter 691/692: Installation and Operation
This document provides essential safety warnings, operating instructions, and installation guidance for the Schneider Electric 691/692 pressure transmitter, covering multilingual information and technical specifications for water applications (0-16 bar).
Preview Schneider Electric & Pytes batterikonfigurationsvejledning til invertere og laderegulatorer
Detaljerede konfigurationsindstillinger for Pytes-batterier med Schneider Electric XW+ og XW Pro MPPT-invertere og laderegulatorer, der dækker oplader- og inverterparametre for optimal ydeevne af solenergisystemet.
Preview Schneider Electric TeSys Deca Frame 2 motorafbrydere: Produktreferencer og specifikationer
Udforsk Schneider Electrics TeSys Deca Frame 2-serie af motorafbrydere. Dette dokument indeholder omfattende produktreferencer, tekniske specifikationer og applikationsdetaljer for forskellige modeller, herunder GV2L, GV2LE, GV2ME, GV2P og GV2RT.