EARU EARU-1008

EARU Electric 440V 63A 3-Phase Voltage and Overcurrent Protector Instruction Manual

Model: EARU-1008

1. Introduktion

This manual provides comprehensive instructions for the installation, operation, and maintenance of the EARU Electric 3-Phase Voltage and Overcurrent Protector, Model EARU-1008. This device is designed to safeguard 3-phase electrical systems by continuously monitoring voltage and current, offering protection against over-voltage, under-bindtage, overcurrent, and phase failure. It is suitable for industrial and commercial applications requiring reliable electrical monitoring and protection.

2. Sikkerhedsoplysninger

ADVARSEL: Fare for elektrisk stød. Installation og vedligeholdelse bør kun udføres af kvalificeret personale.

  • Afbryd altid strømmen, før du installerer eller servicerer enheden.
  • Sørg for korrekt jording for at forhindre elektrisk stød.
  • Kontroller, at alle ledningsforbindelser er sikre og korrekte i henhold til ledningsdiagrammet.
  • Brug ikke enheden, hvis den ser ud til at være beskadiget.
  • Overhold alle lokale og nationale elektriske regler.

3. Produktet er slutview

3.1. Nøglefunktioner

  • Real-time 3-Phase Monitoring: Displays live voltage (L1, L2, L3) and current (L1, L2, L3) values.
  • Omfattende beskyttelse: Safeguards against over-voltage, under-bindtage, overcurrent, and phase failure.
  • Justerbare parametre: User-configurable settings for protection thresholds and recovery delays.
  • Automatic Phase Failure Reset: Detects and automatically resets after phase anomalies.
  • High-Visibility LED Display: Bright red LED for clear readings in various lighting conditions.
  • DIN-skinnemontering: Easy integration into standard electrical panels.
  • Clear Terminal Labeling: Simplified installation with clearly marked input and output terminals.

3.2. Komponenter og display

The device features a clear LED display and intuitive control buttons for configuration. The display shows real-time voltage and current for each phase, along with indicators for protection status.

EARU Electric Voltage Protector Display and Controls

Billede 3.2.1: Front view of the EARU Electric Voltage Protector, showing the LED display for L1, L2, L3 voltage and current, along with control buttons (SET, Up, Down, Power) and protection indicators. Terminal labels for N, L1, L2, L3 (IN and OUT) are also visible.

EARU Electric Voltage Protector Product Features and Terminals

Billede 3.2.2: Et perspektiv view highlighting the product features and the input/output terminals (N, L1, L2, L3) at the top and bottom of the device. This image emphasizes the physical layout and connection points.

4. Opsætning og installation

4.1. Montering

The EARU-1008 is designed for DIN rail mounting. Securely attach the device to a standard 35mm DIN rail within an electrical enclosure.

4.2. Ledningsforbindelser

Refer to the wiring diagram below for correct connections. Ensure all connections are tight and properly insulated.

  1. Connect the incoming neutral (N) and phase lines (L1, L2, L3) to the 'IN' terminals.
  2. Connect the outgoing neutral (N) and phase lines (L1, L2, L3) to the 'OUT' terminals.
  3. Dobbelttjek alle forbindelser, før du tilslutter strøm.
EARU Electric Voltage Protector Wiring Diagram

Billede 4.2.1: Detailed wiring diagram for the EARU Electric Voltage Protector, showing connections for N, L1, L2, L3 for both input and output. The diagram illustrates how to integrate the protector into a 3-phase electrical system.

5. Betjeningsvejledning

5.1. Første opstart

Once wired, apply power to the device. The LED display will illuminate, showing the real-time voltage og strøm for hver fase.

5.2. Displayindikatorer

  • V: Voltage display.
  • A: Aktuelt display.
  • Magt: Output indication.
  • >V: Over-voltage indikation.
  • <V: Under-voltage indikation.
  • > jeg: Over-current indication.

5.3. Indstilling af parametre

Use the 'SET' button to enter the configuration menu and the 'Up' and 'Down' keys to adjust values. Press 'SET' again to confirm and move to the next parameter. Hold 'SET' for 3 seconds to enter settings mode.

EARU Electric Voltage Protector Setting Parameters

Billede 5.3.1: A detailed guide to setting various protection parameters on the EARU Electric Voltage Protector. This includes overvoltage, undervoltage, overcurrent, and recovery delay settings, with default values and adjustment ranges.

Vigtige justerbare parametre inkluderer:

  • Overvoltage beskyttelsesindstilling: Range 230-300V (Default 270V).
  • Overvoltage Protection Recover Setting: Range 225-295V (Default 265V).
  • Overvoltage Genopretningsforsinkelse: Range 1-500s (Default 30s).
  • Overvoltage Tripforsinkelse: Range 0.1-30s (Default 1.0s).
  • Undervoltage beskyttelsesindstilling: Range 140-210V (Default 170V).
  • Undervoltage Protection Recover Setting: Range 145-215V (Default 175V).
  • Undervoltage Tripforsinkelse: Range 0.1-30s (Default 1.0s).
  • Overstrømsbeskyttelsesindstilling: Range 1-63A (Default 30A).
  • Overcurrent Trip Delay: Range 0.1-30s (Default 1.0s).
  • Voltage & Current Manual Error Calibration: Adjust for accuracy, range -9.5% to +9.5% (Default 0%).
  • Power-on Delay Setting: Adjustable Range: 1-500S (Default: 10s).

5.4. Manuel TIL/FRA

The power button allows for manual switching of the device output.

6. Vedligeholdelse

The EARU-1008 is designed for minimal maintenance. However, periodic checks are recommended:

  • Hold enheden ren og fri for støv og snavs.
  • Periodically inspect wiring connections for tightness and signs of wear.
  • Sørg for tilstrækkelig ventilation omkring enheden for at forhindre overophedning.

7. Fejlfinding

Hvis enheden ikke fungerer som forventet, skal du overveje følgende:

  • Intet display/Ingen strøm: Check the main power supply and all wiring connections.
  • Beskyttelsestur: Identify the active protection indicator (>V, <V, >I). Check the corresponding voltage or current levels. The device will automatically reset once conditions return to normal, based on configured recovery delays.
  • Phase Failure: The device automatically detects and responds to phase failures, initiating a cut-off and auto-reset once the phase is restored.
  • Forkerte aflæsninger: If readings appear inaccurate, consider performing a manual error calibration as described in Section 5.3.
EARU Electric Voltage Protector Protection Features

Billede 7.1: This image highlights the various protection features of the EARU Electric Voltage Protector, including phase failure cut-off, low voltage-afskæring, høj lydstyrketage cut-off, overload cut-off, phase sequence cut-off, and auto-reset on normal conditions. These are key aspects for troubleshooting protection trips.

8. Specifikationer

ParameterVærdi
MærkeEARU
ModelEARU-1008
Nominel forsyning VoltageAC 3*220V (N-L1/L2/L3) / 440V
Nominel frekvens50/60Hz
Indstillingsområde for overstrømsbeskyttelse1-63A (Default 30A)
Over Voltage Beskyttelsesindstillingsområde230-300V (Standard 270V)
Under bindtage Beskyttelsesindstillingsområde140-210V (Standard 170V)
Produktdimensioner20 x 10 x 20 cm
Varens vægt450 g
MonteringstypeDIN-skinne
EARU Electric Voltage Protector Dimensions and Technical Specifications

Billede 8.1: This image provides a visual representation of the EARU Electric Voltage Protector's dimensions and a table of key technical specifications, including voltage, frequency, and protection ranges.

9. Garanti og support

9.1. Garanti

The EARU Electric Voltage Protector (Model EARU-1008) comes with a 1 års producentgaranti fra købsdatoen, dækker defekter i materialer og udførelse ved normal brug. Gem venligst din købsbevis i tilfælde af garantikrav.

9.2. Kundesupport

For technical assistance, troubleshooting, or warranty inquiries, please contact EARU customer support through your retailer or the official EARU website. Provide your model number (EARU-1008) and a detailed description of the issue for efficient service.

© 2023 EARU Electric. Alle rettigheder forbeholdes.