SmartGen HAT361 HAT361C

SmartGen HAT361 HAT361C Dual Power Automatic Switching Controller

Brugermanual

Model: HAT361, HAT361C | Brand: SmartGen

1. Introduktion

The SmartGen HAT360 series dual power automatic transfer switch (ATS) controller, including models HAT361 and HAT361C, is designed with a microprocessor core for precise monitoring and control of dual power systems. It accurately measures two-way voltages, detects abnormalities (such as over/under voltage, over/under frequency, loss of phase, and reverse phase sequence), and intelligently manages the transfer between power sources. This controller integrates an LCD display and digital communication capabilities, providing a user-friendly interface for efficient power management.

The HAT361C model includes RS485 communication for remote control and monitoring via Modbus protocol.

2. Sikkerhedsoplysninger

Læs og forstå alle sikkerhedsinstruktioner før installation og betjening. Manglende overholdelse af disse instruktioner kan resultere i elektrisk stød, brand eller alvorlig personskade.

  • Sørg for, at alle strømkilder er afbrudt, før du udfører installation, ledningsføring eller vedligeholdelse.
  • Kun kvalificeret personale bør installere og servicere dette udstyr.
  • Verify all wiring connections are correct and secure according to the provided diagrams.
  • Do not operate the controller if it is damaged or malfunctioning.
  • Keep the controller away from moisture, extreme temperatures, and corrosive environments.
  • Sørg for korrekt jording for at forhindre elektriske farer.

3. Produktet er slutview

The HAT361/HAT361C controllers are designed for dual power ATS applications, offering robust features for reliable power transfer.

3.1 Funktioner og egenskaber

  • Configurable for 3P4W, 3P3W, 2P3W, or 1P2W AC systems.
  • Intelligent MCU-based monitoring and control.
  • S1/S2 master/slave configuration for auto transfer/restore and non-restore modes.
  • Supports Auto and Manual operation modes.
  • OFF mode disables breaker close/open functions.
  • System type settings for S1 Mains S2 Mains, S1 Gen S2 Mains.
  • Measures and displays 2-way 3-phase voltage, frequency, and alarm status.
  • Suitable for two-breaking, one-breaking, and no-breaking switches.
  • Includes switch re-closing function.
  • RS485 serial communication port (optional on HAT361C) for remote control, measuring, communication, and adjustment via Modbus protocol.
  • Overvoltage, undervoltage, overfrequency, underfrequency, loss of phase, and reverse phase sequence detection.
  • Adjustable thresholds for voltage and frequency abnormalities.
  • Manual test function for genset start/stop.
  • LED indicators for current ATS close status, power status, mode (manual/auto/OFF), and alarms.
  • 2-vejs N-trådsisoleret design.

3.2 Frontpanelets layout

The front panel provides visual indicators and control buttons for easy operation.

SmartGen HAT361 Front Panel

Figure 1: SmartGen HAT361 Front Panel. Shows S1/S2 indicators, LOAD indicator, OFF button, Auto/Manual buttons, S1 Close/Open/S2 Close buttons, and the SmartGen display.

SmartGen HAT361C Front Panel

Figure 2: SmartGen HAT361C Front Panel. Similar layout to HAT361, indicating the 'C' model variant.

4. Opsætning og installation

Careful installation and wiring are crucial for the proper functioning of the ATS controller.

4.1 Controller Dimensions and Panel Cutout

The controller is designed for panel mounting. Ensure the panel cutout matches the specified dimensions.

MålingVærdi
Kuffert Dimensioner132 mm x 102 mm x 49 mm
Panel udskæring132 mm x 102 mm

4.2 Rear Panel and Terminal Description

The rear panel houses all necessary connection terminals. Refer to the diagrams and table below for proper wiring.

SmartGen HAT361 Rear Panel Wiring Terminals

Figure 3: SmartGen HAT361 Rear Panel with Wiring Terminals. Shows inputs for S1/S2 AC voltage, GEN START, S1/S2 CLOSE INPUT, RS485, and AUX OUTPUT.

HAT361C Panel Diagram

Figure 4: HAT361C Panel Diagram. Detailed view of terminal numbering on the rear panel.

Ingen.PunktBemærkning
1A1AC 3 phase 4 wire voltage input of S1 (For single phase input, only connect A1,N1)
2B1
3C1
4N1
5A2AC 3 phase 4 wire voltage input of S2 (For single phase input, only connect A2,N2)
6B2
7C2
8N2
9INGENATS supply power N (Provide supply power for ATS)
10INGENATS supply power L (Capacity: 12A 250VAC)
11LOATS supply power L (NC for terminal 10 of HAT361)
12INGEN
13KOMOutput common port
14S1 CLOSES1 close output (Capacity: 10A 250VAC)
15S2 CLOSES2 close output (Capacity: 10A 250VAC)
16S1 OPEN OUTPUTS1 open output (Capacity: 10A 250VAC)
17S2 OPEN OUTPUTS2 open output (Capacity: 10A 250VAC)
18GEN STARTGenset start output (Capacity: 7A 250VAC)
19KOMInput common port
20FORCE OPENForced open input (Connect GND of input common port)
21KOMInput common port
22S2 CLOSE INPUTS2 close input (Connect GND of input common port)
23KOMInput common port
24S1 CLOSE INPUTS1 close input (Connect GND of input common port. Users need to connect this terminal to terminal 27 based on on-site network arrangement, used to connect with the 120Ω resistor inside the controller)
25TRRS485 matching resistor (120Ω impedance matching resistor inside the controller)
26TR
27B (-)RS485 kommunikationsport
28A (+)
29KOMFælles havn
30AUX-INPUTAux. input (Connect GND of input common port)
31AUX-UDGANGAux. output (Capacity: 10A 250VAC)
32

4.3 Typiske ledningsdiagrammer

Below are typical application wiring diagrams. Always consult local electrical codes and standards.

4.3.1 SGG-N/T Application Diagram

SGG-N/T Application Wiring Diagram

Figure 5: SGG-N/T Application Diagram. Illustrates connections for S1 Power Input, S2 Power Input, Load, ATS Controller, and Remote Start for SGG-N/T type switches. Note: Suitable for HAT363 (No Breaking) controller model.

4.3.2 ATYS Application Diagram

ATYS Application Wiring Diagram

Figure 6: ATYS Application Diagram. Illustrates connections for S1 Power Input, S2 Power Input, Load, ATS Controller, and Remote Start for ATYS type switches. Note: Suitable for HAT363 (One breaking) controller model.

4.3.3 PHETENG Application Diagram

PHETENG Application Wiring Diagram

Figure 7: PHETENG Application Diagram. Illustrates connections for S1 Power Input, S2 Power Input, Load, ATS Controller, and Remote Start for PHETENG type switches. Note: Suitable for HAT363 (Two breakings) controller model.

4.3.4 Motor Type Application Diagram

Motor Type Application Wiring Diagram

Figure 8: Motor Type Application Diagram. Illustrates connections for S1 Power Input, S2 Power Input, Load, ATS Controller, and Remote Start for Motor Type switches. Note: Suitable for HAT361/HAT363 (One breaking) controller model.

5. Betjening

This section details the operational modes, key functions, and display information of the controller.

5.1 Indicator Display

The front panel LEDs provide immediate status feedback.

IndikatorBeskrivelse
S1 Power IndicatorExtinguishes when S1 power blackout; Illuminates when S1 power is normal.
S1 Close IndicatorFlashes when S1 power is abnormal (over/under voltage, under/over frequency, loss of phase, reverse phase sequence); Illuminates when S1 is closed, otherwise, it extinguishes.
S2 Power IndicatorIlluminates when S2 power is normal; Extinguishes when S2 power blackout.
S2 Close IndicatorFlashes when S2 power is abnormal (over/under voltage, under/over frequency, loss of phase, reverse phase sequence); Illuminates when S2 is closed, otherwise, it extinguishes.
AlarmindikatorIlluminates when there is an alarm.
OFF Mode IndicatorIlluminates in OFF mode, extinguishes in other modes.
Indikator for automatisk tilstandIlluminates in Auto mode, extinguishes in other modes.
Indikator for manuel tilstandIlluminates in Manual mode, extinguishes in other modes.

5.2 Key Function Description

The controller features several keys for navigation and control.

IkonNøgleFunktionsbeskrivelse
UpIn main interface, scrolls up the screen; In menu interface, moves cursor up or increases number.
NedIn main interface, scrolls down the screen; In menu interface, moves cursor down or reduces number.
*/okSet/Confirm/Lamp PrøveIn main interface, moves cursor and confirms settings. Long press tests lamps (all white screen, all LEDs illuminate, alarms reset).
SLUKKETSLUKKETEnters OFF mode, controller exits control.
AutoAuto-tilstandEnters Auto mode.
S1 CloseS1 CloseActive in manual mode; closes S1 outputs, S1 takes load.
ÅbenÅbenActive in manual mode; load disconnects.
S2 CloseS2 CloseActive in manual mode; closes S2 outputs, S2 takes load.
ManuelManuel tilstandEnters Manual mode.

5.3 LCD-skærm

The LCD provides detailed information about the system status.

TilfredsBeskrivelse
Hovedgrænsefladedisplay
S1 BlackoutS1 voltage status
S2 BlackoutS2 voltage status
OffloadATS status
Genset WorkingGensæt status
Manuel tilstandStatuslinje
Volt
LL1S1 line voltage
LL2S2 line voltage
Volt
LN1S1 phase voltage
LN2S2 phase voltage
Frekv
F1S1 frequency
F2S2 frequency
Fasesekvens
P1S1 Phase Sequence
P2S2 Phase Sequence
S1 Failed to CloseAlarminformation

5.4 Driftstilstande

5.4.1 Manuel tilstand

To enter Manual Mode, press the Manuel key. The manual status indicator will illuminate. In this mode, you can manually control the S1 and S2 breakers:

  • S1 Close: If the load is open, S1 closes and supplies power to the load.
  • S2 Close: If the load is open, S2 closes and supplies power to the load.
  • Åben: Disconnects the load from both power sources.

5.4.2 Auto-tilstand

To enter Auto Mode, press the Auto key. The auto status indicator will illuminate. In Auto Mode, the controller automatically transfers the switch based on the status of S1 and S2 power, transfer priority, and auto transfer/restore settings to ensure continuous power supply to the load.

5.4.3 Auto Transfer/Restore Logic

The controller follows specific logic for automatic transfer and restoration. An example of 'S1 master' and 'S2 Mains S2 Gen' control logic is illustrated below:

Auto Transfer/Restore Flowchart

Figure 9: Auto Transfer/Restore Flowchart. Details the sequence of events for S1 Normal, S1 Abnormal, S2 Normal, and S2 Abnormal conditions, including delays and generator start signals.

5.4.4 Auto Transfer Non-Restore (Mutual Backup Active) Logic

This mode is used when both power sources act as mutual backups.

Auto Transfer Non-Restore Flowchart

Figure 10: Auto Transfer Non-Restore (Mutual Backup Active) Flowchart. Illustrates the logic for non-restorative transfer between S1 and S2.

6. Specifikationer

Detailed technical parameters for the HAT361/HAT361C controllers.

6.1 Tekniske parametre

genstandeIndhold
Operation VoltageAC supply, voltage range AC170-277V
Strømforbrug≤5W (Standby mode: ≤2W)
AC Voltage Indgang3P4W (L-N): AC170V~AC277V
3P3W (L-L): AC170V~AC277V
2P3W (L-N): AC170V~AC277V
1P2W (L-N): AC170V~AC277V
Nominel voltageNominel: 380V
Nominel frekvensRange: 50Hz/60Hz
NøjagtighedVoltage: ±2%, Frequency: ±0.1Hz
Luk relæudgang10A AC250V volts free output
Hjælperelæudgang10A AC250V volts free output
Genset Crank Relay Output7A AC250V volts free output
LONG Relay Output12A AC275V Active output
FORBINDELSESmartGen special interface for program upgrade, parameter configuration
RS485Modbus-RTU communication protocol, max communication distance is 1000m (HAT361C only)
DesignstandardMeet GB/T 14048.11-2016 and IEC/EN 60947-6-1
SikkerhedskravMeet EN 61010-1 (installation category (overvoltage type) III, 300V, pollution degree 2), altitude ≤3000m
Kuffert Dimensioner132 mm x 102 mm x 49 mm
Panel udskæring132 mm x 102 mm
Arbejdstemperatur(-25~+70)°C
Arbejdsfugtighed(20~90)%RH
Opbevaringstemperatur(-30~+80)°C
BeskyttelsesniveauFrontpanel IP40
IsoleringsstyrkePåfør AC2.2kV voltage mellem høj voltage terminal og lav voltage terminal and the leakage current is not more than 3mA within 1min; insulation resistor 100MΩ
Vægt0.59 kg

6.2 Modelsammenligning

PunktHAT361HAT361CHAT363HAT363C
Inputs (L1,N,70V-277V)3+13+13+13+1
Outputs (Fixed + Aux.)4+14+15+15+1
Genset Control
RS485
LONG Output

Note: HAT361/HAT361C defaults to one breaking. HAT363/HAT363C defaults to two breakings.

7. Vedligeholdelse

To ensure the longevity and reliable operation of your SmartGen ATS controller, follow these general maintenance guidelines:

  • **Regular Inspection**: Periodically check the controller for any visible damage, loose connections, or signs of overheating.
  • **Cleaning**: Keep the controller's front panel and ventilation openings clean and free of dust. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.
  • **Firmwareopdateringer**: Tjek producentens website for any available firmware updates. Follow the instructions carefully if performing an update.
  • **Environmental Conditions**: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent premature component failure.
  • **Wiring Integrity**: Annually inspect all wiring connections for tightness and corrosion. Loose connections can lead to intermittent operation or damage.

8. Fejlfinding

If you encounter issues with your HAT361/HAT361C controller, consider the following general troubleshooting steps:

  • **No Power/Display Off**: Check the power supply to the controller. Ensure all power input terminals are correctly wired and receiving the specified voltage.
  • **No Automatic Transfer**: Verify that the controller is in 'Auto Mode'. Check the status of S1 and S2 power sources on the display. Ensure all abnormal conditions (over/under voltage, frequency) are cleared. Review the wiring for S1/S2 voltage inputs and breaker control outputs.
  • **Manual Operation Fails**: Ensure the controller is in 'Manual Mode'. Check the wiring to the S1/S2 close and open outputs.
  • **Alarm Indicator On**: Check the LCD display for specific alarm messages. Refer to the 'Indicator Display' section for common alarm meanings. Address the underlying issue (e.g., voltage abnormality, frequency deviation).
  • **Communication Issues (HAT361C)**: Verify RS485 wiring (A+, B-, GND) is correct and secure. Ensure the 120Ω matching resistor is properly connected if required by your setup. Check communication settings (baud rate, parity) on both the controller and the connected device.
  • **Incorrect Readings**: Confirm that the voltage and current transformer ratios (if applicable) are correctly configured in the controller's settings.

If the problem persists after performing these checks, contact technical support.

9. Brugertips

  • **Parameter Configuration**: Take time to properly configure all parameters, especially voltage and frequency thresholds, to match your specific power system requirements.
  • **Test Regularly**: Periodically test the automatic transfer function to ensure the system operates as expected during a power outage.
  • **Backup Settings**: If possible, record or back up your controller's configuration settings for quick restoration in case of a reset or replacement.
  • **Environmental Protection**: While the front panel is IP40 rated, ensure the overall installation protects the controller from excessive dust and moisture, especially the rear terminals.

10. Garanti og support

For warranty information, technical support, or service inquiries, please contact your authorized SmartGen dealer or the manufacturer directly. Keep your purchase receipt and product serial number handy when contacting support.

Fabrikantens kontaktoplysninger:

  • Web: www.smartgen.cn/
  • Email: sales@smartgen.cn

SmartGen forbeholder sig retten til at ændre indholdet af dette dokument uden forudgående varsel.

Documents - SmartGen – HAT361 HAT361C
[Pdf] Brugermanual Dimensionsvejledning
Administrator SmartGen HAT361 HAT361C HAT363 HAT363C User Manual v1 2 HAT360 Dual Power ATS Controller Controllers Technical Parameters AC System 1P2W 2P3W 3P3W 3P4W Alternator Frequency 50 60Hz Applicable Switch Type two breaking one no switch Case Dimensions mm 143*124*49 Panel Cutout 132*113 Operating Temp 25~ 70 ℃ Product Overview series dual power controller is made with the microprocessor as core which can precisely measure way voltages make correct judgment and control outputs for occurred voltag smartgen america upload iblock 09f 0u5jvrea0bkqhixsg9lplg6q6lzezovn |||
HAT360 SERIES HAT361/HAT361C/HAT363/HAT363C DUAL POWER ATS CONTROLLER USER MANUAL Registered trademark No.28 Xuemei Street, Zhengzhou, Henan, China Tel: 86-371-67988888/67981888/67992951 86-371-67981000 overseas Fax: 86-371-67992952 Web: www.smartgen.com.cn/ www.smartgen.cn/ Email: sales sma...
pointtal: 50 filestørrelse: 1.75 millioner sideantal: 30 dokumentdato: 2023-10-27
[Pdf] Brugermanual

With the development of technology and society,people s living standardsare improving unceasingly,they need more reliable,secure,uninterruptedpower supply that many of them use dual power supply. Under this situation,SmartGen provide high-quality products for reliable, continuous power supply to sol...
pointtal: 32 filestørrelse: 4 millioner sideantal: 3 dokumentdato: 2023-12-19