Sure-Lites LPX7

Sure-Lites LPX7 Universal Emergency Exit Light User Manual

Model: LPX7 | Brand: Sure-Lites

Indledning

The Sure-Lites LPX7 Series LED Exit Light is a universal emergency exit sign designed for general purpose applications. This unit features a durable polycarbonate housing and is equipped with LED lamps, offering energy efficiency and reliability. It supports dual voltage input (120/277 VAC) and includes a nickel cadmium battery for emergency operation, providing a minimum run time of 90 minutes during power loss.

The LPX7 series is engineered for ease of installation and maintenance, making it a suitable replacement for previous models like the CCX Series. It ships with components to configure either red or green exit legends, providing flexibility for various installation requirements.

Sure-Lites LPX7 Universal Emergency Exit Light

Figure 1: Sure-Lites LPX7 Universal Emergency Exit Light with red legend illuminated.

Sikkerhedsoplysninger

Læs og forstå alle instruktioner, før du installerer eller bruger dette produkt. Manglende overholdelse af disse instruktioner kan resultere i elektrisk stød, brand eller andre farer, der kan forårsage materielle skader eller personskade.

Pakkens indhold

Kontroller, at alle komponenter er til stede og ubeskadigede, før installationen påbegyndes:

Opsætning og installation

The LPX7 exit sign is designed for universal mounting, allowing for ceiling, wall, or end mount installations. Follow these steps for proper setup:

1. Valg af sted

Choose a mounting location that is visible and meets local building codes for emergency exit signage. Ensure the mounting surface is structurally sound to support the unit's weight.

2. Strømafbrydelse

Before starting any electrical work, turn off power to the circuit at the main breaker panel to prevent electric shock.

3. Monteringsforberedelse

Determine the desired mounting method (ceiling, wall, or end mount). The unit is designed for semi-flush mount installation. Refer to the dimensions diagram for precise measurements.

Dimensions of Sure-Lites LPX7 Emergency Exit Light

Figure 2: Dimensional drawing of the LPX7 exit light, showing overall width of 13 inches (330mm), overall height of 7 1/2 inches (190mm), and overall depth of 2 1/8 inches (54mm).

4. Elektrisk tilslutning

Connect the unit to a 120 VAC or 277 VAC, 60 Hz power source. The LPX7 features dual voltage input. Ensure proper wiring according to the provided wiring diagram (typically found inside the unit or on a separate sheet). All connections must be secure and insulated.

5. Batteritilslutning

Connect the internal Nickel Cadmium (NiCAD) battery. The battery is typically pre-installed but may require connecting a small plug to the circuit board. Ensure the connection is firm.

6. Legend Configuration

Insert the desired red or green legend panels into the unit. The LPX7 ships with both options, allowing for field configuration.

7. Slutsamling

Secure the unit to the mounting surface using the provided hardware. Ensure the housing is properly closed and secured.

8. Power Restoration & Testing

Restore power to the circuit. The exit sign should illuminate. Press the "TEST" button (usually a small push-button on the side or bottom of the unit) to verify emergency operation. The unit should switch to battery power and remain illuminated for at least 30 seconds. Release the button, and the unit should return to AC power.

Operation

The Sure-Lites LPX7 Emergency Exit Light operates automatically. When connected to a continuous AC power source, the LED lamps will remain illuminated, indicating the exit path. The internal Nickel Cadmium battery continuously charges while AC power is present.

Nødtilstand

I tilfælde af en magt outage or interruption to the AC supply, the unit will automatically switch to emergency mode, drawing power from its internal battery. The LED lamps will remain illuminated for a minimum of 90 minutes, providing essential egress lighting.

Test knap

A test button is provided on the unit for routine maintenance checks. Pressing and holding this button simulates a power failure, allowing you to verify that the battery and lamps are functioning correctly in emergency mode. Release the button to return to normal AC operation.

Emergency exit light installed in a waiting area

Figur 3: Eksample installation of an emergency exit light in a commercial waiting area, demonstrating its function in a public space.

Emergency exit light installed in an auditorium

Figur 4: Eksample installation of an emergency exit light in an auditorium, highlighting its visibility in a large gathering space.

Opretholdelse

Regular maintenance ensures the continued reliable operation of your emergency exit light. Always disconnect power before performing any maintenance.

Månedlig test

Perform a monthly 30-second test by pressing the test button. The unit should operate on battery power for the duration of the test. If the lamps do not illuminate or dim significantly, the battery may need replacement or further charging.

Annual Testing

Conduct an annual 90-minute discharge test. Disconnect AC power to the unit and allow it to operate on battery power for 90 minutes. The lamps should remain illuminated for the entire duration. If the unit fails to operate for 90 minutes, the battery requires replacement.

Rensning

Rengør enhedens yderside regelmæssigt med en blød, tør klud.amp cloth. Do not use abrasive cleaners or solvents, as these can damage the polycarbonate housing.

Udskiftning af batteri

The Nickel Cadmium battery has a typical lifespan of 5-7 years. If the unit fails to meet the required emergency run time during testing, replace the battery with an approved Sure-Lites replacement battery. Ensure proper polarity when connecting the new battery.

Fejlfinding

If your Sure-Lites LPX7 Emergency Exit Light is not functioning as expected, refer to the following common issues and solutions:

ProblemMulig årsagLøsning
Unit does not illuminate when AC power is on.No AC power to the unit; Loose wiring connection; Faulty LED lamps.Check circuit breaker and power supply. Verify all wiring connections are secure. Contact qualified service personnel if lamps are faulty.
Unit does not illuminate in emergency mode (during test or power outagog).Battery not connected; Battery not charged; Battery has reached end of life; Faulty circuit board.Ensure battery is properly connected. Allow 24 hours for initial battery charge. Replace battery if it fails annual test. Contact qualified service personnel.
Lamps are dim in emergency mode.Batteriet er ikke fuldt opladet; batteriet er ved at være brugt op.Allow unit to charge for 24 hours. If problem persists, replace battery.

If the problem persists after attempting these solutions, contact Sure-Lites customer support or a qualified electrician.

Specifikationer

FeatureDetalje
ModelnummerLPX7
Input bindtage120/277 VAC, 60 Hz
LyskildeLED (2 Lamps)
Farvetemperatur5000K
Legend ColorConfigurable Red or Green
Legend Height6 tommer
MonteringstypeUniversal (Ceiling, Wall, End Mount)
Materiale til husPolycarbonat
Husets farveHvid
BatteritypeNickel Cadmium (NiCAD)
Nødkørselstid90 minutter minimum
Samlet højde7.5 tommer (190 mm)
Samlet bredde13 tommer (330 mm)
Samlet dybde2.125 tommer (54 mm)
Varens vægt2.88 pund

Garanti og support

Garantioplysninger

The Sure-Lites LPX7 Emergency Exit Light comes with a 5 års garanti from the date of purchase. This warranty covers defects in materials and workmanship under normal use and service. The warranty does not cover damage resulting from improper installation, misuse, abuse, or acts of nature.

Kundesupport

For technical assistance, warranty claims, or replacement parts, please contact Sure-Lites customer support. Refer to the Sure-Lites official webwebstedet eller produktemballagen for de mest aktuelle kontaktoplysninger.

Note: Always provide your product model number (LPX7) and date of purchase when contacting support to expedite assistance.

Relaterede dokumenter - LPX7

Preview Sure-Lites EBPLEDL6SF Emergency LED Driver - Product Specifications and Data
Detailed specifications, features, and installation data for the Sure-Lites EBPLEDL6SF Emergency LED Driver by Cooper Lighting Solutions. Includes product overview, technical data, certifications, and dimensional drawings.
Preview Sure-Lites EBP1400NCX/NCF Emergency Ballast Installation Manual
Comprehensive installation, operation, and maintenance guide for Sure-Lites EBP1400NCX and EBP1400NCF emergency ballasts, detailing safety precautions, wiring diagrams, and lamp kompatibilitet.
Preview Sure-Lites FirstLink Connected Emergency Lighting System | Cooper Lighting Solutions
Explore the Sure-Lites FirstLink connected emergency lighting system from Cooper Lighting Solutions. This brochure details system features, hardware, app control, and service plans designed for building safety and code compliance.
Preview Sure-Lites ELX Series LED Exit Sign - Technical Specifications
Detailed technical specifications for the Sure-Lites ELX Series self-powered LED exit signs, including features, construction, code compliance, energy data, and mounting options.
Preview Sure-Lites APEL-seriens nødbelysningsarmatur
Udforsk Sure-Lites APEL-serien af ​​nødbelysning, der er UL 924-godkendt, har 90 minutters driftstid, justerbare LED-hoveder og et holdbart nikkel-cadmium-batteri. Ideel til pålidelig nødudgang med fjernbetjeningskapacitet.
Preview Sure-Lites All-Pro APX RG Series LED Exit Sign - Technical Specifications
Detailed specifications for the Sure-Lites All-Pro APX RG Series LED Exit Sign, featuring thermoplastic housing, selectable red or green faces, AC-only or battery backup options, and compliance with UL924 and California Title 20.