1. Introduktion
This manual provides essential information for the safe and effective installation, operation, and maintenance of the Omron G7L-2A-BUBJ-CB-DC24 General Purpose Relay. This relay is designed for high-capacity voltage applications, featuring a test button, Class B rated insulation, screw terminal connections, and upper bracket mounting. It is suitable for controlling larger power sources in various industrial settings.
2. Sikkerhedsoplysninger
WARNING: Electrical shock hazard. Always disconnect power before installing, servicing, or removing this device.
- Sørg for, at alle lokale og nationale elektriske forskrifter følges under installationen.
- Installation og service bør kun udføres af kvalificeret personale.
- Bekræft korrekt voltage and current ratings before connecting the relay to any circuit.
- Do not operate the relay in environments exceeding its specified operating temperature range or dielectric strength.
- Inspect the relay for any physical damage before installation. Do not install damaged units.
3. Produktet er slutview
The Omron G7L-2A-BUBJ-CB-DC24 is a robust general-purpose relay designed for reliable switching in demanding applications. It features Double Pole Single Throw Normally Open (DPST-NO) contacts, allowing for simple on/off switching of two independent circuits simultaneously.

This image displays the Omron G7L-2A-BUBJ-CB-DC24 General Purpose Relay, showing its robust housing, multiple screw terminals for electrical connections, and the integrated test button. The upper bracket mounting design is also visible.
Nøglefunktioner:
- Electric Relay with Test Button: Allows for manual verification of operation status.
- Screw Terminal Connection: Provides secure and reliable electrical connections.
- Upper Bracket Mounting: Designed for easy installation in equipment racks.
- DPST-NO Contacts: Double Pole Single Throw Normally Open configuration for straightforward switching.
- UL Class B Insulation: Ensures flame resistance for enhanced safety.
- Certificeringer: UL recognized for safety and CSA certified for quality assurance.
4. Specifikationer
| Specifikation | Værdi |
|---|---|
| Modelnummer | G7L-2A-BUBJ-CB-DC24 |
| Kontaktformular | DPST-NO (Double Pole Single Throw Normally Open) |
| Input Current Rating | 79 mA |
| Input bindtage | 24VDC |
| Load Rating | 220VAC, 25 Amp |
| Dielektrisk styrke | 4,000VAC |
| Driftstemperatur | -25 til +60 grader C |
| Kapslingsdimensioner (H x B x D) | 49 x 34.5 x 68.6mm (2.8 x 1.5 x 2.1 inches) |
| Isoleringsklasse | Klasse B |
| Connector Type | Skrueterminal |
| Monteringstype | Øvre beslag |
| Kontaktmateriale | Silver or Copper |
| Vægt | 0.71 ounce |
| Standarder opfyldt | UL (Underwriter's Laboratories), CSA (Canadian Standards Association) |
5. Installation
5.1 Kontrol før installation
- Ensure the power supply to the circuit is completely disconnected.
- Verify that the relay's specifications (voltage, current) match the requirements of your application.
- Confirm that the mounting location is stable and within the specified operating temperature range.
5.2 Montering
The G7L-2A-BUBJ-CB-DC24 relay is designed for upper bracket mounting. Secure the relay firmly to the designated upper bracket within your equipment rack or control panel using appropriate fasteners. Ensure there is adequate clearance for wiring and ventilation.
5.3 Ledningsføring
This relay utilizes screw terminal connections. Follow the wiring diagram provided with your system or equipment. The relay has DPST-NO contacts. Connect the control circuit to the 24VDC input terminals and the load circuits to the appropriate screw terminals for the 220VAC, 25 amp load. Ensure all connections are tight and secure to prevent loose contacts and potential hazards.
- Identify the control input terminals (24VDC).
- Identify the load output terminals (220VAC, 25A).
- Strip wire insulation to the appropriate length for screw terminals.
- Insert wires into the correct terminals and tighten screws securely. Do not overtighten to avoid damaging the terminals.
- Dobbelttjek alle ledninger for korrekthed og sikkerhed, før du genopretter strømmen.
6. Betjening
The Omron G7L-2A-BUBJ-CB-DC24 relay functions by using a small 24VDC control signal to switch a larger 220VAC, 25 amp load. When the 24VDC control voltage is applied, the internal mechanism activates, closing the Normally Open (NO) contacts and allowing current to flow through the connected load circuit.
6.1 Test Button Functionality
The integrated test button allows for manual verification of the relay's switching action without applying the control voltage. Pressing the test button will manually close the contacts, enabling you to check the continuity of the load circuit or confirm the mechanical operation of the relay. Release the button to return the contacts to their normally open state.
7. Vedligeholdelse
Regular inspection and basic maintenance can help ensure the longevity and reliable operation of your Omron relay.
- Visuel inspektion: Periodically inspect the relay for any signs of physical damage, discoloration, or loose connections.
- Terminaltæthed: Ensure all screw terminals remain tight. Loose connections can lead to overheating and intermittent operation.
- Miljøforhold: Verify that the operating environment remains within the specified temperature and humidity limits.
- Rensning: Rengør om nødvendigt forsigtigt relæets yderside med en tør, blød klud. Brug ikke opløsningsmidler eller slibende rengøringsmidler.
8. Fejlfinding
If the relay is not functioning as expected, consider the following troubleshooting steps:
- No Switching Action:
- Check if the 24VDC control voltage is correctly applied to the input terminals.
- Verify the control circuit wiring for continuity and correct polarity.
- Use the test button to confirm the mechanical operation of the relay. If the test button works but electrical activation does not, the issue may be with the control signal.
- Load Not Receiving Power:
- Ensure the 220VAC power source for the load is active and correctly wired to the relay's load terminals.
- Check the load circuit wiring for breaks or loose connections.
- Confirm that the relay contacts are closing when activated (either by control signal or test button).
- Overheating/Unusual Noise:
- Afbryd straks strømmen.
- Check for loose wiring connections at the terminals.
- Ensure the load current does not exceed the relay's 25 amp bedømmelse.
- Bekræft input voltage is stable and within the 24VDC specification.
If problems persist after performing these checks, consult a qualified electrician or contact Omron technical support.
9. Garanti og support
For warranty information, technical support, or service inquiries regarding your Omron G7L-2A-BUBJ-CB-DC24 General Purpose Relay, please refer to the official Omron webwebstedet eller kontakt din autoriserede Omron-distributør. Gem din købskvittering til garantikrav.