ETEK EKL13

ETEK EKL13 RCBO Residual Current Circuit Breaker with Overcurrent Protection

Brugermanual

1. Introduktion

The ETEK EKL13 RCBO (Residual Current Circuit Breaker with Overcurrent Protection) is an advanced electrical safety device designed to protect against various electrical faults. It combines the functions of a Miniature Circuit Breaker (MCB) and a Residual Current Device (RCD), offering comprehensive protection against short circuits, overloads, and dangerous earth leakage currents. This manual provides essential information for the safe installation, operation, and maintenance of your EKL13 RCBO.

2. Sikkerhedsoplysninger

WARNING: Electrical work should only be performed by qualified and licensed electricians. Improper installation or handling can result in serious injury or death.

  • Always disconnect power at the main supply before installing, servicing, or removing the RCBO.
  • Ensure the RCBO's rated current and sensitivity match the requirements of your electrical system.
  • Do not operate the device if it appears damaged or faulty.
  • Følg alle lokale og nationale elektriske forskrifter og bestemmelser.
  • The device housing is made of flame-retardant material for enhanced safety.

3. Opsætning og installation

The EKL13 RCBO is designed for easy installation on a standard DIN rail within a distribution box.

3.1. Montering

  1. Sørg for, at hovedstrømforsyningen er SLUKKET.
  2. Locate an available slot on the DIN rail inside your electrical distribution box.
  3. Align the RCBO with the DIN rail. The video below demonstrates the mounting process.
  4. Press the RCBO firmly onto the DIN rail until it clicks into place. Ensure it is securely fastened.
Video: Demonstration of DIN rail mounting and operation of the EKL13 RCBO.

3.2. Ledninger

Refer to the wiring diagram printed on the device and the image below for correct connections. The EKL13 RCBO features silver alloy contact terminal blocks for large load current and excellent conductivity.

ETEK EKL13 RCBO Product Parameters and Wiring Diagram
Billede: Detaljeret view of the EKL13 RCBO showing the product handle, test button, product parameters, wiring diagram, and CE certification mark.

The wiring diagram on the device indicates the following connections:

  • 1N (Input Neutral): Connect the incoming neutral wire.
  • 1 (Input Line): Connect the incoming live/phase wire.
  • 2N (Output Neutral): Connect the outgoing neutral wire to the load.
  • 2 (Output Line): Connect the outgoing live/phase wire to the load.

Sørg for, at alle forbindelser er tætte og sikre for at forhindre løse kontakter og potentielle farer.

Product Selection Diagram for Distribution Box
Image: Illustrative diagram showing various components in a distribution box, including where an RCBO fits in the electrical circuit.

4. Betjeningsvejledning

The EKL13 RCBO is simple to operate with its main handle and test button.

4.1. Switching ON/OFF

  • For at dreje strømmen ON, push the handle upwards. The indicator window will show RØD, indicating the line is connected.
  • For at dreje strømmen SLUKKET, push the handle downwards. The indicator window will show GRØN, indicating the line is disconnected.
RCBO Indicator Window Visual Red and Green
Image: Visual representation of the indicator window showing green for OFF (line disconnected) and red for ON (line connected).

4.2. Testknap

The RCBO is equipped with a 'Test Monthly' button (marked 'T'). This button is crucial for verifying the proper functioning of the residual current protection mechanism.

5. Vedligeholdelse

Regular maintenance ensures the continued reliability and safety of your EKL13 RCBO.

5.1. Monthly Test

It is recommended to press the 'Test Monthly' button at least once a month. When pressed, the RCBO should trip (switch to OFF position), indicating that the leakage protection core is functioning correctly. If the device does not trip, it may be faulty and should be inspected and replaced by a qualified electrician.

RCBO Leakage Protection Core Rapid Power Off
Image: Highlights the 0.1s rapid power off feature for leakage protection and the monthly test button.

6. Fejlfinding

The EKL13 RCBO is designed to protect against common electrical hazards. If the device trips, it indicates a fault in the circuit it protects.

  • RCBO trips frequently: This indicates a persistent fault such as a short circuit, overload, or earth leakage.
  • No power to the circuit: Check if the RCBO is in the OFF position. If it trips immediately after being reset, a fault is present.
  • RCBO does not trip when test button is pressed: The leakage protection mechanism may be faulty.

Action: If the RCBO trips, first try to reset it. If it trips again immediately or repeatedly, or if the test button fails to trip the device, do not attempt further resets. Disconnect power to the affected circuit and consult a qualified electrician to identify and rectify the underlying electrical fault.

Common Electrical Problems: Short Circuit, Overload, Line Overload
Image: Illustrates common electrical problems like short circuit hazard, overload hazard, and line overload, against which the RCBO provides protection.

7. Specifikationer

The following table outlines the technical specifications for the ETEK EKL13 RCBO:

ParameterVærdi
StandardIEC/EN61009-1
Antal stænger1P+N
Nominel strøm6-63A (modelafhængig)
Type beskyttelseAC, A
Rated sensitivity currents (IΔn)10, 30, 100, 300mA (model dependent)
Residual current off-time under IΔn≤0.1s
Vurderet voltage (Ue)230/240V~
Nominel frekvens50/60Hz
Nominel brudkapacitet6,000A
Nominel impuls voltage (Uimp)4,000V
Thermal-magnetic characteristicB, C
Elektrisk levetid4,000 cyklusser
CertificeringCE

7.1. Dimensioner

ETEK EKL13 RCBO Product Dimensions
Image: Dimensions of the EKL13 RCBO, showing measurements such as 81.8mm height, 36mm width, 49.8mm depth, and 46.1mm mounting depth.

8. Brugertips

  • Phase and Neutral Compatibility: The EKL13 RCBO is designed for 1P+N configurations, meaning it works with one phase (live) and one neutral wire.
  • Europæisk certificering: The product holds CE certification, confirming its compliance with European safety standards.
  • Følsomhed: The rated sensitivity current (IΔn) is available in various ratings (10mA, 30mA, 100mA, 300mA). Ensure you select the appropriate sensitivity for your application to provide adequate protection against earth leakage.

9. Garanti og support

For any technical assistance, warranty claims, or support inquiries, please contact your authorized ETEK dealer or the ETEK customer service department. Keep your purchase receipt as proof of purchase.


ETEK EKL13-63 RCBO Residual Current Circuit Breaker with Overcurrent Protection & DIN Rail Installation

ETEK EKL13-63 RCBO Residual Current Circuit Breaker with Overcurrent Protection & DIN Rail Installation

0:37 • 720×720 • visuel_overview

Relaterede dokumenter - EKL13-63

Preview ETEK Type B, B HP, B+, EV RCD'er og RCBO'er: Fejlstrømsafbrydere
Opdag ETEKs avancerede AC-DC-følsomme fejlstrømsafbrydere (RCD'er) og fejlstrømsafbrydere med overstrømsbeskyttelse (RCBO'er). Disse enheder, der findes i modellerne Type B, Type B HP, Type B+ og Type EV, tilbyder omfattende beskyttelse mod forskellige fejlstrømme til private, kommercielle og industrielle applikationer.
Preview ETEK ETL3-63-seriens RCCB med overstrømsbeskyttelse (RCBO) brugermanual
Brugermanual til ETEK ETL3-63, ETL3-63H, ETL3-63M og ETL3-63MH RCCB med overstrømsbeskyttelse (RCBO). Indeholder tekniske data, karakteristika, dimensioner og kredsløbsdiagrammer til installation og drift.
Preview ETEK Industristyrings-elektrisk: Omfattende produktkatalog og tekniske specifikationer
Udforsk ETEKs udvalg af industrielle elektriske styringsprodukter, herunder kontaktorer, relæer, afbrydere, afbrydere og meget mere. Dette katalog indeholder detaljerede tekniske specifikationer, produktinformationviews og udvælgelsesvejledninger til automatisering og elektriske systemer.
Preview ETEK Metal Consumer Units and Electrical Distribution Equipment
This comprehensive catalog from ETEK showcases their extensive range of Metal Consumer Units and electrical distribution equipment. Featuring products like MCBs, RCCBs, RCBOs, SPDs, isolator switches, and multifunction meters, ETEK provides reliable and safe solutions for residential, commercial, and industrial electrical installations. Discover detailed specifications and product information for the EKDB16S series and more.
Preview ETEK kredsløbsbeskyttelsesløsninger til fotovoltaiske systemer
Omfattende katalog over ETEK Electrics kredsløbsbeskyttelsesløsninger til solcelleanlæg, herunder MCB'er, MCCB'er, SPD'er, isolatorafbrydere, kombinerbokse, stik og kabler, designet til sikkerhed og pålidelighed i solenergiapplikationer.
Preview ETEK Fuse Series Produktguide 2024: Omfattende oversigtview og specifikationer
Udforsk ETEK Fuse-serien, en række højtydende sikringer designet til industrielle og kommercielle anvendelser. Denne vejledning indeholder detaljerede specifikationer, applikationsnoter og udvælgelseskriterier for ETEK-sikringsproduktlinjen.