Watt Stopper CX-105-3

Watt Stopper CX-105-3 Passive Infrared Occupancy Sensor User Manual

Model: CX-105-3

1. Introduktion

This manual provides essential information for the proper installation, operation, and maintenance of the Watt Stopper CX-105-3 Passive Infrared (PIR) Occupancy Sensor. Please read these instructions carefully before installation and retain this manual for future reference. The CX-105-3 is designed to detect occupancy in a given area and automatically control lighting or other electrical loads, contributing to energy efficiency.

2. Sikkerhedsoplysninger

ADVARSEL: Risiko for elektrisk stød.

  • Installationen skal udføres af en kvalificeret elektriker i overensstemmelse med alle nationale og lokale el-forskrifter.
  • Always disconnect power at the circuit breaker or fuse before installing or servicing the sensor.
  • Sørg for, at alle ledningsforbindelser er sikre og korrekt isolerede.
  • Må ikke installeres i vådt eller damp steder, medmindre de specifikt er godkendt til sådanne miljøer.

3. Produktet er slutview

The Watt Stopper CX-105-3 is a 24 VDC/VAC Passive Infrared Occupancy Sensor designed for ceiling or wall mount applications. It features a dual-element, temperature-regulated pyroelectric sensor for reliable motion detection and a two-sided aisleway lens for optimized coverage patterns.

Nøglefunktioner:

  • Strømbehov: Operates with a 24 VDC/VAC power pack (e.g., BZ-150, sold separately).
  • Automatisk tænd/sluk: Provides automatic lighting control, with options for auto or manual-on when used with compatible power packs.
  • Sensortype: Dual Element, Temperature Regulated pyroelectric sensor for enhanced accuracy.
  • Dækning: Offers 360-degree coverage, suitable for various room layouts.
  • Justerbare indstillinger: User-adjustable time delay and sensitivity to customize performance.
Watt Stopper CX-105-3 Passive Infrared Occupancy Sensor

Figure 1: Watt Stopper CX-105-3 Passive Infrared Occupancy Sensor. This image shows the compact, white housing of the sensor, typically mounted on a ceiling or wall.

4. Installation

The CX-105-3 sensor is designed for either ceiling or wall mounting. Proper placement is crucial for optimal performance.

4.1 Kontrol før installation

  • Sørg for, at strømmen er afbrudt ved afbryderen.
  • Verify that a compatible 24 VDC/VAC power pack (e.g., Watt Stopper BZ-150) is available and correctly installed. The sensor requires this external power pack for operation.
  • Vælg et monteringssted, der giver en uhindret view of the area to be monitored. Avoid placing the sensor near heat sources, air vents, or direct sunlight, which can cause false triggers.

4.2 Montering

  1. Carefully remove the sensor cover to access the mounting holes and wiring terminals.
  2. Mount the sensor securely to the ceiling or wall using appropriate screws and anchors (not included). Ensure the sensor is level.
  3. Route the low-voltage wiring from the power pack to the sensor.

4.3 Ledningsføring

Connect the sensor to the 24 VDC/VAC power pack according to the wiring diagram provided with the power pack. Typically, this involves connecting the sensor's low-voltage wires to the corresponding terminals on the power pack. Refer to the power pack's instruction manual for specific wiring details.

4.4 Efterinstallation

  1. Replace the sensor cover, ensuring it is securely fastened.
  2. Gendan strømmen ved afbryderen.
  3. Allow a brief warm-up period (typically 30-60 seconds) for the sensor to stabilize.

5. Betjening

Once installed and powered, the CX-105-3 sensor will begin detecting motion within its 360-degree coverage area. When occupancy is detected, the sensor signals the connected power pack to activate the controlled load (e.g., turn on lights). When no motion is detected for a user-adjustable time delay, the sensor signals the power pack to deactivate the load.

5.1 Justering af indstillinger

The CX-105-3 features user-adjustable settings for time delay and sensitivity. These adjustments are typically made via potentiometers or dip switches located on the sensor itself, often accessible by removing the sensor cover. Refer to the specific markings on your sensor for adjustment details.

  • Tidsforsinkelse: Sets the duration the load remains ON after the last detected motion. Adjust this to prevent lights from turning off too quickly in occupied spaces.
  • Følsomhed: Determines how easily the sensor detects motion. Higher sensitivity detects smaller movements but may increase false triggers. Lower sensitivity requires more significant motion but reduces false triggers.

6. Vedligeholdelse

The Watt Stopper CX-105-3 sensor requires minimal maintenance to ensure continued optimal performance.

  • Rensning: Periodically wipe the sensor lens with a soft, dry cloth to remove dust or debris. Do not use abrasive cleaners or solvents, as these can damage the lens.
  • Inspektion: Occasionally inspect the sensor for any physical damage or loose connections.

No user-serviceable parts are inside the sensor. For any repairs, contact qualified service personnel.

7. Fejlfinding

Hvis sensoren ikke fungerer som forventet, skal duview følgende almindelige problemer og løsninger:

ProblemMulig årsagLøsning
Lysene tændes ikke ved bevægelse.
  • No power to sensor/power pack.
  • Forkert ledningsføring.
  • Sensorlinse blokeret.
  • Følsomhed indstillet for lavt.
  • Check circuit breaker and power pack connections.
  • Verify wiring against power pack diagram.
  • Fjern eventuelle forhindringer fra sensorens view.
  • Øg sensorfølsomheden.
Lights remain ON or turn ON without motion (false triggers).
  • Sensor detecting unwanted motion.
  • Heat sources or air currents in detection zone.
  • Følsomhed indstillet for højt.
  • Adjust sensor placement or coverage.
  • Relocate sensor away from heat sources/vents.
  • Reducer sensorfølsomheden.
Lysene slukker for hurtigt.
  • Tidsforsinkelsen er indstillet for kort.
  • Sensor not detecting subtle motion.
  • Increase the time delay setting.
  • Increase sensor sensitivity or adjust placement.

If problems persist after attempting these solutions, contact Watt Stopper technical support or a qualified electrician.

8. Specifikationer

AttributVærdi
ModelnummerCX-105-3
FabrikantWattstopper
StrømkildeKablet elektrisk
Voltage24 Volts (VDC/VAC)
MonteringstypeLoftmontering, Vægmontering
SensortypePassive Infrared (PIR), Dual Element, Temperature Regulated
Dækning360 grader
FarveHvid
Varens vægt1 pund
Pakkedimensioner5.16 x 2.72 x 2.68 tommer
Batterier påkrævetIngen

9. Garanti og support

For information regarding the product warranty, please refer to the documentation provided with your purchase or visit the official Watt Stopper website. For technical support, installation assistance, or troubleshooting beyond the scope of this manual, please contact Watt Stopper customer service directly.

Kontaktoplysninger: Se venligst producentens officielle webwebstedet eller produktemballagen for de mest aktuelle kontaktoplysninger.

© 2024 Watt Stopper. All rights reserved.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.