ABB S203-B16
ABB S203-B16 miniatureafbryder brugermanual
Model: S203-B16
1. Produktet er slutview
The ABB S203-B16 is a low voltage, 3-pole miniature circuit breaker designed for equipment protection. It features a 480Y/277 VAC voltage rating, a 16 A amperage rating, and an interrupt rating of 6 kA.
This device incorporates thermal/magnetic trip mechanisms for reliable overcurrent fault protection in various applications, including commercial appliances, control circuits, and computer equipment.

Figur 1: Forside view of the ABB S203-B16 Miniature Circuit Breaker, showing the toggle switch and model markings.
2. Sikkerhedsoplysninger
Always adhere to local electrical codes and regulations during installation and operation. Installation should only be performed by qualified personnel.
- Sørg for, at strømmen er afbrudt før installation eller vedligeholdelse.
- Betjen ikke afbryderen, hvis den ser ud til at være beskadiget.
- Brug passende personlige værnemidler (PPE).
- Refer to the wiring diagrams for correct connections.
3. Opsætning og installation
The S203-B16 circuit breaker is designed for DIN-rail mounting.
- Montering: Securely attach the circuit breaker to a standard DIN-rail. Ensure the mounting clip engages properly.
- Ledningsføring: Connect the electrical conductors to the screw terminals. The wire size supported is 18 - 4 AWG for conductors and 18 - 8 AWG for busbars.
- Terminalstramning: Sørg for, at alle skrueterminaler er spændt til det angivne moment for at forhindre løse forbindelser og overophedning.

Figur 2: Bagside view illustrating the DIN-rail mounting mechanism.

Figur 3: Øverst view showing the input terminals of the circuit breaker.

Figur 4: Nederst view showing the output terminals of the circuit breaker.
4. Betjeningsvejledning
The ABB S203-B16 circuit breaker is operated via a toggle actuator.
- At tænde: Push the toggle actuator upwards to the "ON" position.
- At slukke: Push the toggle actuator downwards to the "OFF" position.
- Tripindikation: In case of an overcurrent or short circuit, the toggle actuator will automatically move to an intermediate "TRIPPED" position.
- Resetting After Trip: To reset the circuit breaker after a trip, first move the toggle completely to the "OFF" position, then push it upwards to the "ON" position. Investigate the cause of the trip before resetting.
5. Vedligeholdelse
The ABB S203-B16 circuit breaker requires minimal maintenance. Regular inspections are recommended to ensure proper function and safety.
- Visuel inspektion: Undersøg regelmæssigt afbryderen for tegn på fysisk skade, misfarvning eller løse forbindelser.
- Rensning: If necessary, clean the exterior of the circuit breaker with a dry, lint-free cloth. Do not use abrasive cleaners or solvents.
- Terminaltjek: Verify that all terminal connections remain tight.
- Miljøforhold: Ensure the operating environment remains within the specified temperature range (-25 to 55 deg C) and IP20 enclosure rating.
6. Fejlfinding
| Problem | Mulig årsag | Løsning |
|---|---|---|
| Afbryderen udløses ofte. | Overload, short circuit, or faulty appliance/wiring. | Reduce load, check for short circuits, inspect connected equipment and wiring. |
| Afbryderen nulstilles ikke. | Persistent fault, internal damage. | Ensure the fault is cleared. If it still doesn't reset, the unit may be damaged and require replacement. Consult a qualified electrician. |
| Afbryderen føles varm. | Overbelastning, løse forbindelser eller intern fejl. | Reduce load, check terminal tightness, or replace the unit if overheating persists without apparent cause. |
If troubleshooting steps do not resolve the issue, contact a qualified electrician or ABB customer support.
7. Specifikationer
| Feature | Detalje |
|---|---|
| Model | S203-B16 |
| Type | Lav voltage Miniature Circuit Breaker |
| Antal poler | 3 |
| Voltage Bedømmelse | 480Y/277 VAC |
| Ampaldersbedømmelse | 16 A |
| Frekvensvurdering | 50/60 Hz |
| Afbryd vurdering | 6 kA |
| Rejsetype | Thermal/Magnetic |
| Trip Range | 3 - 5 A Magnetic and 1.13 - 1.45 A Thermal |
| Aktuator type | Skift |
| Trådstørrelse | 18 - 4 AWG Conductor, 18 - 8 AWG Busbar |
| Terminaltype | Skrue |
| Indkapslingstype | IP20 |
| Monteringstype | DIN-skinne |
| Temperatur vurdering | -25 til 55 grader C |
| Dimensioner | 88 mm Height x 52-1/2 mm Width x 69 mm Depth |
| Materiale | Støbt plast |
| Standards/Approvals | IEC/EN 60898-1, IEC/EN 60947-2, UL 1077, CSA 22.2 |

Figur 5: Side view displaying product specifications and international certifications.

Figur 6: Side view showing the product barcode and manufacturing details.
8. Garantioplysninger
For detailed warranty information regarding your ABB S203-B16 Miniature Circuit Breaker, please refer to the official ABB warranty policy available on the manufacturer's website or contact ABB customer service directly. Keep your purchase receipt as proof of purchase.
9. Kundesupport
If you require technical assistance, have questions about installation, operation, or maintenance, please contact ABB customer support.
- ABB Official Webwebsted: www.abb.com
- Teknisk support: Refer to the support section on the ABB website for contact numbers and online resources specific to your region.