GEYA GRT8-B2

GEYA GRT8-B2 Delay Off Single Function Time Relay

Instruktionsmanual

1. Sikkerhedsoplysninger

Please read this manual carefully before installation and operation. Failure to follow these instructions may result in equipment damage, injury, or death. Keep this manual for future reference.

  • Elektrisk fare: Installation and maintenance must be performed by qualified personnel only. Disconnect all power before working on the device.
  • Voltage Kompatibilitet: Sørg for, at forsyningen voltage matches the device's specifications (AC230V for this model).
  • Korrekt ledningsføring: Use appropriate wire gauges and ensure all connections are secure to prevent overheating or short circuits.
  • Miljø: Udsæt ikke enheden for fugt, ekstreme temperaturer eller ætsende miljøer.

2. Produktet er slutview

The GEYA GRT8-B2 is a single-function electronic time relay designed for delay-off applications. It features two SPDT (Single Pole Double Throw) output contacts and offers a wide range of adjustable time settings. This relay is suitable for DIN rail mounting and provides visual indication of its status via LED indicators.

Nøglefunktioner:

  • Delay can be set directly via panel knobs for convenience.
  • Function Mode: Delay OFF (Type B).
  • Time scale: 0.1s - 10 days, divided into 10 ranges.
  • Forsyning voltage: AC230V.
  • Output contact: 2 SPDT (2NO2NC).
  • Relæstatus angivet med LED.
  • 1-MODUL, DIN-skinnemontering.
  • Ultra-small size: 18mm width.

Komponentidentifikation:

The image below illustrates the main components and terminals of the GRT8-B2 time relay.

GEYA GRT8-B2 Time Relay Component Identification

Figur 2.1: Front view of the GEYA GRT8-B2 time relay, showing the trigger terminal (A1, S, A2), supply terminal (Un), LED indicators (Green for Supply, Red for Output), 10 time range selection knob, time percentage setting knob, and output contacts (15, 16, 18 for 1SPDT; 25, 26, 28 for 2SPDT).

3. Opsætning og installation

Montering:

The GRT8-B2 time relay is designed for DIN rail mounting. Ensure the DIN rail is securely installed in a suitable enclosure, away from excessive heat, moisture, and vibration.

Ledningsdiagram:

Refer to the wiring diagrams below for proper connection of the time relay. Always ensure power is disconnected before making any connections.

GEYA GRT8-B2 Wiring Diagram and Dimensions

Figur 3.1: Wiring diagram for GRT8-B2 (2SPDT) showing connections for supply voltage (Un), trigger (S), and output contacts (15-16-18 and 25-26-28). Also includes physical dimensions.

GEYA GRT8-B2 Example Ledningsdiagram

Figur 3.2: Example wiring diagram for GRT8-B2 showing connection to a trigger switch and a load (signal light). Terminals 15-18 (NO) close on power-on and disconnect after delay. Terminals 15-16 (NC) disconnect on power-on and close after delay.

Terminalforbindelser:

  • A1(+), A2(-): Forsyning voltage input (AC230V).
  • S: Trigger terminal for external control (e.g., push button).
  • 15, 16, 18: First SPDT output contact. 15 is common, 16 is normally closed (NC), 18 is normally open (NO).
  • 25, 26, 28: Second SPDT output contact. 25 is common, 26 is normally closed (NC), 28 is normally open (NO).

4. Betjeningsvejledning

The GRT8-B2 operates in Delay OFF mode (Function B). This means that upon receiving a trigger or power-on, the output contacts will immediately change state, and then revert to their original state after a set delay time.

Tidsindstilling:

The delay time is set using two rotary knobs on the front panel:

GEYA GRT8-B2 Time Setting Knobs and Ranges

Figur 4.1: Time setting knobs. Knob 1 selects the delay gear (s, m, h, d, ON, OFF). Knob 2 provides fine adjustment of the delay time from 10% to 100% within the selected range.

  • Knob 1 (Time Range Selection): Selects the base time unit (seconds, minutes, hours, days) and the maximum value within that unit. Available ranges include: 0.1-1s, 1-10s, 6-60s, 1-10min, 6-60min, 1-10hr, 0.1-1day, 1-10day. There are also 'only ON' and 'only OFF' settings for continuous operation or immediate disconnection.
  • Knob 2 (Time Percentage Setting %): Adjusts the delay time as a percentage (10% to 100%) of the selected time range.

Exampdet: To set a 5-minute delay, select the '10m' range with Knob 1 and set Knob 2 to '50%'.

Function Mode B (Delay OFF):

In Delay OFF mode, when power is applied or the trigger (S terminal) is activated, the load connected to the relay's output contacts (e.g., 15-18) will turn ON immediately. After the set delay time has elapsed, the load will turn OFF. If the trigger is held during the delay, the load remains ON until the trigger is released, then the delay starts.

GEYA Delay ON and Delay OFF Function Explanation

Figur 4.2: Illustration of Delay ON (A) and Delay OFF (B) functions. For Delay OFF (B), after power-up, the light turns on and the relay begins to delay. After the set time (e.g., 10 seconds), the light will turn off.

Operationel demonstration:

Watch the video below for a practical demonstration of how to use a GEYA GRT8-B1 (similar to GRT8-B2) off-delay time relay.

Video 4.1: A demonstration of the GEYA GRT8-B1 off-delay time relay. The video shows setting the delay, applying power, and observing the load's behavior (light turning on immediately and then off after the delay). It also demonstrates the effect of holding down a reset button during the timing delay.

5. Vedligeholdelse

The GEYA GRT8-B2 time relay is designed for reliable operation with minimal maintenance. However, regular checks can help ensure its longevity and proper function.

  • Visuel inspektion: Undersøg relæet regelmæssigt for tegn på fysisk skade, misfarvning eller løse forbindelser.
  • Terminaltæthed: Ensure all screw terminals remain tight to prevent intermittent connections or overheating.
  • Rensning: Rengør om nødvendigt forsigtigt enhedens yderside med en tør, blød klud. Brug ikke slibende rengøringsmidler eller opløsningsmidler.
  • Miljøforhold: Kontroller, at driftsmiljøet holder sig inden for de angivne temperatur- og fugtighedsområder.

6. Fejlfinding

If the GEYA GRT8-B2 time relay is not functioning as expected, consider the following common issues and solutions:

ProblemMulig årsagLøsning
Relay does not activate (LEDs off)No power supply; Incorrect wiring; Faulty unit.Kontroller forsyningsvolumentage at A1/A2 terminals; Verify wiring according to diagram; Replace unit if faulty.
Load does not switch after delayIncorrect time setting; Faulty load; Incorrect output wiring.Adjust time range and percentage knobs; Test the load independently; Verify output contact wiring (NO/NC).
Delay time is inaccurateIncorrect time range/percentage indstilling.Carefully re-adjust both time setting knobs.
Relay continuously ON/OFFKnob 1 set to 'only ON' or 'only OFF'.Adjust Knob 1 to a specific time range.

7. Tekniske specifikationer

Below are the detailed technical specifications for the GEYA GRT8-B2 Delay Off Single Function Time Relay (AC230V model).

GEYA GRT8-B2 Technical Specifications Table

Figur 7.1: Detailed technical parameter table for GRT8-A1/B1 and GRT8-A2/B2 models, highlighting the AC230V specifications.

ParameterVærdi
FungereB: Delay OFF
ForsyningsterminalerA1-A2
VoltagRækkeviddeAC230V (50-60Hz)
StrømindgangAC max. 6VA / 1.9W
Forsyning Voltage Tolerance-15%; +10%
Supply IndicationGrøn LED
Tidsintervaller0.1s - 10 days, ON, OFF
TidsindstillingPotentiometer
Time Deviation10% - mechanical setting
Gentag nøjagtighed0.2% - set value stability
Temperaturkoefficient0.05%/°C, at=20°C (0.05%/°F, at=68°F)
Produktion2xSPDT
Nuværende vurdering2x16A (AC1)
Switching Voltage250VAC / 24VDC
Min. Breaking Capacity DC500mW
UdgangsindikationRød LED
Mekanisk liv1x107
Elektrisk levetid (AC1)1x105
Nulstil tidmax. 200ms
Driftstemperatur-20°C til +55°C (-4°F til 131°F)
Opbevaringstemperatur-35°C til +75°C (-22°F til 158°F)
MonteringDIN-skinne EN/IEC 60715
BeskyttelsesgradIP40 for front panel / IP20 terminals
DriftspositionEnhver
Overvoltage kategoriIII
Forureningsgrad2
Max. Cable Size (mm²)Solid wire max. 1x2.5 or 2x1.5 / with sleeve max. 1x2.5 (AWG 12)
Dimensioner90x18x64 mm
StandarderEN 61812-1, IEC6947-5-1

8. Garanti og support

Garantioplysninger:

GEYA products are manufactured to high-quality standards and are covered by a limited warranty against defects in materials and workmanship. Please refer to the warranty card included with your product or visit the official GEYA webhjemmeside for detaljerede garantivilkår.

Kundesupport:

For technical assistance, troubleshooting, or product inquiries, please contact GEYA customer support through the following channels:

  • Online: Visit the official GEYA webwebsted med ofte stillede spørgsmål, produktdokumentation og kontaktformularer.
  • E-mail: Refer to your product packaging or the GEYA webwebstedet for den relevante support-e-mailadresse.
  • Telefon: Contact numbers for regional support may be available on the GEYA webwebsted.

When contacting support, please have your product model number (GRT8-B2) and purchase information ready.