Advantage Controls Mega Tron Controller

Overview
The MegaTron controller supports BACnet communications with Building Management Systems and WebAdvantage. BACnet uses an object-oriented model so systems can interoperate over shared networks to exchange control/status functions.
Conformance & Object Support
- Applikationssoftwareversion: JA.16.0 and higher
- Firmwarerevision: JA.16.0 and higher
- BACnet Protocol Revision: 24
- BACnet Standardized Device Profile (bilag L): BACnet Application Specific Controller (B-ASC)
- BACnet interoperabilitet byggeklodser understøttet (bilag K): DS-RP-B, DM-DDB-B, DM-DCC-B, DM-RD-B
- Indstillinger for datalinklag: BACnet IP (Annex J)
- Character Set Supported: ANSI X3.4
Object/property support matrix: “See table 1-1 Object/Property Support Matrix.” (The table content is shown as property support markers but is not enumerated as concrete max values in the source excerpt.)
Example object instance summaries (examples shown in source excerpt): Binary Input objects BI-000 to BI-003; Binary Value objects BV-012 to BV-273 (multiple alarm/monitor functions); Analog Input objects AI-000 to at least AI-071 shown; Analog Value objects AV-000 to at least AV-126 shown; Multi-State Value objects MSV-000 to MSV-019 shown.
Hurtige opsætningstrin
- Open setup menus: Trykke Setup/Run, så KONFIGURER, NETVÆRK, INDSTILLINGER.
- Select BACnet: Trykke BAC. If options are not visible, enable the dual network card (source note).
- Enter instance/port: Indtast ENHEDSINSTANS og HAVN. Trykke Indtast to accept on each.
- Reset communications card: Trykke NULSTIL, og tryk derefter på Indtast to accept; wait for the communications card reset countdown.
- Reboot controller: After reset, cycle power til controlleren.
- Set device identifier (MegaTron XS): Go to Configure menu → Network settings → BAC and enter the device object identifier. The device object instance number range is 0 til 4194303, og 4194303 is described as “unconfigured” and not a valid device instance number.
BACnet introduktion
- MegaTron-controlleren er i stand til at oprette forbindelse til WebAdvantage Server og de fleste bygningsstyringssystemer. De WebAdvantage service requires a gateway to the internet with firewall and security rules in place. The
- Building Management System needs to be on the same subnet to properly receive traffic from the MegaTron. This may require some advanced routing of network traffic within the network wiring or programming of advanced switching equipment. The datatraffic for both is provided via the same Ethernet cable coming from the MegaTron.
- BACnet-protokollen tillader grænseflader med mere brugerdefinerbare pc-applikationer ved hjælp af HMI/SCADA og enkeltstående HMI-systemer
BACnet overståetview
- BACnet is an American National Standard. The BACnet protocol allows the creation of an automation and controls system which may interoperate with other BACnet systems. In BACnet terms, interoperate means that two or more
- BACnet-speaking computer systems may share the same communications networks, and ask each other to perform various functions on a peer-to-peer basis.
- BACnets fleksibilitet har to vigtige fordele: leverandøruafhængighed og fremadrettet kompatibilitet med fremtidige generationer af systemer. Dette opnås ved hjælp af en objektorienteret tilgang til at repræsentere al information inden for hver controller. Da BACnet er baseret på standarder, giver det maksimale fordele for både leverandøren, der designer BACnet-systemer, og specifikatoren eller ejeren af disse systemer.
Protokolimplementering
- Applikationssoftwareversion: JA.16.0 og højere
- Firmwarerevision: JA.16.0 og højere
- BACnet Protocol Revision: 24
- BACnet Standardized Device Profile (Annex L): BACnet Application Specific Controller (B-ASC) BACnet Interoperability Building Blocks Supported (Annex K):
- DS-RP-B
- DM-DDB-B
- DM-DCC-B
- DM-RD-B
- Standard Object Types Supported: See table 1-1 “Object/Property Support Matrix”. Data Link Layer Options: BACnet IP, (Annex J)
- Understøttet tegnsæt: ANSI X3.4
Forbinder
- Denne vejledning er designet til at hjælpe med at forbinde en BACnet-aktiveret MegaTron til en lokal BMS.
- Note: Screens may vary slightly between models.
BACnet opsætning
- Step 1: Press Setup/Run, CONFIGURE, NETWORK, SETTINGS. (See figures 1, 2, 3 and 4. H26 dual cards add figure 3B. H26 only available for MegaTron MT.)
- Step 2: Press BAC. (See figure 4.) Note: If these options are not visible, the dual network card needs to be enabled. See enabling dual network card to continue setup.
- Step 3: Enter the DEVICE INSTANCE and PORT. Press Enter to accept on each. (See figure 6.)
- Step 4: Press RESET and then press Enter to accept. The communications card will reset after a short countdown. (See figures 7 and 8.)
- Step 5: After the communications card has been reset cycle power to the controller.

MegaTron XS opsætning

- MegaTron XS vil være et "enhedsobjekt" på det bestemte BACnet-netværk. Hvert enhedsobjekt (din MegaTron XS) skal have en objektidentifikator, der er unik på netværket. Enhedsobjektets instansnummer konfigureres normalt på stedet, efter at enheden er installeret. Enhedsobjektets instansnummerområde er mellem 0 og 4194303. Bemærk, at 4194303 er kendt som "ukonfigureret" og egentlig ikke er et gyldigt enhedsinstansnummer. Alle enheder skal svare med deres eget enhedsobjekt-instansnummer, når der anmodes om 4194303.
- For at indtaste din enheds objektidentifikator skal du gå til menuen Konfigurer i MegaTron XS og vælge netværksindstillingerne. Vælg derefter BAC.
Objektdefinitioner
- Objekt-/egenskabsstøttematrix (tabel 1-1)
|
Ejendom |
Objekttype | |||||
| Enhed | Binær input | Binary Value | Analog indgang | Analog værdi | Multi-State Værdi | |
| Objektidentifikator | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
| Objektnavn | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
| Objekttype | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
| Beskrivelse | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
| Systemstatus | ✓ | |||||
| Leverandørens navn | ✓ | |||||
| Leverandøridentifikator | ✓ | |||||
| Modelnavn | ✓ | |||||
| Firmware-revision | ✓ | |||||
| App. Softwarerevision | ✓ | |||||
| Protokolversion | ✓ | |||||
| Protokolrevision | ✓ | |||||
| Understøttede tjenester | ✓ | |||||
| Understøttede objekttyper | ✓ | |||||
| Objektliste | ✓ | |||||
| Max APDU-længde | ✓ | |||||
| Segmenteringsstøtte | ✓ | |||||
| APDU timeout | ✓ | |||||
| Nummer APDU Genforsøg | ✓ | |||||
| Revision af database | ✓ | |||||
| Nutidsværdi | ✓ | ✓ | ✓ | ✓ | ✓ | |
| Statusflag | ✓ | ✓ | ✓ | ✓ | ✓ | |
| Hændelsestilstand | ✓ | ✓ | ✓ | ✓ | ✓ | |
| Ude af drift | ✓ | ✓ | ✓ | ✓ | ✓ | |
| Enheder | ✓ | ✓ | ||||
| Polaritet | ✓ | ✓ | ||||
| Antal stater | ✓ | |||||
| Tilstandstekst | ✓ |
Oversigt over binært inputobjektforekomst (tabel 1-2)
| Forekomst-id | Objektnavn | Formål | Nutidsværdi – Adgang |
| 0 | BI-000 | System #1 – Flowkontakt | Kun læse |
| 1 | BI-001 | System #2 – Flowkontakt | Kun læse |
| 2 | BI-002 | System #3 – Flowkontakt | Kun læse |
| 3 | BI-003 | System #4 – Flowkontakt | Kun læse |
Oversigt over binær værdiobjektforekomst (tabel 1-3)
| Forekomst-id | Objektnavn | Formål | Nutidsværdi – Adgang |
| 12 | BV-012 | System #1 – Konduktivitet høj alarm | Kun læse |
| 13 | BV-013 | System #1 – Alarm for lav ledningsevne | Kun læse |
| 14 | BV-014 | System #1 – Alarm for ledningsevnegrænse | Kun læse |
| 15 | BV-015 | System #1 – pH-høj alarm | Kun læse |
| 16 | BV-016 | System #1 – pH lav alarm | Kun læse |
| 17 | BV-017 | System #1 – pH-grænsealarm | Kun læse |
| 18 | BV-018 | System #1 – ORP høj alarm | Kun læse |
| 19 | BV-019 | System #1 – ORP lav alarm | Kun læse |
| 20 | BV-020 | System #1 – ORP-grænsealarm | Kun læse |
| 21 | BV-021 | System #1 – S. Høj temperatur alarm | Kun læse |
| 22 | BV-022 | System #1 – S. Lav temperatur alarm | Kun læse |
| 23 | BV-023 | System #1 – M. Temperatur høj alarm | Kun læse |
| 24 | BV-024 | System #1 – M. Lav temperatur alarm | Kun læse |
| 25 | BV-025 | System #1 – D. Høj temperatur alarm | Kun læse |
| 26 | BV-026 | System #1 – D. Lav temperatur alarm | Kun læse |
| 27 | BV-027 | System #1 – Ingen flowalarm | Kun læse |
| 28 | BV-028 | System #1 – Digital Input 1 Alarm | Kun læse |
| 29 | BV-029 | System #1 – Digital Input 2 Alarm | Kun læse |
| 30 | BV-030 | System #1 – Digital Input 3 Alarm | Kun læse |
| 31 | BV-031 | System #1 – Digital Input 4 Alarm | Kun læse |
| 32 | BV-032 | System #1 – Digital Input 5 Alarm | Kun læse |
| 34 | BV-034 | System #1 – M. Konduktivitet høj alarm | Kun læse |
| 35 | BV-035 | System #1 – M. Alarm for lav ledningsevne | Kun læse |
| 36 | BV-036 | System #1 – M. Alarm for ledningsevnegrænse | Kun læse |
| 37 | BV-037 | System #1 – Notesblok 1 Høj alarm | Kun læse |
| 38 | BV-038 | System #1 – Notesblok 2 Høj alarm | Kun læse |
| 39 | BV-039 | System #1 – Notesblok 3 Høj alarm | Kun læse |
| 40 | BV-040 | System #1 – Notesblok 4 Høj alarm | Kun læse |
| 41 | BV-041 | System #1 – Notesblok 5 Høj alarm | Kun læse |
| 42 | BV-042 | System #1 – Notesblok 6 Høj alarm | Kun læse |
| 43 | BV-043 | System #1 – Notesblok 7 Høj alarm | Kun læse |
| 44 | BV-044 | System #1 – Notesblok 8 Høj alarm | Kun læse |
| 45 | BV-045 | System #1 – Notesblok 9 Høj alarm | Kun læse |
| 46 | BV-046 | System #1 – Notesblok 10 Høj alarm | Kun læse |
| 47 | BV-047 | System #1 – Notesblok 1 lav alarm | Kun læse |
| 48 | BV-048 | System #1 – Notesblok 2 lav alarm | Kun læse |
| 49 | BV-049 | System #1 – Notesblok 3 lav alarm | Kun læse |
| 50 | BV-050 | System #1 – Notesblok 4 lav alarm | Kun læse |
| 51 | BV-051 | System #1 – Notesblok 5 lav alarm | Kun læse |
| 52 | BV-052 | System #1 – Notesblok 6 lav alarm | Kun læse |
| 53 | BV-053 | System #1 – Notesblok 7 lav alarm | Kun læse |
| 54 | BV-054 | System #1 – Notesblok 8 lav alarm | Kun læse |
| 55 | BV-055 | System #1 – Notesblok 9 lav alarm | Kun læse |
| 56 | BV-056 | System #1 – Notesblok 10 lav alarm | Kun læse |
| 57 | BV-057 | System #1 – Notesblok 1 Tidsalarm | Kun læse |
| 58 | BV-058 | System #1 – Notesblok 2 Tidsalarm | Kun læse |
| 59 | BV-059 | System #1 – Notesblok 3 Tidsalarm | Kun læse |
| 60 | BV-060 | System #1 – Notesblok 4 Tidsalarm | Kun læse |
| 61 | BV-061 | System #1 – Notesblok 5 Tidsalarm | Kun læse |
| 62 | BV-062 | System #1 – Notesblok 6 Tidsalarm | Kun læse |
| 63 | BV-063 | System #1 – Notesblok 7 Tidsalarm | Kun læse |
| 64 | BV-064 | System #1 – Notesblok 8 Tidsalarm | Kun læse |
| 65 | BV-065 | System #1 – Notesblok 9 Tidsalarm | Kun læse |
| 66 | BV-066 | System #1 – Notesblok 10 Tidsalarm | Kun læse |
| 81 | BV-081 | System #2 – Konduktivitet høj alarm | Kun læse |
| 82 | BV-082 | System #2 – Alarm for lav ledningsevne | Kun læse |
| 83 | BV-083 | System #2 – Alarm for ledningsevnegrænse | Kun læse |
| 84 | BV-084 | System #2 – pH-høj alarm | Kun læse |
| 85 | BV-085 | System #2 – pH lav alarm | Kun læse |
| 86 | BV-086 | System #2 – pH-grænsealarm | Kun læse |
| 87 | BV-087 | System #2 – ORP høj alarm | Kun læse |
| 88 | BV-088 | System #2 – ORP lav alarm | Kun læse |
| 89 | BV-089 | System #2 – ORP-grænsealarm | Kun læse |
| 90 | BV-090 | System #2 – S. Høj temperatur alarm | Kun læse |
| 91 | BV-091 | System #2 – S. Lav temperatur alarm | Kun læse |
| 92 | BV-092 | System #2 – M. Temperatur høj alarm | Kun læse |
| 93 | BV-093 | System #2 – M. Lav temperatur alarm | Kun læse |
| 94 | BV-094 | System #2 – D. Høj temperatur alarm | Kun læse |
| 95 | BV-095 | System #2 – D. Lav temperatur alarm | Kun læse |
| 96 | BV-096 | System #2 – Ingen flowalarm | Kun læse |
| 97 | BV-097 | System #2 – Digital Input 1 Alarm | Kun læse |
| 98 | BV-098 | System #2 – Digital Input 2 Alarm | Kun læse |
| 99 | BV-099 | System #2 – Digital Input 3 Alarm | Kun læse |
| 100 | BV-100 | System #2 – Digital Input 4 Alarm | Kun læse |
| 101 | BV-101 | System #2 – Digital Input 5 Alarm | Kun læse |
| 103 | BV-103 | System #2 – M. Konduktivitet høj alarm | Kun læse |
| 104 | BV-104 | System #2 – M. Alarm for lav ledningsevne | Kun læse |
| 105 | BV-105 | System #2 – M. Alarm for ledningsevnegrænse | Kun læse |
| 106 | BV-106 | System #2 – Notesblok 1 Høj alarm | Kun læse |
| 107 | BV-107 | System #2 – Notesblok 2 Høj alarm | Kun læse |
| 108 | BV-108 | System #2 – Notesblok 3 Høj alarm | Kun læse |
| 109 | BV-109 | System #2 – Notesblok 4 Høj alarm | Kun læse |
| 110 | BV-110 | System #2 – Notesblok 5 Høj alarm | Kun læse |
| 111 | BV-111 | System #2 – Notesblok 6 Høj alarm | Kun læse |
| 112 | BV-112 | System #2 – Notesblok 7 Høj alarm | Kun læse |
| 113 | BV-113 | System #2 – Notesblok 8 Høj alarm | Kun læse |
| 114 | BV-114 | System #2 – Notesblok 9 Høj alarm | Kun læse |
| 115 | BV-115 | System #2 – Notesblok 10 Høj alarm | Kun læse |
| 116 | BV-116 | System #2 – Notesblok 1 lav alarm | Kun læse |
| 117 | BV-117 | System #2 – Notesblok 2 lav alarm | Kun læse |
| 118 | BV-118 | System #2 – Notesblok 3 lav alarm | Kun læse |
| 119 | BV-119 | System #2 – Notesblok 4 lav alarm | Kun læse |
| 120 | BV-120 | System #2 – Notesblok 5 lav alarm | Kun læse |
| 121 | BV-121 | System #2 – Notesblok 6 lav alarm | Kun læse |
| 122 | BV-122 | System #2 – Notesblok 7 lav alarm | Kun læse |
| 123 | BV-123 | System #2 – Notesblok 8 lav alarm | Kun læse |
| 124 | BV-124 | System #2 – Notesblok 9 lav alarm | Kun læse |
| 125 | BV-125 | System #2 – Notesblok 10 lav alarm | Kun læse |
| 126 | BV-126 | System #2 – Notesblok 1 Tidsalarm | Kun læse |
| 127 | BV-127 | System #2 – Notesblok 2 Tidsalarm | Kun læse |
| 128 | BV-128 | System #2 – Notesblok 3 Tidsalarm | Kun læse |
| 129 | BV-129 | System #2 – Notesblok 4 Tidsalarm | Kun læse |
| 130 | BV-130 | System #2 – Notesblok 5 Tidsalarm | Kun læse |
| 131 | BV-131 | System #2 – Notesblok 6 Tidsalarm | Kun læse |
| 132 | BV-132 | System #2 – Notesblok 7 Tidsalarm | Kun læse |
| 133 | BV-133 | System #2 – Notesblok 8 Tidsalarm | Kun læse |
| 134 | BV-134 | System #2 – Notesblok 9 Tidsalarm | Kun læse |
| 135 | BV-135 | System #2 – Notesblok 10 Tidsalarm | Kun læse |
| 150 | BV-150 | System #3 – Konduktivitet høj alarm | Kun læse |
| 151 | BV-151 | System #3 – Alarm for lav ledningsevne | Kun læse |
| 152 | BV-152 | System #3 – Alarm for ledningsevnegrænse | Kun læse |
| 153 | BV-153 | System #3 – pH-høj alarm | Kun læse |
| 154 | BV-154 | System #3 – pH lav alarm | Kun læse |
| 155 | BV-155 | System #3 – pH-grænsealarm | Kun læse |
| 156 | BV-156 | System #3 – ORP høj alarm | Kun læse |
| 157 | BV-157 | System #3 – ORP lav alarm | Kun læse |
| 158 | BV-158 | System #3 – ORP-grænsealarm | Kun læse |
| 159 | BV-159 | System #3 – S. Høj temperatur alarm | Kun læse |
| 160 | BV-160 | System #3 – S. Lav temperatur alarm | Kun læse |
| 161 | BV-161 | System #3 – M. Temperatur høj alarm | Kun læse |
| 162 | BV-162 | System #3 – M. Lav temperatur alarm | Kun læse |
| 163 | BV-163 | System #3 – D. Høj temperatur alarm | Kun læse |
| 164 | BV-164 | System #3 – D. Lav temperatur alarm | Kun læse |
| 165 | BV-165 | System #3 – Ingen flowalarm | Kun læse |
| 166 | BV-166 | System #3 – Digital Input 1 Alarm | Kun læse |
| 167 | BV-167 | System #3 – Digital Input 2 Alarm | Kun læse |
| 168 | BV-168 | System #3 – Digital Input 3 Alarm | Kun læse |
| 169 | BV-169 | System #3 – Digital Input 4 Alarm | Kun læse |
| 170 | BV-170 | System #3 – Digital Input 5 Alarm | Kun læse |
| 172 | BV-172 | System #3 – M. Konduktivitet høj alarm | Kun læse |
| 173 | BV-173 | System #3 – M. Alarm for lav ledningsevne | Kun læse |
| 174 | BV-174 | System #3 – M. Alarm for ledningsevnegrænse | Kun læse |
| 175 | BV-175 | System #3 – Notesblok 1 Høj alarm | Kun læse |
| 176 | BV-176 | System #3 – Notesblok 2 Høj alarm | Kun læse |
| 177 | BV-177 | System #3 – Notesblok 3 Høj alarm | Kun læse |
| 178 | BV-178 | System #3 – Notesblok 4 Høj alarm | Kun læse |
| 179 | BV-179 | System #3 – Notesblok 5 Høj alarm | Kun læse |
| 180 | BV-180 | System #3 – Notesblok 6 Høj alarm | Kun læse |
| 181 | BV-181 | System #3 – Notesblok 7 Høj alarm | Kun læse |
| 182 | BV-182 | System #3 – Notesblok 8 Høj alarm | Kun læse |
| 183 | BV-183 | System #3 – Notesblok 9 Høj alarm | Kun læse |
| 184 | BV-184 | System #3 – Notesblok 10 Høj alarm | Kun læse |
| 185 | BV-185 | System #3 – Notesblok 1 lav alarm | Kun læse |
| 186 | BV-186 | System #3 – Notesblok 2 lav alarm | Kun læse |
| 187 | BV-187 | System #3 – Notesblok 3 lav alarm | Kun læse |
| 188 | BV-188 | System #3 – Notesblok 4 lav alarm | Kun læse |
| 189 | BV-189 | System #3 – Notesblok 5 lav alarm | Kun læse |
| 190 | BV-190 | System #3 – Notesblok 6 lav alarm | Kun læse |
| 191 | BV-191 | System #3 – Notesblok 7 lav alarm | Kun læse |
| 192 | BV-192 | System #3 – Notesblok 8 lav alarm | Kun læse |
| 193 | BV-193 | System #3 – Notesblok 9 lav alarm | Kun læse |
| 194 | BV-194 | System #3 – Notesblok 10 lav alarm | Kun læse |
| 195 | BV-195 | System #3 – Notesblok 1 Tidsalarm | Kun læse |
| 196 | BV-196 | System #3 – Notesblok 2 Tidsalarm | Kun læse |
| 197 | BV-197 | System #3 – Notesblok 3 Tidsalarm | Kun læse |
| 198 | BV-198 | System #3 – Notesblok 4 Tidsalarm | Kun læse |
| 199 | BV-199 | System #3 – Notesblok 5 Tidsalarm | Kun læse |
| 200 | BV-200 | System #3 – Notesblok 6 Tidsalarm | Kun læse |
| 201 | BV-201 | System #3 – Notesblok 7 Tidsalarm | Kun læse |
| 202 | BV-202 | System #3 – Notesblok 8 Tidsalarm | Kun læse |
| 203 | BV-203 | System #3 – Notesblok 9 Tidsalarm | Kun læse |
| 204 | BV-204 | System #3 – Notesblok 10 Tidsalarm | Kun læse |
| 219 | BV-219 | System #4 – Konduktivitet høj alarm | Kun læse |
| 220 | BV-220 | System #4 – Alarm for lav ledningsevne | Kun læse |
| 221 | BV-221 | System #4 – Alarm for ledningsevnegrænse | Kun læse |
| 222 | BV-222 | System #4 – pH-høj alarm | Kun læse |
| 223 | BV-223 | System #4 – pH lav alarm | Kun læse |
| 224 | BV-224 | System #4 – pH-grænsealarm | Kun læse |
| 225 | BV-225 | System #4 – ORP høj alarm | Kun læse |
| 226 | BV-226 | System #4 – ORP lav alarm | Kun læse |
| 227 | BV-227 | System #4 – ORP-grænsealarm | Kun læse |
| 228 | BV-228 | System #4 – S. Høj temperatur alarm | Kun læse |
| 229 | BV-229 | System #4 – S. Lav temperatur alarm | Kun læse |
| 230 | BV-230 | System #4 – M. Temperatur høj alarm | Kun læse |
| 231 | BV-231 | System #4 – M. Lav temperatur alarm | Kun læse |
| 232 | BV-232 | System #4 – D. Høj temperatur alarm | Kun læse |
| 233 | BV-233 | System #4 – D. Lav temperatur alarm | Kun læse |
| 234 | BV-234 | System #4 – Ingen flowalarm | Kun læse |
| 235 | BV-235 | System #4 – Digital Input 1 Alarm | Kun læse |
| 236 | BV-236 | System #4 – Digital Input 2 Alarm | Kun læse |
| 237 | BV-237 | System #4 – Digital Input 3 Alarm | Kun læse |
| 238 | BV-238 | System #4 – Digital Input 4 Alarm | Kun læse |
| 239 | BV-239 | System #4 – Digital Input 5 Alarm | Kun læse |
| 241 | BV-241 | System #4 – M. Konduktivitet høj alarm | Kun læse |
| 242 | BV-242 | System #4 – M. Alarm for lav ledningsevne | Kun læse |
| 243 | BV-243 | System #4 – M. Alarm for ledningsevnegrænse | Kun læse |
| 244 | BV-244 | System #4 – Notesblok 1 Høj alarm | Kun læse |
| 245 | BV-245 | System #4 – Notesblok 2 Høj alarm | Kun læse |
| 246 | BV-246 | System #4 – Notesblok 3 Høj alarm | Kun læse |
| 247 | BV-247 | System #4 – Notesblok 4 Høj alarm | Kun læse |
| 248 | BV-248 | System #4 – Notesblok 5 Høj alarm | Kun læse |
| 249 | BV-249 | System #4 – Notesblok 6 Høj alarm | Kun læse |
| 250 | BV-250 | System #4 – Notesblok 7 Høj alarm | Kun læse |
| 251 | BV-251 | System #4 – Notesblok 8 Høj alarm | Kun læse |
| 252 | BV-252 | System #4 – Notesblok 9 Høj alarm | Kun læse |
| 253 | BV-253 | System #4 – Notesblok 10 Høj alarm | Kun læse |
| 254 | BV-254 | System #4 – Notesblok 1 lav alarm | Kun læse |
| 255 | BV-255 | System #4 – Notesblok 2 lav alarm | Kun læse |
| 256 | BV-256 | System #4 – Notesblok 3 lav alarm | Kun læse |
| 257 | BV-257 | System #4 – Notesblok 4 lav alarm | Kun læse |
| 258 | BV-258 | System #4 – Notesblok 5 lav alarm | Kun læse |
| 259 | BV-259 | System #4 – Notesblok 6 lav alarm | Kun læse |
| 260 | BV-260 | System #4 – Notesblok 7 lav alarm | Kun læse |
| 261 | BV-261 | System #4 – Notesblok 8 lav alarm | Kun læse |
| 262 | BV-262 | System #4 – Notesblok 9 lav alarm | Kun læse |
| 263 | BV-263 | System #4 – Notesblok 10 lav alarm | Kun læse |
| 264 | BV-264 | System #4 – Notesblok 1 Tidsalarm | Kun læse |
| 265 | BV-265 | System #4 – Notesblok 2 Tidsalarm | Kun læse |
| 266 | BV-266 | System #4 – Notesblok 3 Tidsalarm | Kun læse |
| 267 | BV-267 | System #4 – Notesblok 4 Tidsalarm | Kun læse |
| 268 | BV-268 | System #4 – Notesblok 5 Tidsalarm | Kun læse |
| 269 | BV-269 | System #4 – Notesblok 6 Tidsalarm | Kun læse |
| 270 | BV-270 | System #4 – Notesblok 7 Tidsalarm | Kun læse |
| 271 | BV-271 | System #4 – Notesblok 8 Tidsalarm | Kun læse |
| 272 | BV-272 | System #4 – Notesblok 9 Tidsalarm | Kun læse |
| 273 | BV-273 | System #4 – Notesblok 10 Tidsalarm | Kun læse |
| 232 | BV-232 | System #4 – D. Høj temperatur alarm | Kun læse |
| 233 | BV-233 | System #4 – D. Lav temperatur alarm | Kun læse |
| 234 | BV-234 | System #4 – Ingen flowalarm | Kun læse |
| 235 | BV-235 | System #4 – Digital Input 1 Alarm | Kun læse |
| 236 | BV-236 | System #4 – Digital Input 2 Alarm | Kun læse |
| 237 | BV-237 | System #4 – Digital Input 3 Alarm | Kun læse |
| 238 | BV-238 | System #4 – Digital Input 4 Alarm | Kun læse |
| 239 | BV-239 | System #4 – Digital Input 5 Alarm | Kun læse |
| 241 | BV-241 | System #4 – M. Konduktivitet høj alarm | Kun læse |
| 242 | BV-242 | System #4 – M. Alarm for lav ledningsevne | Kun læse |
| 243 | BV-243 | System #4 – M. Alarm for ledningsevnegrænse | Kun læse |
| 244 | BV-244 | System #4 – Notesblok 1 Høj alarm | Kun læse |
| 245 | BV-245 | System #4 – Notesblok 2 Høj alarm | Kun læse |
| 246 | BV-246 | System #4 – Notesblok 3 Høj alarm | Kun læse |
| 247 | BV-247 | System #4 – Notesblok 4 Høj alarm | Kun læse |
| 248 | BV-248 | System #4 – Notesblok 5 Høj alarm | Kun læse |
| 249 | BV-249 | System #4 – Notesblok 6 Høj alarm | Kun læse |
| 250 | BV-250 | System #4 – Notesblok 7 Høj alarm | Kun læse |
| 251 | BV-251 | System #4 – Notesblok 8 Høj alarm | Kun læse |
| 252 | BV-252 | System #4 – Notesblok 9 Høj alarm | Kun læse |
| 253 | BV-253 | System #4 – Notesblok 10 Høj alarm | Kun læse |
| 254 | BV-254 | System #4 – Notesblok 1 lav alarm | Kun læse |
| 255 | BV-255 | System #4 – Notesblok 2 lav alarm | Kun læse |
| 256 | BV-256 | System #4 – Notesblok 3 lav alarm | Kun læse |
| 257 | BV-257 | System #4 – Notesblok 4 lav alarm | Kun læse |
| 258 | BV-258 | System #4 – Notesblok 5 lav alarm | Kun læse |
| 259 | BV-259 | System #4 – Notesblok 6 lav alarm | Kun læse |
| 260 | BV-260 | System #4 – Notesblok 7 lav alarm | Kun læse |
| 261 | BV-261 | System #4 – Notesblok 8 lav alarm | Kun læse |
| 262 | BV-262 | System #4 – Notesblok 9 lav alarm | Kun læse |
| 263 | BV-263 | System #4 – Notesblok 10 lav alarm | Kun læse |
| 264 | BV-264 | System #4 – Notesblok 1 Tidsalarm | Kun læse |
| 265 | BV-265 | System #4 – Notesblok 2 Tidsalarm | Kun læse |
| 266 | BV-266 | System #4 – Notesblok 3 Tidsalarm | Kun læse |
| 267 | BV-267 | System #4 – Notesblok 4 Tidsalarm | Kun læse |
| 268 | BV-268 | System #4 – Notesblok 5 Tidsalarm | Kun læse |
| 269 | BV-269 | System #4 – Notesblok 6 Tidsalarm | Kun læse |
| 270 | BV-270 | System #4 – Notesblok 7 Tidsalarm | Kun læse |
| 271 | BV-271 | System #4 – Notesblok 8 Tidsalarm | Kun læse |
| 272 | BV-272 | System #4 – Notesblok 9 Tidsalarm | Kun læse |
| 273 | BV-273 | System #4 – Notesblok 10 Tidsalarm | Kun læse |
| 277 | BV-277 | ma Indgang 1 Høj alarm | Kun læse |
| 278 | BV-278 | ma Indgang 1 Lav alarm | Kun læse |
| 280 | BV-280 | ma Indgang 2 Høj alarm | Kun læse |
| 281 | BV-281 | ma Indgang 2 Lav alarm | Kun læse |
| 283 | BV-283 | ma Indgang 3 Høj alarm | Kun læse |
| 284 | BV-284 | ma Indgang 3 Lav alarm | Kun læse |
| 286 | BV-286 | ma Indgang 4 Høj alarm | Kun læse |
| 287 | BV-287 | ma Indgang 4 Lav alarm | Kun læse |
| 289 | BV-289 | ma Indgang 5 Høj alarm | Kun læse |
| 290 | BV-290 | ma Indgang 5 Lav alarm | Kun læse |
| 292 | BV-292 | ma Indgang 6 Høj alarm | Kun læse |
| 293 | BV-293 | ma Indgang 6 Lav alarm | Kun læse |
| 295 | BV-295 | ma Indgang 7 Høj alarm | Kun læse |
| 296 | BV-296 | ma Indgang 7 Lav alarm | Kun læse |
| 298 | BV-298 | ma Indgang 8 Høj alarm | Kun læse |
| 299 | BV-299 | ma Indgang 8 Lav alarm | Kun læse |
| 302 | BV-302 | Flowmåler 1 Flowalarm | Kun læse |
| 303 | BV-303 | Flowmåler 1 Flowbekræftelsesalarm | Kun læse |
| 304 | BV-304 | Flowmåler 1 Volumenalarm | Kun læse |
| 305 | BV-305 | Flowmåler 2 Flowalarm | Kun læse |
| 306 | BV-306 | Flowmåler 2 Flowbekræftelsesalarm | Kun læse |
| 307 | BV-307 | Flowmåler 2 Volumenalarm | Kun læse |
| 308 | BV-308 | Flowmåler 3 Flowalarm | Kun læse |
| 309 | BV-309 | Flowmåler 3 Flowbekræftelsesalarm | Kun læse |
| 310 | BV-310 | Flowmåler 3 Volumenalarm | Kun læse |
| 311 | BV-311 | Flowmåler 4 Flowalarm | Kun læse |
| 312 | BV-312 | Flowmåler 4 Flowbekræftelsesalarm | Kun læse |
| 313 | BV-313 | Flowmåler 4 Volumenalarm | Kun læse |
| 314 | BV-314 | Flowmåler 5 Flowalarm | Kun læse |
| 315 | BV-315 | Flowmåler 5 Flowbekræftelsesalarm | Kun læse |
| 316 | BV-316 | Flowmåler 5 Volumenalarm | Kun læse |
| 317 | BV-317 | Flowmåler 6 Flowalarm | Kun læse |
| 318 | BV-318 | Flowmåler 6 Flowbekræftelsesalarm | Kun læse |
| 319 | BV-319 | Flowmåler 6 Volumenalarm | Kun læse |
| 320 | BV-320 | Flowmåler 7 Flowalarm | Kun læse |
| 321 | BV-321 | Flowmåler 7 Flowbekræftelsesalarm | Kun læse |
| 322 | BV-322 | Flowmåler 7 Volumenalarm | Kun læse |
| 323 | BV-323 | Flowmåler 8 Flowalarm | Kun læse |
| 324 | BV-324 | Flowmåler 8 Flowbekræftelsesalarm | Kun læse |
| 325 | BV-325 | Flowmåler 8 Volumenalarm | Kun læse |
| 326 | BV-326 | Flowmåler 9 Flowalarm | Kun læse |
| 327 | BV-327 | Flowmåler 9 Flowbekræftelsesalarm | Kun læse |
| 328 | BV-328 | Flowmåler 9 Volumenalarm | Kun læse |
| 329 | BV-329 | Flowmåler 10 Flowalarm | Kun læse |
| 330 | BV-330 | Flowmåler 10 Flowbekræft | Kun læse |
| 331 | BV-331 | Flowmåler 10 Volumenalarm | Kun læse |
| 332 | BV-332 | Relæ 1 Max timer | Kun læse |
| 333 | BV-333 | Relæ 2 Max timer | Kun læse |
| 334 | BV-334 | Relæ 3 Max timer | Kun læse |
| 335 | BV-335 | Relæ 4 Max timer | Kun læse |
| 336 | BV-336 | Relæ 5 Max timer | Kun læse |
| 337 | BV-337 | Relæ 6 Max timer | Kun læse |
| 338 | BV-338 | Relæ 7 Max timer | Kun læse |
| 339 | BV-339 | Relæ 8 Max timer | Kun læse |
| 340 | BV-340 | Relæ 9 Max timer | Kun læse |
| 341 | BV-341 | Relæ 10 Max timer | Kun læse |
| 342 | BV-342 | Relæ 11 Max timer | Kun læse |
| 343 | BV-343 | Relæ 12 Max timer | Kun læse |
| 344 | BV-344 | Relæ 13 Max timer | Kun læse |
| 345 | BV-345 | Relæ 14 Max timer | Kun læse |
| 346 | BV-346 | Relæ 15 Max timer | Kun læse |
| 347 | BV-347 | Relæ 16 Max timer | Kun læse |
| 348 | BV-348 | Relæ 17 Max timer | Kun læse |
| 349 | BV-349 | Relæ 18 Max timer | Kun læse |
| 350 | BV-350 | Relæ 19 Max timer | Kun læse |
| 351 | BV-351 | Relæ 20 Max timer | Kun læse |
| 352 | BV-352 | mA-indgang 1-grænse | Kun læse |
| 353 | BV-353 | mA-indgang 2-grænse | Kun læse |
| 354 | BV-354 | mA-indgang 3-grænse | Kun læse |
| 355 | BV-355 | mA-indgang 4-grænse | Kun læse |
| 356 | BV-356 | mA-indgang 5-grænse | Kun læse |
| 357 | BV-357 | mA-indgang 6-grænse | Kun læse |
| 358 | BV-358 | mA-indgang 7-grænse | Kun læse |
| 359 | BV-359 | mA-indgang 8-grænse | Kun læse |
| 360 | BV-360 | mA-indgang 9 Grænsealarm | Kun læse |
| 361 | BV-361 | mA-indgang 10 Grænsealarm | Kun læse |
| 362 | BV-362 | mA-indgang 11 Grænsealarm | Kun læse |
| 363 | BV-363 | mA-indgang 12 Grænsealarm | Kun læse |
| 364 | BV-364 | mA-indgang 13 Grænsealarm | Kun læse |
| 365 | BV-365 | mA-indgang 14 Grænsealarm | Kun læse |
| 366 | BV-366 | mA-indgang 15 Grænsealarm | Kun læse |
| 367 | BV-367 | mA-indgang 16 Grænsealarm | Kun læse |
| 369 | BV-369 | ma Indgang 9 Høj alarm | Kun læse |
| 370 | BV-370 | ma Indgang 9 Lav alarm | Kun læse |
| 372 | BV-372 | ma Indgang 10 Høj alarm | Kun læse |
| 373 | BV-373 | ma Indgang 10 Lav alarm | Kun læse |
| 375 | BV-375 | ma Indgang 11 Høj alarm | Kun læse |
| 376 | BV-376 | ma Indgang 11 Lav alarm | Kun læse |
| 378 | BV-378 | ma Indgang 12 Høj alarm | Kun læse |
| 379 | BV-379 | ma Indgang 12 Lav alarm | Kun læse |
| 381 | BV-381 | ma Indgang 13 Høj alarm | Kun læse |
| 382 | BV-382 | ma Indgang 13 Lav alarm | Kun læse |
| 384 | BV-384 | ma Indgang 14 Høj alarm | Kun læse |
| 385 | BV-385 | ma Indgang 14 Lav alarm | Kun læse |
| 387 | BV-387 | ma Indgang 15 Høj alarm | Kun læse |
| 388 | BV-388 | ma Indgang 15 Lav alarm | Kun læse |
| 390 | BV-390 | ma Indgang 16 Høj alarm | Kun læse |
| 391 | BV-391 | ma Indgang 16 Lav alarm | Kun læse |
Oversigt over analog inputobjektforekomst (tabel 1-4)
| Forekomst-id | Objektnavn | Formål | Nutidsværdi – Adgang |
| 0 | AI-000 | System #1 – Ledningsevne | Kun læse |
| 1 | AI-001 | System #2 – Ledningsevne | Kun læse |
| 2 | AI-002 | System #3 – Ledningsevne | Kun læse |
| 3 | AI-003 | System #4 – Ledningsevne | Kun læse |
| 4 | AI-004 | System #1 – M. Ledningsevne | Kun læse |
| 5 | AI-005 | System #2 – M. Ledningsevne | Kun læse |
| 6 | AI-006 | System #3 – M. Ledningsevne | Kun læse |
| 7 | AI-007 | System #4 – M. Ledningsevne | Kun læse |
| 8 | AI-008 | System #1 – pH | Kun læse |
| 9 | AI-009 | System #2 – pH | Kun læse |
| 10 | AI-010 | System #3 – pH | Kun læse |
| 11 | AI-011 | System #4 – pH | Kun læse |
| 12 | AI-012 | System #1 – ORP | Kun læse |
| 13 | AI-013 | System #2 – ORP | Kun læse |
| 14 | AI-014 | System #3 – ORP | Kun læse |
| 15 | AI-015 | System #4 – ORP | Kun læse |
| 16 | AI-016 | System #1 – S. Temp | Kun læse |
| 17 | AI-017 | System #2 – S. Temp | Kun læse |
| 18 | AI-018 | System #3 – S. Temp | Kun læse |
| 19 | AI-019 | System #4 – S. Temp | Kun læse |
| 20 | AI-020 | System #1 – M. Temp | Kun læse |
| 21 | AI-021 | System #2 – M. Temp | Kun læse |
| 22 | AI-022 | System #3 – M. Temp | Kun læse |
| 23 | AI-023 | System #4 – M. Temp | Kun læse |
| 24 | AI-024 | Sys #1 – Vandmåler #1 – Samlet værdi | Kun læse |
| 25 | AI-025 | Sys #2 – Vandmåler #1 – Samlet værdi | Kun læse |
| 26 | AI-026 | Sys #3 – Vandmåler #1 – Samlet værdi | Kun læse |
| 27 | AI-027 | Sys #4 – Vandmåler #1 – Samlet værdi | Kun læse |
| 28 | AI-028 | Sys #1 – Vandmåler #2 – Samlet værdi | Kun læse |
| 29 | AI-029 | Sys #2 – Vandmåler #2 – Samlet værdi | Kun læse |
| 30 | AI-030 | Sys #3 – Vandmåler #2 – Samlet værdi | Kun læse |
| 31 | AI-031 | Sys #4 – Vandmåler #2 – Samlet værdi | Kun læse |
| 32 | AI-032 | System #1 – M.Cycles | Kun læse |
| 33 | AI-033 | System #2 – M.Cycles | Kun læse |
| 34 | AI-034 | System #3 – M.Cycles | Kun læse |
| 35 | AI-035 | System #4 – M.Cycles | Kun læse |
| 36 | AI-036 | 4-20 mA / 0-5V Indgang #1 – Værdi | Kun læse |
| 37 | AI-037 | 4-20 mA / 0-5V Indgang #2 – Værdi | Kun læse |
| 38 | AI-038 | 4-20 mA / 0-5V Indgang #3 – Værdi | Kun læse |
| 39 | AI-039 | 4-20 mA / 0-5V Indgang #4 – Værdi | Kun læse |
| 40 | AI-040 | 4-20 mA / 0-5V Indgang #5 – Værdi | Kun læse |
| 41 | AI-041 | 4-20 mA / 0-5V Indgang #6 – Værdi | Kun læse |
| 42 | AI-042 | 4-20 mA / 0-5V Indgang #7 – Værdi | Kun læse |
| 43 | AI-043 | 4-20 mA / 0-5V Indgang #8 – Værdi | Kun læse |
| 44 | AI-044 | Flowmåler #1 – Kontaktværdi | Kun læse |
| 45 | AI-045 | Flowmåler #2 – Kontaktværdi | Kun læse |
| 46 | AI-046 | Flowmåler #3 – Kontaktværdi | Kun læse |
| 47 | AI-047 | Flowmåler #4 – Kontaktværdi | Kun læse |
| 48 | AI-048 | Flowmåler #5 – Kontaktværdi | Kun læse |
| 49 | AI-049 | Flowmåler #6 – Kontaktværdi | Kun læse |
| 50 | AI-050 | Flowmåler #7 – Kontaktværdi | Kun læse |
| 51 | AI-051 | Flowmåler #8 – Kontaktværdi | Kun læse |
| 52 | AI-052 | Flowmåler #9 – Kontaktværdi | Kun læse |
| 53 | AI-053 | Flowmåler #10 – Kontaktværdi | Kun læse |
| 54 | AI-054 | Flowmåler #1 – Flowhastighed (pr. MIN.) | Kun læse |
| 55 | AI-055 | Flowmåler #2 – Flowhastighed (pr. MIN.) | Kun læse |
| 56 | AI-056 | Flowmåler #3 – Flowhastighed (pr. MIN.) | Kun læse |
| 57 | AI-057 | Flowmåler #4 – Flowhastighed (pr. MIN.) | Kun læse |
| 58 | AI-058 | Flowmåler #5 – Flowhastighed (pr. MIN.) | Kun læse |
| 59 | AI-059 | Flowmåler #6 – Flowhastighed (pr. MIN.) | Kun læse |
| 60 | AI-060 | Flowmåler #7 – Flowhastighed (pr. MIN.) | Kun læse |
| 61 | AI-061 | Flowmåler #8 – Flowhastighed (pr. MIN.) | Kun læse |
| 62 | AI-062 | Flowmåler #9 – Flowhastighed (pr. MIN.) | Kun læse |
| 63 | AI-063 | Flowmåler #10 – Flowhastighed (pr. MIN.) | Kun læse |
| 64 | AI-064 | 4-20 mA / 0-5V Indgang #9 – Værdi | Kun læse |
| 65 | AI-065 | 4-20 mA / 0-5V Indgang #10 – Værdi | Kun læse |
| 66 | AI-066 | 4-20 mA / 0-5V Indgang #11 – Værdi | Kun læse |
| 67 | AI-067 | 4-20 mA / 0-5V Indgang #12 – Værdi | Kun læse |
| 68 | AI-068 | 4-20 mA / 0-5V Indgang #13 – Værdi | Kun læse |
| 69 | AI-069 | 4-20 mA / 0-5V Indgang #14 – Værdi | Kun læse |
| 70 | AI-070 | 4-20 mA / 0-5V Indgang #15 – Værdi | Kun læse |
| 71 | AI-071 | 4-20 mA / 0-5V Indgang #16 – Værdi | Kun læse |
Resume af analog værdiobjektforekomst (tabel 1-5)
| Forekomst-id | Objektnavn | Formål | Nutidsværdi – Adgang |
| 0 | AV-000 | System #1 – Konduktivitetsindstillingspunkt #1 | Læs/skriv |
| 1 | AV-001 | System #2 – Konduktivitetsindstillingspunkt #1 | Læs/skriv |
| 2 | AV-002 | System #3 – Konduktivitetsindstillingspunkt #1 | Læs/skriv |
| 3 | AV-003 | System #4 – Konduktivitetsindstillingspunkt #1 | Læs/skriv |
| 4 | AV-004 | System #1 – Konduktivitetsindstillingspunkt #2 | Læs/skriv |
| 5 | AV-005 | System #2 – Konduktivitetsindstillingspunkt #2 | Læs/skriv |
| 6 | AV-006 | System #3 – Konduktivitetsindstillingspunkt #2 | Læs/skriv |
| 7 | AV-007 | System #4 – Konduktivitetsindstillingspunkt #2 | Læs/skriv |
| 8 | AV-008 | System #1 – Konduktivitet høj alarm | Læs/skriv |
| 9 | AV-009 | System #2 – Konduktivitet høj alarm | Læs/skriv |
| 10 | AV-010 | System #3 – Konduktivitet høj alarm | Læs/skriv |
| 11 | AV-011 | System #4 – Konduktivitet høj alarm | Læs/skriv |
| 12 | AV-012 | System #1 – Alarm for lav ledningsevne | Læs/skriv |
| 13 | AV-013 | System #2 – Alarm for lav ledningsevne | Læs/skriv |
| 14 | AV-014 | System #3 – Alarm for lav ledningsevne | Læs/skriv |
| 15 | AV-015 | System #4 – Alarm for lav ledningsevne | Læs/skriv |
| 16 | AV-016 | System #1 – M. Konduktivitetsindstillingspunkt | Læs/skriv |
| 17 | AV-017 | System #2 – M. Konduktivitetsindstillingspunkt | Læs/skriv |
| 18 | AV-018 | System #3 – M. Konduktivitetsindstillingspunkt | Læs/skriv |
| 19 | AV-019 | System #4 – M. Konduktivitetsindstillingspunkt | Læs/skriv |
| 20 | AV-020 | System #1 – M. Konduktivitet høj alarm | Læs/skriv |
| 21 | AV-021 | System #2 – M. Konduktivitet høj alarm | Læs/skriv |
| 22 | AV-022 | System #3 – M. Konduktivitet høj alarm | Læs/skriv |
| 23 | AV-023 | System #4 – M. Konduktivitet høj alarm | Læs/skriv |
| 24 | AV-024 | System #1 – M. Alarm for lav ledningsevne | Læs/skriv |
| 25 | AV-025 | System #2 – M. Alarm for lav ledningsevne | Læs/skriv |
| 26 | AV-026 | System #3 – M. Alarm for lav ledningsevne | Læs/skriv |
| 27 | AV-027 | System #4 – M. Alarm for lav ledningsevne | Læs/skriv |
| 28 | AV-028 | System #1 – pH-indstillingspunkt #1 | Læs/skriv |
| 29 | AV-029 | System #2 – pH-indstillingspunkt #1 | Læs/skriv |
| 30 | AV-030 | System #3 – pH-indstillingspunkt #1 | Læs/skriv |
| 31 | AV-031 | System #4 – pH-indstillingspunkt #1 | Læs/skriv |
| 32 | AV-032 | System #1 – pH-indstillingspunkt #2 | Læs/skriv |
| 33 | AV-033 | System #2 – pH-indstillingspunkt #2 | Læs/skriv |
| 34 | AV-034 | System #3 – pH-indstillingspunkt #2 | Læs/skriv |
| 35 | AV-035 | System #4 – pH-indstillingspunkt #2 | Læs/skriv |
| 36 | AV-036 | System #1 – pH-høj alarm | Læs/skriv |
| 37 | AV-037 | System #2 – pH-høj alarm | Læs/skriv |
| 38 | AV-038 | System #3 – pH-høj alarm | Læs/skriv |
| 39 | AV-039 | System #4 – pH-høj alarm | Læs/skriv |
| 40 | AV-040 | System #1 – pH lav alarm | Læs/skriv |
| 41 | AV-041 | System #2 – pH lav alarm | Læs/skriv |
| 42 | AV-042 | System #3 – pH lav alarm | Læs/skriv |
| 43 | AV-043 | System #4 – pH lav alarm | Læs/skriv |
| 44 | AV-044 | System #1 – ORP sætpunkt #1 | Læs/skriv |
| 45 | AV-045 | System #2 – ORP sætpunkt #1 | Læs/skriv |
| 46 | AV-046 | System #3 – ORP sætpunkt #1 | Læs/skriv |
| 47 | AV-047 | System #4 – ORP sætpunkt #1 | Læs/skriv |
| 48 | AV-048 | System #1 – ORP sætpunkt #2 | Læs/skriv |
| 49 | AV-049 | System #2 – ORP sætpunkt #2 | Læs/skriv |
| 50 | AV-050 | System #3 – ORP sætpunkt #2 | Læs/skriv |
| 51 | AV-051 | System #4 – ORP sætpunkt #2 | Læs/skriv |
| 52 | AV-052 | System #1 – ORP høj alarm | Læs/skriv |
| 53 | AV-053 | System #2 – ORP høj alarm | Læs/skriv |
| 54 | AV-054 | System #3 – ORP høj alarm | Læs/skriv |
| 55 | AV-055 | System #4 – ORP høj alarm | Læs/skriv |
| 56 | AV-056 | System #1 – ORP lav alarm | Læs/skriv |
| 57 | AV-057 | System #2 – ORP lav alarm | Læs/skriv |
| 58 | AV-058 | System #3 – ORP lav alarm | Læs/skriv |
| 59 | AV-059 | System #4 – ORP lav alarm | Læs/skriv |
| 60 | AV-060 | System #1 – S. Temp sætpunkt | Læs/skriv |
| 61 | AV-061 | System #2 – S. Temp sætpunkt | Læs/skriv |
| 62 | AV-062 | System #3 – S. Temp sætpunkt | Læs/skriv |
| 63 | AV-063 | System #4 – S. Temp sætpunkt | Læs/skriv |
| 64 | AV-064 | System #1 – S. Høj temperatur alarm | Læs/skriv |
| 65 | AV-065 | System #2 – S. Høj temperatur alarm | Læs/skriv |
| 66 | AV-066 | System #3 – S. Høj temperatur alarm | Læs/skriv |
| 67 | AV-067 | System #4 – S. Høj temperatur alarm | Læs/skriv |
| 68 | AV-068 | System #1 – S. Lav temperatur alarm | Læs/skriv |
| 69 | AV-069 | System #2 – S. Lav temperatur alarm | Læs/skriv |
| 70 | AV-070 | System #3 – S. Lav temperatur alarm | Læs/skriv |
| 71 | AV-071 | System #4 – S. Lav temperatur alarm | Læs/skriv |
| 72 | AV-072 | System #1 – M. Temp sætpunkt | Læs/skriv |
| 73 | AV-073 | System #2 – M. Temp sætpunkt | Læs/skriv |
| 74 | AV-074 | System #3 – M. Temp sætpunkt | Læs/skriv |
| 75 | AV-075 | System #4 – M. Temp sætpunkt | Læs/skriv |
| 76 | AV-076 | System #1 – M. Temperatur høj alarm | Læs/skriv |
| 77 | AV-077 | System #2 – M. Temperatur høj alarm | Læs/skriv |
| 78 | AV-078 | System #3 – M. Temperatur høj alarm | Læs/skriv |
| 79 | AV-079 | System #4 – M. Temperatur høj alarm | Læs/skriv |
| 80 | AV-080 | System #1 – M. Lav temperatur alarm | Læs/skriv |
| 81 | AV-081 | System #2 – M. Lav temperatur alarm | Læs/skriv |
| 82 | AV-082 | System #3 – M. Lav temperatur alarm | Læs/skriv |
| 83 | AV-083 | System #4 – M. Lav temperatur alarm | Læs/skriv |
| 84 | AV-084 | System #1 – D. Temp sætpunkt | Læs/skriv |
| 85 | AV-085 | System #2 – D. Temp sætpunkt | Læs/skriv |
| 86 | AV-086 | System #3 – D. Temp sætpunkt | Læs/skriv |
| 87 | AV-087 | System #4 – D. Temp sætpunkt | Læs/skriv |
| 88 | AV-088 | System #1 – D. Høj temperatur alarm | Læs/skriv |
| 89 | AV-089 | System #2 – D. Høj temperatur alarm | Læs/skriv |
| 90 | AV-090 | System #3 – D. Høj temperatur alarm | Læs/skriv |
| 91 | AV-091 | System #4 – D. Høj temperatur alarm | Læs/skriv |
| 92 | AV-092 | System #1 – D. Lav temperatur alarm | Læs/skriv |
| 93 | AV-093 | System #2 – D. Lav temperatur alarm | Læs/skriv |
| 94 | AV-094 | System #3 – D. Lav temperatur alarm | Læs/skriv |
| 95 | AV-095 | System #4 – D. Lav temperatur alarm | Læs/skriv |
| 96 | AV-096 | System #1 – Flow Switch Conf. | Læs/skriv |
| 97 | AV-097 | System #2 – Flow Switch Conf. | Læs/skriv |
| 98 | AV-098 | System #3 – Flow Switch Conf. | Læs/skriv |
| 99 | AV-099 | System #4 – Flow Switch Conf. | Læs/skriv |
| 100 | AV-100 | mA 1 – Outputværdi | Læs/skriv |
| 101 | AV-101 | mA 2 – Outputværdi | Læs/skriv |
| 102 | AV-102 | mA 3 – Outputværdi | Læs/skriv |
| 103 | AV-103 | mA 4 – Outputværdi | Læs/skriv |
| 104 | AV-104 | mA 5 – Outputværdi | Læs/skriv |
| 105 | AV-105 | mA 6 – Outputværdi | Læs/skriv |
| 106 | AV-106 | System #1 – Timer #1 – Run Time | Læs/skriv |
| 107 | AV-107 | System #1 – Timer #2 – Run Time | Læs/skriv |
| 108 | AV-108 | System #1 – Timer #3 – Run Time | Læs/skriv |
| 109 | AV-109 | System #1 – Timer #4 – Run Time | Læs/skriv |
| 110 | AV-110 | System #1 – Timer #5 – Run Time | Læs/skriv |
| 111 | AV-111 | System #2 – Timer #1 – Run Time | Læs/skriv |
| 112 | AV-112 | System #2 – Timer #2 – Run Time | Læs/skriv |
| 113 | AV-113 | System #2 – Timer #3 – Run Time | Læs/skriv |
| 114 | AV-114 | System #2 – Timer #4 – Run Time | Læs/skriv |
| 115 | AV-115 | System #2 – Timer #5 – Run Time | Læs/skriv |
| 116 | AV-116 | System #3 – Timer #1 – Run Time | Læs/skriv |
| 117 | AV-117 | System #3 – Timer #2 – Run Time | Læs/skriv |
| 118 | AV-118 | System #3 – Timer #3 – Run Time | Læs/skriv |
| 119 | AV-119 | System #3 – Timer #4 – Run Time | Læs/skriv |
| 120 | AV-120 | System #3 – Timer #5 – Run Time | Læs/skriv |
| 121 | AV-121 | System #4 – Timer #1 – Run Time | Læs/skriv |
| 122 | AV-122 | System #4 – Timer #2 – Run Time | Læs/skriv |
| 123 | AV-123 | System #4 – Timer #3 – Run Time | Læs/skriv |
| 124 | AV-124 | System #4 – Timer #4 – Run Time | Læs/skriv |
| 125 | AV-125 | System #4 – Timer #5 – Run Time | Læs/skriv |
| 126 | AV-126 | Skrivebeskyttet tilstand | Kun læse |
Resumé af objektforekomster med flere tilstande (tabel 1-6)
Note #1 1=H-OFF 2=H-ON 3=OFF 4=ON
| Forekomst-id | Objektnavn | Formål | Nutidsværdi – Adgang |
| 0 | MSV-000 | Relæ 1 – Tilstand | Læs/skriv |
| 1 | MSV-001 | Relæ 2 – Tilstand | Læs/skriv |
| 2 | MSV-002 | Relæ 3 – Tilstand | Læs/skriv |
| 3 | MSV-003 | Relæ 4 – Tilstand | Læs/skriv |
| 4 | MSV-004 | Relæ 5 – Tilstand | Læs/skriv |
| 5 | MSV-005 | Relæ 6 – Tilstand | Læs/skriv |
| 6 | MSV-006 | Relæ 7 – Tilstand | Læs/skriv |
| 7 | MSV-007 | Relæ 8 – Tilstand | Læs/skriv |
| 8 | MSV-008 | Relæ 9 – Tilstand | Læs/skriv |
| 9 | MSV-009 | Relæ 10 – Tilstand | Læs/skriv |
| 10 | MSV-010 | Relæ 11 – Tilstand | Læs/skriv |
| 11 | MSV-011 | Relæ 12 – Tilstand | Læs/skriv |
| 12 | MSV-012 | Relæ 13 – Tilstand | Læs/skriv |
| 13 | MSV-013 | Relæ 14 – Tilstand | Læs/skriv |
| 14 | MSV-014 | Relæ 15 – Tilstand | Læs/skriv |
| 15 | MSV-015 | Relæ 16 – Tilstand | Læs/skriv |
| 16 | MSV-016 | Relæ 17 – Tilstand | Læs/skriv |
| 17 | MSV-017 | Relæ 18 – Tilstand | Læs/skriv |
| 18 | MSV-018 | Relæ 19 – Tilstand | Læs/skriv |
| 19 | MSV-019 | Relæ 20 – Tilstand | Læs/skriv |
Hent Advantage i vandbehandlingsudstyr
Advantage Controls can give you the Advantage in products, knowledge and support on all of your water treatment equipment needs.
- Køletårn-controllere
- Kedel Blow Down Controllere
- Blow down ventilpakker
- Magnetventiler
- Vandmålere
- Kemiske målepumper
- Korrosions kupon stativer
- Tanke til kemisk opløsning
- Solid fodersystemer
- Fodertimere
- Filterudstyr
- Glykol fodersystemer
- Præfabrikerede systemer

Fejlfinding
- Setup menu options not visible: The manual notes that if the BAC options are not visible, the “dual network card needs to be enabled.”
- After BACnet reset: The manual instructs that after pressing RESET and accepting with Enter, the communications card will reset after a short countdown, and then you must cycle power til controlleren.
- Network not receiving traffic from MegaTron: The manual states that the Building Management System needs to be on the same subnet to properly receive traffic from the MegaTron, which may require advanced routing or advanced switching equipment programming.
- WebAdvantage connectivity requirements: For WebAdvantage, the manual states that an internet gateway med firewall and security rules in place is required (if you are using WebAdvantage service).
Dokumenter/ressourcer
![]() | Mega Tron controller |
Referencer
- web80.advantagecontrols.comweb80.advantagecontrols.com
- advantagecontrols.comwww.advantagecontrols.com
- Brugermanualmanual.tools