APC SURTD3000RMXLT3U

APC Smart-UPS RT 3000VA 208V 3U rackmonteret UPS-system brugermanual

Model: SURTD3000RMXLT3U

Indledning

This manual provides essential instructions for the safe installation, operation, and maintenance of your APC Smart-UPS RT 3000VA 208V 3U Rackmount UPS System. This Uninterruptible Power Supply (UPS) is designed to provide reliable power protection for your critical electronic equipment, ensuring continuous operation during power outages og udsving.

Vigtige sikkerhedsinstruktioner

Please read these instructions carefully before installing, operating, servicing, or maintaining the equipment. Failure to follow these instructions can result in serious injury or equipment damage.

Opsætning og installation

1. Udpakning og inspektion

Carefully unpack the UPS and inspect it for any shipping damage. Report any damage to the carrier and your dealer. The package should contain the UPS unit, rackmount hardware, and documentation.

2. Physical Installation (Rackmount)

The APC Smart-UPS RT 3000VA is designed for 3U rackmount installation. Use the provided rackmount hardware to secure the unit in a standard 19-inch equipment rack. Ensure adequate space for airflow around the unit.

APC Smart-UPS RT 3000VA 3U Rackmount UPS System with rackmount ears attached

Figur 1: Front view of the APC Smart-UPS RT 3000VA 3U Rackmount UPS System with rackmount ears attached, ready for installation. The front panel features status indicators and control buttons.

3. Batteritilslutning

The UPS ships with internal batteries disconnected for safety. Locate the battery connector on the rear or front panel (refer to the specific model diagram if available) and firmly connect the battery cables. The UPS will not power on or provide backup power until the batteries are connected.

4. Elektriske forbindelser

Side view of APC Smart-UPS RT 3000VA 3U Rackmount UPS System

Figur 2: Side view of the APC Smart-UPS RT 3000VA 3U Rackmount UPS System, showing the depth of the unit and ventilation grilles. This perspective highlights the robust construction for rack integration.

5. Første opstart

After all connections are secure, press the power button on the front panel to turn on the UPS. The UPS will perform a self-test and the status indicators will illuminate. Allow the batteries to charge for at least 24 hours to ensure full runtime capacity.

Operation

Frontpanel display og kontroller

The front panel features an LED status display with load and battery bar-graphs, along with indicators for On Line, On Battery, Replace Battery, Overload, and Bypass. Control buttons allow for power on/off, self-test, and menu navigation.

Normal drift

Under normal conditions, the UPS operates in "On Line" mode, providing conditioned power to connected equipment and charging the batteries. The "On Line" indicator will be illuminated.

Om batteridrift

Under en magt outage eller betydelig volumentage fluctuation, the UPS automatically transfers to battery power. The "On Battery" indicator will illuminate, and an audible alarm may sound. The UPS will provide power for approximately 14.1 minutes at full load (2100 Watts) with standard battery configuration.

Bypass drift

The UPS features an internal bypass (automatic and manual). In bypass mode, utility power is supplied directly to the connected equipment, bypassing the UPS's power conditioning circuitry. This mode is typically used for maintenance or in case of an internal UPS fault. The "Bypass" indicator will be illuminated.

Emergency Power Off (EPO)

The UPS includes an Emergency Power Off (EPO) port. Connecting an EPO switch to this port allows for immediate shutdown of the UPS and connected equipment in an emergency situation. Refer to the installation guide for EPO connection details.

Opretholdelse

Udskiftning af batteri

The UPS uses maintenance-free sealed Lead-Acid batteries. The "Replace Battery" indicator will illuminate when the batteries need replacement. Batteries are hot-swappable, meaning they can be replaced without powering down the connected equipment. Refer to the specific battery replacement instructions provided with your replacement battery modules. Typical recharge time for new batteries is 2.5 hours.

Rensning

Keep the UPS free of dust and debris. Use a dry cloth to clean the exterior. Do not use liquid cleaners or solvents.

Firmware opdateringer

Periodically check the APC website for available firmware updates for your UPS model. Firmware updates can provide improved performance, features, and bug fixes. Follow the instructions provided with the firmware update package carefully.

Fejlfinding

Dette afsnit indeholder løsninger på almindelige problemer. Kontakt APC's tekniske support ved mere komplekse problemer.

ProblemMulig årsagLøsning
UPS'en tænder ikke.Batteries disconnected or not charged. No input power.Ensure batteries are properly connected. Verify input power cable is securely plugged into a live outlet. Allow batteries to charge.
"Replace Battery" indicator is lit.Batteries are at the end of their service life.Order and install new battery modules.
UPS'en bipper kontinuerligt.UPS is on battery power or overloaded.Check utility power. Reduce load on the UPS if overloaded.
"Overload" indicator is lit.Connected equipment exceeds UPS capacity.Disconnect non-essential equipment to reduce the load.

Specifikationer

FeatureDetalje
ModelSURTD3000RMXLT3U
Udgangseffektkapacitet2100 Watt / 3000 VA
Nominel Output Voltage208 V (Configurable for 208 or 240 V)
Udgangsforbindelser2x NEMA L6-20R, 2x NEMA L6-30R
Nominel input Voltage208 V
IndgangsforbindelserNEMA L6-30P
BatteritypeVedligeholdelsesfri forseglet bly-syre
Typisk genopladningstid2.5 timer
Typical Backup Time (Full Load)14.1 minutes (2100 Watts)
Interface -porteSmart-Slot (1 available)
Emergency Power Off (EPO)Ja
Produktdimensioner39 x 24 x 13.5 tommer
Varens vægt120 pund

Garanti og support

Garantioplysninger

APC provides a two-year warranty for this product. Please retain your proof of purchase for warranty claims. The warranty covers defects in materials and workmanship under normal use.

Teknisk support

For technical assistance, troubleshooting, or warranty service, please contact APC customer support. Visit the official APC webwebsted for kontaktoplysninger, ofte stillede spørgsmål og yderligere ressourcer.

APC Webwebsted: www.apc.com

Relaterede dokumenter - SURTD3000RMXLT3U

Preview APC Smart-UPS SRT 3000VA 208V Datablad og tekniske specifikationer
Omfattende teknisk datablad for APC Smart-UPS SRT 3000VA 208V, med detaljerede oplysninger om elektriske specifikationer, fysiske egenskaber, driftstid, miljømæssige driftsforhold og produktcertificeringer.
Preview APC Smart-UPS SRT 10000VA 208V Tekniske specifikationer
Detaljerede tekniske specifikationer for APC Smart-UPS SRT 10000VA 208V, inklusive detaljer om output, input, batteri, kommunikation, fysiske, miljømæssige og overholdelsesstandarder. Model SRT10KXLT.
Preview APC Smart-UPS installationsvejledning: SMT750RMI2UC til SMT3000RMI2UC
Denne vejledning indeholder installationsvejledning til APC Smart-UPS-modellerne SMT750RMI2UC, SMT1000RMI2UC, SMT1500RMI2UC, SMT2200RMI2UC og SMT3000RMI2UC. Den dækker rackmontering, tilslutninger og SmartConnect-opsætning.
Preview APC Smart-UPS SMT750-3000RM2UC Installationsvejledning | Schneider Electric
Omfattende installationsvejledning til APC Smart-UPS SMT750, SMT1000, SMT1500, SMT2200 og SMT3000RM2UC rackmonterede UPS-modeller. Lær, hvordan du udpakker, installerer og tilslutter din UPS.
Preview Manuale for Funzionamento APC Smart-UPS C: Guide Completa
Funktionsmanualtagtilgængelig for APC Smart-UPS C (1000/1500/2000/3000 VA, 120/230 Vac, mantaggio a Rack 2U). Inkluder istruzioni di sicurezza, installation, funzionamento, specifiche tecniche, risoluzione problemi e garanzia.
Preview APC Smart-UPS brugermanual: 1000VA/1500VA, 750XL/1000XL tårn-UPS
Omfattende brugermanual til APC Smart-UPS Tower-modeller, der dækker installation, betjening, konfiguration, fejlfinding og lovgivningsmæssige oplysninger om afbrydelsesfri strømforsyning.