VEVOR ACWC/5TON

VEVOR ACWC/5TON Air Cooled Water Chiller Instruction Manual

Model: ACWC/5TON

1. Introduktion

This manual provides essential information for the safe and efficient installation, operation, and maintenance of your VEVOR ACWC/5TON Air Cooled Water Chiller. Please read this manual thoroughly before operating the unit and retain it for future reference. Proper understanding and adherence to these instructions will ensure optimal performance and longevity of your chiller.

2. Sikkerhedsoplysninger

ADVARSEL: Manglende overholdelse af disse sikkerhedsinstruktioner kan resultere i alvorlig personskade, død eller materielle skader.

  • Afbryd altid strømmen, før du udfører vedligeholdelse eller service.
  • Sørg for, at enheden er korrekt jordforbundet for at forhindre elektrisk stød.
  • Brug ikke køleren med beskadigede netledninger eller stik.
  • Keep hands and clothing clear of moving parts, especially fans.
  • Sørg for tilstrækkelig ventilation omkring enheden for at forhindre overophedning.
  • Bloker ikke luftindtag eller -udtag.
  • Use only clean, non-corrosive water in the system.
  • Refer to local codes and regulations for installation and electrical connections.

3. Produktfunktioner

The VEVOR ACWC/5TON Air Cooled Water Chiller is designed for reliable industrial cooling applications. Key features include:

  • High-Performance & Stable Cooling Core: Equipped with a 5HP Panasonic compressor for consistent and efficient operation. Features a DN1 in / DN25 mm circulation pipeline with 58L/min water flow, minimizing vibration and noise. A 53L food-grade stainless steel water tank provides reliable cooling with an easy-to-maintain modular design.
  • Powerful & Long-Lasting Cooling System: The 3.75kW cooling core delivers an impressive 12,900 kcal/h cooling capacity. The sealed water reservoir reduces evaporation, allowing for extended operation with fewer refills, maximizing efficiency and convenience.
  • Advanced Security Safeguard: Features overload current protection, automatic power-off for abnormal pressure, audible & visual alarms, and an intelligent water replenishment system. The temperature control module ensures stable performance in ambient temperatures up to 40°C.
  • Smart Touch Control Interface: Integrated with a touchscreen panel and microprocessor control system, enabling precise 5-25°C temperature regulation. The intuitive button layout with dedicated mode selection and start/stop keys simplifies operation, improving user efficiency.
  • Versatile Industrial Applications: Suitable for semiconductor manufacturing, surface treatment, precision machining, and more. In injection molding, precise mold temperature control enhances production efficiency, making it an essential component for modern smart manufacturing lines.

4. Opsætning

4.1 Udpakning og inspektion

Carefully remove the chiller from its packaging. Inspect the unit for any signs of shipping damage. Report any damage to your carrier and supplier immediately. Ensure all components listed in the packing list are present.

4.2 Placering

Place the chiller on a level, stable surface capable of supporting its weight (approximately 397 lbs / 180 kg). Ensure there is ample space around the unit for proper airflow and ventilation. Avoid placing the unit in direct sunlight or near heat sources. Maintain at least 30 cm (12 inches) clearance on all sides for optimal performance.

VEVOR ACWC/5TON Air Cooled Water Chiller, front view

Figur 1: Forside view of the VEVOR ACWC/5TON Air Cooled Water Chiller, showing its compact design and casters for portability.

4.3 Elektrisk tilslutning

Connect the chiller to a dedicated power supply that matches the voltage and frequency requirements specified on the unit's nameplate. Ensure the circuit is protected by an appropriate circuit breaker and that the unit is properly grounded. Consult a qualified electrician if you are unsure about electrical connections.

4.4 Vandtilslutning

Connect the water inlet and outlet ports to your application using appropriate plumbing. The chiller features a 53L stainless steel water tank. Fill the tank with clean, deionized, or distilled water. Avoid using tap water directly, as minerals can cause scaling and reduce efficiency. Ensure all connections are secure and leak-free.

VEVOR Air Cooled Chiller with visible water connections

Figur 2: Side view of the chiller, highlighting the water inlet and outlet connections for integration into an industrial cooling system.

5. Betjeningsvejledning

5.1 Kontrolpanel overview

The chiller is equipped with a smart touch control interface for easy operation. The panel displays current temperature, set temperature, and operational status. It includes buttons for mode selection, temperature adjustment, and start/stop functions.

VEVOR Industrial Chiller control panel with LED display

Figure 3: Close-up of the multifunctional LED control panel, showing temperature display and control buttons.

5.2 Tænd/sluk

To power on the unit, press the 'Power' button on the control panel. The system will initiate a self-check. To power off, press and hold the 'Power' button until the unit shuts down.

5.3 Temperaturindstilling

Use the 'Up' and 'Down' arrows on the control panel to adjust the desired water temperature. The chiller allows for precise temperature regulation between 5°C and 25°C (41°F - 77°F). Confirm your selection to save the setting.

5.4 Monitoring and Alarms

Regularly monitor the temperature display. The chiller features an advanced security safeguard system with audible and visual alarms for conditions such as overload current, abnormal pressure, and low water levels. Refer to the troubleshooting section if an alarm is triggered.

6. Vedligeholdelse

Regular maintenance is crucial for the efficient and long-term operation of your chiller.

6.1 Rengøring af kondensatoren

The finned condenser requires periodic cleaning to ensure optimal heat dissipation. Disconnect power and use a soft brush or compressed air to remove dust and debris from the condenser fins. Frequency depends on the operating environment.

Indre view of VEVOR Chiller showing compressor and finned condenser

Figure 4: Internal components, including the finned condenser, which requires regular cleaning for efficient operation.

6.2 Water Quality and Replenishment

Check the water level in the tank regularly. The intelligent water replenishment system will alert you to low levels. Use only clean, deionized, or distilled water for replenishment. Periodically drain and refill the water tank to maintain water quality and prevent algae growth or mineral buildup.

6.3 Generelt eftersyn

Periodically inspect all hoses, connections, and electrical wiring for wear, leaks, or damage. Tighten any loose connections. Ensure the casters are clean and move freely if the unit needs to be relocated.

7. Fejlfinding

This section outlines common issues and their potential solutions. For problems not listed here, contact customer support.

ProblemMulig årsagLøsning
Chiller køler ikkeLow refrigerant, dirty condenser, insufficient water flow, incorrect temperature setting.Check refrigerant levels (professional service), clean condenser, verify water pump operation and connections, adjust temperature setting.
Enheden tændes ikkeNo power supply, tripped circuit breaker, faulty power cord.Kontroller strømtilslutningen, nulstil afbryderen, og inspicer netledningen for skader.
VandlækageLoose connections, damaged hoses, tank crack.Tighten all water connections, inspect hoses for damage and replace if necessary, check water tank for cracks.
HøjtryksalarmDirty condenser, insufficient airflow, overcharge of refrigerant.Clean condenser, ensure proper ventilation, consult professional for refrigerant check.
LavtryksalarmLow refrigerant, water flow issues.Consult professional for refrigerant check, verify water pump operation and connections.

8. Specifikationer

Detailed technical specifications for the VEVOR ACWC/5TON Air Cooled Water Chiller:

FeatureSpecifikation
MærkeVEVOR
ModelnavnAir Cooled Water Chiller
ModelnummerACWC/5TON
Kølekapacitet5 Ton / 12,900 kcal/h
Kompressor motor5HP / 3.75KW Panasonic
Reservoirkapacitet53 liter (rustfrit stål)
Vandflow58 l/min
Temperaturkontrolområde5-25°C (41-77°F)
Maks. Omgivelsestemperatur40°C (104°F)
KontroltypeTouch / Microprocessor
MaterialeRustfrit stål
Varens vægt397 pund / 180 kg
Varedimensioner (D x B x H)78"D x 33"W x 72"H (Approx. 110 x 55 x 130 cm)
Wattage3750 watt
UPC197988857907
VEVOR ACWC/5TON Air Cooled Water Chiller dimensions diagram

Figure 5: Dimensional diagram of the VEVOR ACWC/5TON Air Cooled Water Chiller, showing height, width, and depth measurements.

9. Garanti og support

9.1 Garantioplysninger

This VEVOR Air Cooled Water Chiller comes with a 1 års fabriksgaranti. This warranty covers defects in materials and workmanship under normal use. Please retain your proof of purchase for warranty claims. The warranty does not cover damage caused by improper installation, misuse, neglect, or unauthorized modifications.

9.2 Kundesupport

For technical assistance, troubleshooting guidance, or warranty inquiries, please contact VEVOR customer support. You can typically find contact information on the VEVOR official website or through your purchase platform. When contacting support, please have your model number (ACWC/5TON) and purchase date ready.

© 2026 VEVOR. Alle rettigheder forbeholdes.