ETEK EK4Q

ETEK EK4Q Automatic Transfer Switch User Manual

Model: EK4Q | Brand: ETEK

1. Produktet er slutview

The ETEK EK4Q automatic transfer switch (ATS) is a PC class infrequent change-over switch designed for seamless power transition. It features a two-station design, typically used for a primary (common) power source and a secondary (backup) power source. This device is suitable for AC systems operating at 50-60Hz with a rated current ranging from 6A to 63A.

Its primary function is to automatically switch to the backup power supply when the main power fails, ensuring uninterrupted power. The switching speed is less than 50 milliseconds, effectively mitigating disruptions caused by power outages. When both primary and backup power sources are available, the ATS prioritizes the primary power source.

Key features of the ETEK EK4Q ATS include millisecond switching, quick transfer, PC level performance, low energy consumption, silver contacts for reliability, and flame-retardant material for enhanced safety.

ETEK EK4Q Automatic Transfer Switch with 'Automatic Switching After Power Off' text
Figur 1: Automatisk skift efter slukning

2. Sikkerhedsforanstaltninger

Please read and understand these safety precautions before installation, operation, or maintenance of the ETEK EK4Q ATS.

  • Voltage Kompatibilitet: A 220V ATS unit must not be used with a voltage lower than 185V. Similarly, a 110V ATS unit must not be used with a voltage lower than 90V. Operating outside these ranges may cause the internal coil to overheat and burn out.
  • Automatic Mode Restriction: The switch cannot be manually operated when it is in automatic mode. Attempting to do so may damage the internal coil.
  • 4P ATS fasesekvens: For 4-pole (4P) ATS units, ensure the correct connection of the phase sequence. Incorrect phase sequence connection can lead to contact burnout.
  • Manual Operation Procedure: Manual operation should only be performed after all power has been completely cut off. The selector switch must be in the "MANU" (manual) position for manual operation. After manual operation is complete, return the selector switch to the "AUTO" (automatic) position.
  • Spolebeskyttelse: The control circuit coil operates normally within 85%-110% of the rated operating voltage. Low input voltage can cause the coil to overheat and burn out.

3. Installation og opsætning

3.1 Montering

The ETEK EK4Q ATS is designed for 35mm standard DIN rail installation. It can be directly installed into a household lighting distribution box or similar electrical enclosures.

ETEK EK4Q ATS mounted on a 35mm standard DIN rail
Figur 2: Installation på 35 mm standard DIN-skinne

3.2 Komponentidentifikation

Familiarize yourself with the components of the ATS unit:

Detaljeret view of 2P ATS with labeled components
Figure 3: 2P ATS Component Identification
  • I: Common Power Supply (Main)
  • II: Backup Power Supply
  • L1/L2/L3: Live Wires
  • N: Neutral ledning
  • LOAD: Load Output
  • MANU/AUTO Switch: Selector for Manual or Automatic operation.
  • Indikatorer: Lights to show which power source is active (Common Power Indicator, Backup Power Indicator) and closing status (Common Closing Indicator, Backup Closing Indicator).
  • Manuel betjeningshåndtag: Used for manual switching when in MANU mode.
  • AUX-terminal: Ekstern indikator kan tilsluttes for at vise ON/OFF status.

3.3 Ledningsdiagrammer

Sørg for, at al ledningsføring udføres af en kvalificeret elektriker og overholder lokale el-forskrifter.

3.3.1 2-Pole (2P) Wiring

Wiring diagram for 2-pole ATS
Figure 4: 2P Wiring Diagram

Connect the common power supply (L, N) to terminals I and the backup power supply (L, N) to terminals II. The load output (L, N) connects to the bottom terminals.

3.3.2 4-Pole (4P) Wiring

Wiring diagram for 4-pole ATS
Figure 5: 4P Wiring Diagram

For 4P units, connect the common power supply (L1, L2, L3, N) to terminals I and the backup power supply (L1, L2, L3, N) to terminals II. The load output connects to the bottom terminals. Pay close attention to phase sequence for 4P connections.

4. Betjeningsvejledning

4.1 Automatisk drift

In normal operation, set the MANU/AUTO selector switch to the "AUTO" position. The ATS will automatically monitor the primary power supply. If the primary power fails, the switch will automatically transfer the load to the backup power supply within 50 milliseconds. When the primary power is restored, the ATS will automatically switch back to the primary source.

ETEK EK4Q ATS with 'One-Key Conversion' text, showing quick emergency power switching
Figure 6: One-Key Conversion for Emergency Power

4.2 Manuel betjening

Manual operation is primarily for inspection and maintenance purposes. Before attempting any manual operation, ensure all power to the ATS unit is completely cut off.

  1. Cut off all power to the ATS unit.
  2. Move the MANU/AUTO selector switch to the "MANU" (manual) position.
  3. Use the manual operation handle to switch between power sources I and II as needed for inspection or maintenance.
  4. Once manual operations are complete, return the selector switch from the "MANU" position to the "AUTO" position.
  5. Restore power to the ATS unit.

Forsigtighed: Manual operation while the unit is energized or in "AUTO" mode can cause damage to the device and poses a safety risk.

5. Vedligeholdelse

The ETEK EK4Q ATS is designed for durability and minimal maintenance. Its shell is made of high-quality, wear-resistant, and compressive material, ensuring stability in complex and harsh environments.

ETEK EK4Q ATS highlighting its cold and heat-resistant shell
Figur 7: Kulde- og varmebestandig skal

Regular visual inspections are recommended to check for any signs of damage, loose connections, or overheating. Ensure the area around the ATS is clean and free from obstructions to allow for proper ventilation.

For any internal inspection or maintenance, always follow the manual operation safety guidelines outlined in Section 4.2, ensuring all power is disconnected before proceeding.

6. Fejlfinding

  • ATS skifter ikke automatisk:
    • Check if the MANU/AUTO selector switch is in the "AUTO" position.
    • Verify that the control voltage for the coil is within the normal operating range (85%-110% of rated voltage). Low voltage can prevent proper operation or cause coil burnout.
    • Ensure both primary and backup power sources are correctly connected and supplying power.
  • Coil Overheating/Burnout:
    • This is often caused by operating the ATS with a voltage lower than specified (e.g., below 185V for 220V units, or below 90V for 110V units). Verify input voltage.
    • Ensure the switch is not manually operated while in "AUTO" mode.
  • 4P ATS Contacts Burnout:
    • This indicates an incorrect phase sequence connection. Review the wiring diagram (Figure 5) and ensure phases are correctly matched.
  • Excessive Silver Alloy Loss During Manual Operation:
    • This can occur if manual switching is performed too quickly or forcefully, or if done while the unit is energized. Always ensure power is cut off and operate the handle smoothly.

7. Specifikationer

The following table details the technical specifications for the ETEK EK4Q Automatic Transfer Switch:

Table of technical specifications for ETEK EK4Q ATS
Figur 8: Tekniske specifikationer
ParameterVærdi
Antal poler2P/4P
Rated Operating Current Ie(A)40A, 63A
Nominel isolering Voltage UiAC 690V
Nominel voltage UeAC 400V
Nominel frekvens50/60Hz
KlassePC Class (can be switched on a loaded without generating short-circuit current)
Control Circuit Rated Voltage osAC 220V, 50/60Hz (Normal working conditions: 85%Us-110%Us)
Nominel impulsmodstand Voltage8kV
HjælpekredsløbAC 220V 50Hz/60Hz Ie=5A
Kontaktorskiftetid<50 ms
Driftsskiftetid<50 ms
Returskiftetid<50 ms
Sluk tid<50 ms
Change-over Operation Time<50 ms
Mekanisk liv≥6000 gange
Elektrisk liv≥1500 gange

7.1 Dimensioner

Dimensions for 2P and 4P ETEK EK4Q ATS models
Figure 9: Product Dimensions (2P and 4P)
  • 2P Model: Bredde: 66 mm, Dybde: 80 mm, Højde: 106 mm
  • 4P Model: Width: 36mm + 66mm (total 102mm), Depth: 80mm, Height: 106mm

8. Brugertips

  • Understanding Power Source Designations:
    • C to G: Refers to switching between City Power (Common) and a Generator (Backup).
    • C to C: Refers to switching between two City Power sources (e.g., two different utility feeds).
    • C to PV: Refers to switching between City Power (Common) and Photovoltaic (Solar) Energy (Backup), often involving a battery-powered inverter. If your primary source is city power and your secondary is a battery-powered inverter, the 'C to PV' model is the appropriate choice.
  • Voltage Stabilitet: Always ensure your power sources provide stable voltage within the specified operating range to prevent damage to the ATS coil.
  • Manuel tilsidesættelse: Remember that the manual override function is strictly for maintenance and troubleshooting when the power is off. Do not attempt to use it as a regular switching mechanism.

9. Garanti og support

For specific warranty information regarding your ETEK EK4Q Automatic Transfer Switch, please refer to your purchase documentation or contact the seller directly. Warranty terms may vary based on region and retailer.

For technical support or inquiries, you may contact ETEK directly:

Kontaktperson: Fiona Chen (E-Commerce Director)
Telefon/WhatsApp: +86 15858775919
E-mail: sales22@etek-china.com
ETEK contact information including QR code, phone, and email
Figure 10: ETEK Contact Information

Relaterede dokumenter - EK4Q

Preview ETEK ETL3-63-seriens RCCB med overstrømsbeskyttelse (RCBO) brugermanual
Brugermanual til ETEK ETL3-63, ETL3-63H, ETL3-63M og ETL3-63MH RCCB med overstrømsbeskyttelse (RCBO). Indeholder tekniske data, karakteristika, dimensioner og kredsløbsdiagrammer til installation og drift.
Preview ETEK Industristyrings-elektrisk: Omfattende produktkatalog og tekniske specifikationer
Udforsk ETEKs udvalg af industrielle elektriske styringsprodukter, herunder kontaktorer, relæer, afbrydere, afbrydere og meget mere. Dette katalog indeholder detaljerede tekniske specifikationer, produktinformationviews og udvælgelsesvejledninger til automatisering og elektriske systemer.
Preview ETEK Type B, B HP, B+, EV RCD'er og RCBO'er: Fejlstrømsafbrydere
Opdag ETEKs avancerede AC-DC-følsomme fejlstrømsafbrydere (RCD'er) og fejlstrømsafbrydere med overstrømsbeskyttelse (RCBO'er). Disse enheder, der findes i modellerne Type B, Type B HP, Type B+ og Type EV, tilbyder omfattende beskyttelse mod forskellige fejlstrømme til private, kommercielle og industrielle applikationer.
Preview ETEK Metal Consumer Units and Electrical Distribution Equipment
This comprehensive catalog from ETEK showcases their extensive range of Metal Consumer Units and electrical distribution equipment. Featuring products like MCBs, RCCBs, RCBOs, SPDs, isolator switches, and multifunction meters, ETEK provides reliable and safe solutions for residential, commercial, and industrial electrical installations. Discover detailed specifications and product information for the EKDB16S series and more.
Preview ETEK kredsløbsbeskyttelsesløsninger til fotovoltaiske systemer
Omfattende katalog over ETEK Electrics kredsløbsbeskyttelsesløsninger til solcelleanlæg, herunder MCB'er, MCCB'er, SPD'er, isolatorafbrydere, kombinerbokse, stik og kabler, designet til sikkerhed og pålidelighed i solenergiapplikationer.
Preview ETEK EKEC1 AC ladesøjle til elektrisk køretøj brugermanual ver. 3.1
Denne brugermanual indeholder omfattende instruktioner til ETEK EKEC1 AC-ladesøjlen til elektriske køretøjer, herunder produktbeskrivelse, navngivningsregler, tekniske data, installation, betjening, sikkerhedsforanstaltninger, DLB-funktion, indikatorlamper, garanti og vedligeholdelse.