Sargent 1560

Sargent 1560 Electromagnetic Surface Mount Door Holder

Instruktionsmanual

Model: 1560 | Brand: Sargent

1. Introduktion

The Sargent 1560 Electromagnetic Surface Mount Door Holder is designed to securely hold fire and smoke barrier doors in an open position. Upon activation of a remote smoke detector, fire alarm system, or other contact device, the electromagnet releases the door, allowing it to close and contain the spread of fire and smoke. This manual provides essential information for the safe and correct installation, operation, and maintenance of your door holder.

2. Sikkerhedsoplysninger

ADVARSEL: Risiko for elektrisk stød.

  • Always disconnect power to the circuit before attempting any installation, wiring, or servicing of this device.
  • Installation must be performed by qualified personnel in accordance with all applicable local and national electrical codes and regulations.
  • Sørg for den korrekte voltage supply (120VAC, 24VAC/DC, or 12VDC) is used as specified for the unit. Incorrect voltage can cause damage to the unit and pose a safety hazard.
  • Brug ikke enheden, hvis den ser ud til at være beskadiget.

3. Opsætning og installation

Proper installation is crucial for the reliable operation of the Sargent 1560 door holder. Follow these steps carefully.

Sargent 1560 Electromagnetic Surface Mount Door Holder components

This image displays the main electromagnet unit (left) and the separate armature plate (right), which is designed to be mounted on the door.

  1. Bestem monteringssted: Identify the desired open position for the door. The electromagnet unit should be mounted on the wall or floor, and the armature plate on the door, ensuring they align perfectly when the door is in the open position.
  2. Mount the Electromagnet Unit: Securely attach the electromagnet unit to the wall or floor using appropriate fasteners (not included, typically). Ensure the mounting surface is stable and capable of supporting the unit's weight and holding force.
  3. Mount the Armature Plate: Attach the armature plate to the door. The plate must be positioned so that its face makes full and flush contact with the electromagnet's face when the door is in the desired hold-open position. Adjustments may be necessary to achieve optimal alignment.
  4. Ledningsforbindelser:
    • Sørg for, at strømmen er afbrudt ved afbryderen, før du fortsætter.
    • Connect the power supply wires to the terminals on the electromagnet unit. Refer to the specific wiring diagram provided with your unit for detailed connections.
    • Kontroller, at voltage supplied matches the voltage rating of your Sargent 1560 unit (120VAC, 24VAC/DC, or 12VDC).
    • Alle ledninger skal overholde lokale elektriske regler.
  5. Test drift: Restore power to the circuit. Manually open the door to the hold-open position. The electromagnet should engage and hold the door. Activate the fire alarm system or release mechanism to ensure the door releases and closes properly.

4. Betjeningsvejledning

The Sargent 1560 door holder operates automatically once installed and wired correctly.

  • Holding the Door: When the door is opened to the position where the armature plate makes contact with the energized electromagnet, the magnetic force will hold the door securely in place.
  • Releasing the Door: The door holder is designed to release the door when the power supply to the electromagnet is interrupted. This interruption is typically triggered by:
    • Activation of a fire alarm system.
    • Activation of a smoke detector.
    • Manual activation of a release switch (if installed).
  • Upon release, the door will close under the action of its own closing mechanism (e.g., a door closer), preventing the spread of fire and smoke.

5. Vedligeholdelse

Regular maintenance ensures the continued reliability and performance of your door holder.

  • Periodisk eftersyn: Visually inspect the electromagnet unit and armature plate at least annually for any signs of wear, damage, corrosion, or loose components.
  • Rensning: Keep the contact surfaces of both the electromagnet and the armature plate clean and free from dust, dirt, paint, or other debris. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents. A clean contact surface ensures maximum magnetic holding force.
  • Ledningskontrol: Periodically check all electrical connections to ensure they are secure and that the wiring insulation is intact and undamaged.
  • Funktionstest: Test the door holder's release function regularly (e.g., monthly or as required by local fire codes) by activating the associated fire alarm or smoke detection system to ensure the door releases and closes properly.

6. Fejlfinding

If your Sargent 1560 door holder is not functioning as expected, refer to the following troubleshooting guide:

ProblemMulig årsagLøsning
Door not holding open
  • No power to electromagnet
  • Dirty or obstructed contact surfaces
  • Misalignment between electromagnet and armature plate
  • Forkert voltage forsyning
  • Check circuit breaker and wiring for power.
  • Clean electromagnet and armature plate surfaces.
  • Adjust mounting positions for proper alignment.
  • Bekræft bindtage matcher enhedsspecifikationerne.
Door not releasing
  • Continuous power to electromagnet
  • Faulty release mechanism (e.g., smoke detector, fire alarm panel)
  • Wiring fault (e.g., short circuit)
  • Check wiring to ensure power is interrupted upon alarm activation.
  • Test the release mechanism independently.
  • Inspect wiring for damage or incorrect connections.

If the problem persists after attempting these solutions, contact a qualified technician or Sargent customer support.

7. Specifikationer

  • Model: 1560 OG
  • Mærke: Sargent
  • Fabrikant: ASSA ABLOY
  • Monteringstype: Overflademontering
  • Voltage Valgmuligheder: 120VAC, 24VAC/DC, 12VDC (Specifik voltage depends on the model variant purchased)
  • Varens vægt: Cirka 8 pund
  • Anvendelse: Fire and smoke barrier doors

8. Garanti og support

For detailed warranty information, technical assistance, or to purchase replacement parts, please refer to the official Sargent website or contact Sargent customer service directly. Keep your purchase receipt for warranty claims.

Relaterede dokumenter - 1560

Preview SARGENT 2900 FIREGUARD Elektromekanisk lukker-holder Installationsvejledning
Detaljeret installationsvejledning til SARGENT 2900 FIREGUARD elektromekanisk lukker-holder, model 2980 multipunktshold åben med svingfri arm. Indeholder trin til montering, arm- og skinneinstallation, justeringer og ledningsføring.
Preview Sargent L980S Låsbar Ikke-brandsikker Mullion Monteringsvejledning
Omfattende installationsvejledning til Sargent L980S aflåselig, ikke-brandsikker post med detaljerede oplysninger om trinvis montering og cylinderinstallation. Indeholder produktspecifikationer og sikkerhedsoplysninger fra ASSA ABLOY.
Preview Installationsvejledning til Sargent 1430/1431 dørlukker
Omfattende installationsvejledning til Sargent dørlukkere i serien 1430 og 1431, inklusive standard-, parallelarm- og topkarmapplikationer. Detaljer om fjederjustering, regulering af bagbremse og brug af tilbehør.
Preview Sargent FM8700/12-FM8700 Overflademonteret vertikal stangudgangsenhed Installationsvejledning
Omfattende installationsvejledning til Sargent FM8700 og 12-FM8700 overflademonterede vertikale stangudgangsanordninger, der beskriver værktøj, fastgørelseselementer, dørforberedelse, trinvis montering, justeringer og skinneskæring. Indeholder tekstlige beskrivelser af diagrammer og vigtige sikkerhedsadvarsler.
Preview SARGENT 80-seriens udgangsenheder katalog
Comprehensive catalog detailing the SARGENT 80 Series of exit devices, including rim, mortise, and vertical rod options. Features, specifications, fire ratings, windstorm certifications, and trim designs are covered for various applications.
Preview Sargent 80-seriens nødudgangsenheder: Omfattende guide
Explore the Sargent 80 Series of exit devices, including rim, mortise, and vertical rod options. This guide details features, specifications, finishes, and certifications for various models like the 8800, 8900, and 8500 series, suitable for commercial and institutional applications.