Leviton 2761

Leviton 2761 30 Amp NEMA L19-30P Locking Plug Instruction Manual

Model: 2761

Produkt overview

The Leviton 2761 is an industrial-grade, non-grounding locking plug designed for demanding electrical applications. This 30 Amp, 277/480 Volt 3PY, NEMA L19-30P plug features a 4-pole, 4-wire configuration, ensuring secure and reliable power connections. Constructed with a Super Tough Nylon body and solid brass blades/contacts, it offers durability and performance.

Leviton 2761 30 Amp NEMA L19-30P Locking Plug

Image: Leviton 2761 30 Amp NEMA L19-30P Locking Plug, showcasing its black and white body with brass pins.

Sikkerhedsoplysninger

ADVARSEL: Stødfare. To avoid risk of serious injury or death, always turn power off at the circuit breaker before wiring any electrical device. Ensure all connections are secure and comply with local electrical codes. If you are unsure about any step, consult a qualified electrician.

Specifikationer

Modelnummer2761
Ampslette30 Amps
Voltage Bedømmelse277/480 Volt 3PY
NEMA-konfigurationL19-30P
Stænger/Tråde4 polet, 4 leder
Jordforbindelse TypeIkke-jordforbindelse
MaterialeSuper Tough Nylon (Body), Solid Brass (Blade/Contact)
FarveSort-Hvid
GodkendelserUL 498, CSA C22.2, NOM 057

Installationsvejledning

Follow these steps to properly wire your Leviton 2761 locking plug. Refer to the accompanying video for visual guidance.

Video: This video demonstrates the wiring process for Leviton Black and White Plugs and Connectors, including the steps for disassembling, preparing wires, making connections, and reassembling the device.

  1. Sørg for, at strømmen er slukket: Before beginning, verify that the power to the cable is completely off at the circuit breaker to prevent electrical shock.
  2. Identify Plug Configuration: The faceplate of the plug is stamped with the NEMA configuration, amperage og voltage. Confirm these match your requirements.
  3. Disassemble the Plug:
    • Using a Phillips head screwdriver, loosen the quick screws on the faceplate.
    • Carefully remove the faceplate from the body housing.
    • Loosen the two strain relief screws on the strain relief component.
  4. Forbered kablet:
    • Feed the cable through the loosened strain relief and then through the body housing.
    • Strip the cord jacket according to the diagram on the instruction sheet (typically about 1.5 inches). Remove the stripped cord jacket to expose the individual wires.
  5. Prepare Individual Wires:
    • Cut the green (ground) wire to approximately 1 inch in length.
    • Strip approximately 5/8 inch of insulation from all remaining wires using wire strippers.
  6. Connect the Ground Wire:
    • Insert the green (ground) wire into the wire well of the green (ground) terminal screw, located in the center of the device.
    • Tighten the terminal screw securely with a Phillips head screwdriver.
  7. Connect the Neutral Wire:
    • Insert the white (neutral) wire into the wire well of the silver terminal screw.
    • Tighten the terminal screw securely.
  8. Connect Remaining Wires:
    • Insert the remaining three wires into the wire wells of the brass terminals.
    • Tighten each brass terminal screw securely.
  9. Reassemble the Plug:
    • Slide the faceplate back into the body housing, ensuring the channel guide on the body housing aligns perfectly with the faceplate.
    • Tighten the quick screws on the faceplate with a Phillips head screwdriver.
  10. Sikker trækaflastning:
    • Tighten both screws on the strain relief to secure the cable.
    • Note: If your wire is larger than the groove on the strain relief, a section of the strain relief can be removed to accommodate larger wire sizes.

Operation

Once properly wired and assembled, the Leviton 2761 locking plug is ready for use. Insert the plug into a compatible NEMA L19-30R receptacle and twist to lock it into place, ensuring a secure electrical connection. To disconnect, twist in the opposite direction and pull.

Opretholdelse

Regularly inspect the plug for any signs of wear, damage, or loose connections. Ensure the cable jacket and strain relief are intact to prevent wire exposure. Clean the plug exterior with a dry cloth as needed. Do not use abrasive cleaners or solvents. If any damage is observed, discontinue use and replace the plug.

Fejlfinding

Garanti og support

This Leviton product is covered by a manufacturer's warranty. For specific warranty details, claims, or technical support, please contact Leviton customer service directly or visit their official website. Keep your purchase receipt for warranty purposes.

Relaterede dokumenter - 2761

Preview Leviton EV40P EV Series 40 AMP Plug-In Charger Installation Manual
Installation manual for the Leviton EV40P EV Series 40 AMP Plug-In Electric Vehicle Charger. Includes safety warnings, specifications, installation steps, operating procedures, RFID card usage, error messages, maintenance, and warranty information.
Preview Min Leviton-appguide: Styr dine smarte hjemmeenheder
Udforsk My Leviton App-guiden for nemt at tilmelde, integrere og tilpasse dine Decora Smart Wi-Fi-enheder og Leviton Load Center med Smart Breakers for problemfri smart home-kontrol.
Preview Leviton Decora Smart Wi-Fi Mini Plug-In Dimmer (2nd Gen) - Getting Started Guide
Comprehensive guide for the Leviton Decora Smart Wi-Fi Mini Plug-In Dimmer (2nd Gen). Learn installation, setup with Alexa, Google Assistant, and Apple HomeKit, troubleshooting, and safety information.
Preview Leviton Decora Smart Wi-Fi Outdoor Plug-In Switch: Getting Started Guide
Learn how to install and set up your Leviton Decora Smart Wi-Fi Outdoor Plug-In Switch (D2150) for smart control of outdoor lighting and appliances. Includes setup, pairing, and troubleshooting.
Preview Min Leviton-appguide: Smart Home Control til Decora Smart Wi-Fi og Load Centers
En omfattende guide til brug af My Leviton-appen til administration af Leviton Decora Smart Wi-Fi-enheder og Leviton Load Centers med Smart Breakers. Dækker opsætning, tidsplaner, aktiviteter, enhedsindstillinger, tilpasning af dashboard, energiovervågning og kundesupport.
Preview Leviton Scene Capable Plug-In Lamp Dimming Module RZP03-1LW Installation Instructions
Installation instructions for the Leviton Scene Capable Plug-In Lamp Dimming Module (Cat. No. RZP03-1LW). This guide covers setup, Z-Wave network inclusion, operation, and troubleshooting for smart lighting control.