Rakstore XY-MD02 SHT20 Temperature and Humidity Transmitter Module User Manual

Model: XY-MD02

1. Produktet er slutview

The Rakstore XY-MD02 is an industrial-grade temperature and humidity transmitter module. It integrates a high-precision SHT20 sensor and communicates via RS485 using the Modbus-RTU protocol. This module is designed for reliable and accurate environmental monitoring in various applications.

Nøglefunktioner:

  • Industrial-grade chip and SHT20 sensor for high reliability and precision.
  • RS485 output signal.
  • Supports Modbus-RTU protocol and custom common protocol.
  • Wide power supply range: DC 5V-30V.
  • Temperature accuracy: ±0.5℃ (at 25℃).
  • Humidity accuracy: ±3%RH.

2. Pakkens indhold

Når du åbner pakken, skal du kontrollere, at alle komponenter er til stede og ubeskadigede.

  • 1 x XY-MD02 Temperature and Humidity Transmitter Module

Hvis der mangler eller er beskadigede varer, bedes du kontakte kundesupport.

3. Specifikationer

ParameterVærdi
ModelXY-MD02
SensortypeSHT20
StrømforsyningDC 5V-30V
UdgangssignalRS485
KommunikationsprotokolModbus-RTU, Custom Common Protocol
Temperatur nøjagtighed±0.5℃ (at 25℃)
Fugtighedsnøjagtighed± 3% RH
Dimensioner66 mm x 46 mm x 29 mm (omtrentligt)

4. Opsætning og installation

4.1 Fysisk installation

The XY-MD02 module supports standard 35mm DIN rail installation. Ensure the module is securely clipped onto the DIN rail in a location free from excessive vibration, direct sunlight, or extreme temperatures.

XY-MD02 module showing 35mm DIN rail installation clips

Figure 1: Standard 35mm DIN rail installation. The module features clips for easy mounting onto a DIN35 guide rail.

XY-MD02 module with dimensions labeled

Figure 2: Dimensions of the XY-MD02 module, approximately 66mm x 46mm x 29mm.

4.2 Ledningsdiagram

Connect the module according to the following wiring diagram. Ensure correct polarity for the power supply and proper connection for the RS485 communication lines.

Wiring diagram for XY-MD02 module showing power and RS485 connections

Figure 3: Wiring connections for the XY-MD02 module. Connect DC 5-30V to '+' and '-' terminals, and RS485 A+ and B- to their respective terminals.

  • DC 5-30V: Connect the positive (+) and negative (-) terminals of your DC power supply.
  • RS485 A+: Connect to the A+ line of your RS485 network.
  • RS485 B-: Connect to the B- line of your RS485 network.

Caution: Incorrect wiring can damage the module. Always verify connections before applying power.

5. Betjeningsvejledning

5.1 Kommunikationsprotokol

The XY-MD02 module supports the Modbus-RTU protocol. For detailed register addresses and communication commands, refer to the Modbus-RTU protocol documentation specific to this module (typically provided separately or available for download from the manufacturer).

General Modbus-RTU Parameters:

  • Baudrate: Typically 9600 bps (configurable).
  • Databits: 8.
  • Stopbits: 1.
  • Paritet: None (configurable).
  • Slave adresse: Typically 1 (configurable).

The module will begin transmitting temperature and humidity data over the RS485 bus once powered and correctly configured.

5.2 Dataaflæsning

To read temperature and humidity data, send Modbus-RTU read holding registers (Function Code 0x03) or read input registers (Function Code 0x04) commands to the module's slave address. The specific register addresses for temperature and humidity values will be outlined in the detailed protocol documentation.

Example (conceptual):

  • Temperature Register: Address X (e.g., 0x0001)
  • Humidity Register: Address Y (e.g., 0x0002)

The returned values will typically be integer representations that need to be scaled (e.g., divided by 10 or 100) to obtain the actual temperature in ℃ and humidity in %RH.

6. Vedligeholdelse

The XY-MD02 module is designed for low maintenance. However, periodic checks can ensure optimal performance:

  • Rensning: Keep the sensor area free from dust and debris. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.
  • Forbindelser: Kontrollér jævnligt ledningsforbindelserne for at sikre, at de er fastgjorte og fri for korrosion.
  • Miljø: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent sensor degradation.

Warning: Do not attempt to open the module casing, da det kan ugyldiggøre garantien og udsætte interne komponenter for skade.

7. Fejlfinding

ProblemMulig årsagLøsning
No power indicator / Module not respondingForkert strømforsyning voltage or polarity; Loose power connection.Verify power supply is within DC 5V-30V. Check wiring for correct polarity (+/-). Ensure connections are secure.
No data received via RS485Incorrect RS485 wiring (A+/B- reversed); Incorrect communication parameters (baud rate, parity, stop bits); Incorrect slave address; RS485 bus termination issues.Check A+ and B- wiring. Verify communication parameters match the module's settings. Ensure the correct slave address is used. Add or check termination resistors if on a long bus.
Unøjagtige aflæsningerSensor obstructed or dirty; Module exposed to extreme conditions; Sensor damage.Clean the sensor area. Relocate the module to a more stable environment. If issues persist, the sensor may be damaged and require replacement.

8. Garanti og support

This Rakstore XY-MD02 module comes with a standard manufacturer's warranty. Please refer to your purchase documentation or contact your retailer for specific warranty terms and conditions.

For technical support, troubleshooting assistance, or inquiries regarding the Modbus-RTU protocol documentation, please contact Rakstore customer service or visit their official webwebsted.

Fabrikant: RAKSTORE

Dato først tilgængelig: 20. marts 2024

© 2024 Rakstore. All rights reserved.